Fluke i3000s Flex-36 AC Current Clamp, 915 mm (36 in.)

  • Fluke I3000s Flex-36 AC Current Clamp, 915 Mm (36 In.) | Fluke

คุณลักษณะสำคัญ

  • Three ranges
    • 30 A
    • 300 A
    • 3000 A, 1, 10 or 100 mV/A output
  • Ideal for current measurement on thick and hard to reach conductors without breaking the circuit
  • Maximum conductor diameter 178 mm (7 in.)
  • CAT III 600 V safety rating

Also available in pack of 4 for use in Power Quality Analyzers. Click here for more info.

ซื้อเลย

ภาพรวมผลิตภัณฑ์: Fluke i3000s Flex-36 AC Current Clamp, 915 mm (36 in.)

The i3000s Flex is an ac current clamp utilizing the Rogowski principle. It can be used to measure currents up to 3000 A when used in conjunction with oscilloscopes, recorders or data loggers. The flexible and lightweight measuring head allows quick and easy installation in hard to reach areas.

ข้อมูลจำเพาะ: Fluke i3000s Flex-36 AC Current Clamp, 915 mm (36 in.)

Electrical specifications
Current ranges
 30 A
 300 A
 3000 A
 AC rms
Output sensitivity (AC-coupled)
 100 mV
 10 mV
 1 mV per A
Load impedance
 100 kΩ minimum
Accuracy
at +25 °C ± 1 % of range (45 Hz to 65 Hz)
Linearity
10 % to 100 % of range ± 0.2 % of reading
Noise
 8 mV ac rms (30 A)
 2 mV ac rms (300 A, 3000 A)
Frequency range
 10 Hz to 50 kHz (-3 dB)
Phase error
 < ± 1 º (45 Hz to 65 Hz)
 ± 10 º (at 20 kHz)
Position sensitivity
with cable > 25 mm from the coupling ± 2 % of range
External field
with cable > 200 mm from the head ± 1 % of range
Power supply
 2 x AA/MN 1500/LR6 Alkaline, , 400 hours, low battery indicator or dedicated external power supply
Temperature Coefficient
 ± 0.08% of reading per °C
Working voltage
see Safety standards section 600 V AC rms or DC
General Specifications
Head Circumference
 915 mm (36 in.)
Head cable diameter
 14.3 mm (0.56 in)
Head bend radius
 38.1 mm (1.5 in)
Cable length (head to electronics)
 2 m (6.56 ft)
Output connection
 0.5 m cable terminated with safety BNC connector. Supplied with 4mm safety plug adapter
Operating temperature range
 -20 °C to +90 °C (-4 °F to 190 °F) (head)
-20 °C to +85 °C (-4 °F to 185 °F) (electronics)
Storage temperature range
 -40 °C to +105 °C (-40 °F to 221 °F) (head)
-20 °C to +85 °C (-4 °F to 185 °F) (electronics)
Operating humidity
 15 % to 85 % (non-condensing)
Weight
 180 g (0.396 lb) (head)
190 g (0.419 lb) (electronics)
Safety standards
 BS EN 61010-1: 2001
 BS EN 61010-2-032: 2002
 BS EN 61010-031: 2002
 600 Vrms, Category III, Pollution Degree 2
 Use of the probe on uninsulated conductors is limited to 600 V AC rms or dc and frequencies below 1 kHz.
EMC standards
 EN 61326: 1998 +A1, A2, & A3
Maximum conductor size
 610 mm or 914 mm, depending on model

รุ่น: Fluke i3000s Flex-36 AC Current Clamp, 915 mm (36 in.)

Fluke i3000s Flex 36

AC Current Clamp, 915 mm (36 in.)

ซื้อเลย

แหล่งข้อมูล: Fluke i3000s Flex-36 AC Current Clamp, 915 mm (36 in.)