Fluke i310s Current Probe
Model#: i310s
āļāļļāļāļĨāļąāļāļĐāļāļ°āļŠāļģāļāļąāļ
- Current Ranges: 30 A and 300 A ACRMSÂ or Âą45 A and 450 A DC
- Measuring Ranges: Âą45 A and 450 AÂ dc
- Output Sensitivity: 10 mV/A (40 A) to 1 mV/A (400 A)
- Resolution: Âą50 mA (40 A) to Âą100 mA (400 A)
- Load Impedance: > 10 k Ohms and ÂĢ 100 pF
- Frequency Range (small signal): DC to 20 kHz (- 3 dB)
- Phase Shift below 1 kHz, < 2 degrees
- Temperature Coefficient: ¹0.1% of reading / °C
- Power Supply: 9 V Alkaline
āļ āļēāļāļĢāļ§āļĄāļāļĨāļīāļāļ āļąāļāļāđ: Fluke i310s Current Probe
The i310s current probe is based on Hall Effect technology for use in measurement of both DC and AC current. The i310s may be used in conjunction with oscilloscopes and other suitable recording instruments for accurate non-intrusive current measurement.
āļāđāļāļĄāļđāļĨāļāļģāđāļāļēāļ°: Fluke i310s Current Probe
| Electrical Characteristics | ||
| Current ranges | 30 A and 300 A AC rms or Âą45 A and 450 A DC | |
| Measuring ranges | Âą45 A and 450 A DC | |
| AC rms or DC | Âą45 A and 450 A | |
| Inrush current | 600A AC rms MAX | |
| Output sensitivity | 10 mV/A (30 A) | |
| 1 mV/A (300 A) | ||
| Accuracy (at +23°C) | (30 A range) | ¹1% of reading ¹50 mA |
| (300 A range) | Âą1% of reading Âą300 mA | |
| Bandwidth to meet accuracy specification | 1 kHz | |
| Phase shift below 1 kHz | < 2 degrees | |
| Resolution | Âą50 mA (30 A) | |
| Âą100 mA (300 A) | ||
| Load impedance | > 10 k Ohms and âĪ100 pF | |
| Conductor position sensitivity | Âą1.5% relative to centre reading | |
| Frequency range (small signal) | DC to 20 kHz (-3 dB) | |
| Phase shift below 1 kHz | < 2° | |
| Temperature coefficient | ¹0.1% of reading / °C | |
| Power supply | 9 V Alkaline, MN1604/PP3 | |
| Battery life | 30 Hours, low battery indicator | |
| Working voltage (see Safety Standards section) | 300 V AC rms or DC | |
| General Characteristics | ||
| Maximum conductor size | 19 mm diameter | |
| Output connection | Safety BNC connector | |
| Supplied with safety 4mm adaptor | ||
| Output zero | Manual adjust via thumbwheel | |
| Cable length | 2 metres | |
| Operating temperature range | -10 to +50°C | |
| Storage temperature range (with battery removed) | -20 to +85°C | |
| Operating humidity | 15% to 85% (non-condensing) | |
| Weight | 250 g | |
| Safety | IEC 61010-1, Pollution Degree 2 | |
| IEC 61010-2- 032: CAT III 300V | ||
| Use of the probe on uninsulated conductors is limited to 300 V ac rms or dc and frequencies below 1 kHz. | ||
| EMC Compatibility | IEC 61326-1: Portable Electromagnetic Environment | |
āļĢāļļāđāļ: Fluke i310s Current Probe
i310s
AC/DC CURRENT CLAMP