Fluke 789 ProcessMeter™
Compare products: milliamp ma loop calibrators
Key features
- Compact digital multimeter and mA loop calibrator solution
- Full-featured mA loop calibrator with built-in 24v Loop Power
- Quickly and easily troubleshoot every part of a control loop
- Large, bright dual-measurement display
Sale ends soon.
Shop now!
Product overview: Fluke 789 ProcessMeter™
Fluke 789 ProcessMeter™ doubles your troubleshooting power
The Fluke 789 ProcessMeter is the ultimate troubleshooting tool for electricians and instrumentation professionals. It combines the functionality of a full-featured loop calibrator with the power of a CAT III 1000 V, CAT IV 600 V safety rated digital multimeter, and the wireless capabilities of Fluke Connect connectivity with optional IR3000FC module. The 789 has a large, dual display with two levels of backlighting and externally accessible fuse and batteries for easy replacement. And its built-in, selectable 250-ohm HART® resistor eliminates the need to carry a separate resistor.
The 789 also has a built-in 24-Volt loop supply, which reduces the need to carry a separate power supply when doing offline transmitter testing. You can also add the wireless data logging capabilities of the Fluke Connect™ mobile app to log data wirelessly to your smart phone and review it from a remote location.
*Requires Fluke IR3000FC module (not included). Not all models are available in all countries. Check with your local Fluke representative.
Do a lot more while carrying a lot less
The 789 provides all standard DMM capabilities including frequency measurement to 20 kHz, Min/Max/Average/Hold/Relative modes, and diode test and continuity beeper. Combine that with the ability to troubleshoot every part of the loop.
Measure, source, simulate 4-20 mA signals, measure resistance, measure power, provide power to the loop and provide 250-ohm resistance to the loop. The 789 includes SpanCheck; 0% and 100% buttons to toggle between 4 and 20 mA sourcing, while the display can simultaneously show mA and % of scale readings for faster troubleshooting. It also delivers 1200-ohm drive capability on mA source.
Accuracy
This ProcessMeter offers manual step, 100%, 25%, Coarse, Fine, plus auto step and auto ramp. It also delivers 0.1% DC voltage accuracy and 0.05% DC current accuracy.
What's in the box:
- Fluke 789 ProcessMeter
- (1 set) AC175 Alligator Clips
- (1 set) TL71 test lead set
- (4) AA 1.5 V alkaline batteries (installed)
- Quick Reference Guide
- 3-year warranty
Specifications: Fluke 789 ProcessMeter™
| Measurement function | Range and resolution | Best accuracy (% of reading + LSD) | |
| V dc | 400.0 mV, 4.000 V, 40.00 V, 400.0 V, 1000 V | 0.1% + 1 | |
| V ac (true-rms) | 400.0 mV, 4.000 V, 40.00 V, 400.0 V, 1000 V | 0.7% + 2 | |
| mA dc | 30.000 mA | .05% + 2 | |
| A dc | 1.000 A (0.440 A continuous) | 0.2% + 2 | |
| A ac | 1.000 A (0.440 A continuous) | 1% + 2 | |
| Resistance | 400.0 Ohms, 4.000 k, 40.00 k, 400.0 k, 4.0 M, 40 M | 0.2% + 1 | |
| Frequency (0.5 Hz to 20 kHz) | 199.99 Hz, 1999.9 Hz, 19.999 kHz | .005% + 1 | |
| Diode test | 2.000 V (shows diode voltage drop) | 2% + 1 | |
| Continuity | Beeps for resistance < approx. 100 ohms | ||
| Output function | Range and resolution | Drive capability | Accuracy (% of span) |
| DC current output (Internal battery operation) | 0.000 to 20.000 mA or 4.000 to 20.000 mA, (selectable at power-up) Over-range to 24.000 mA | 24 V compliance or, 1,200 ohms, @ 20 mA | 0.05% |
| DC current simulate (Ext. 15 V to 48 V loop supply) | 0.000 to 20.000 mA or 4.000 to 20.000 mA, (selectable at power-up) Over-range to 24.000 mA | 1000 ohms, @ 20 mA | 0.05% |
| 24 V loop supply | Minimum 24 V | 250 ohms at 20 mA | > 24 V |
| Current adjustment modes | Manual: Coarse, Fine, 25% and 100% step | ||
| Automatic: Slow Ramp, Fast Ramp, 25% step | |||
| Temperature range of 18 °C to 28 °C, for one year after calibration | |||
| General specifications | |||
| Maximum voltage applied between any jack and earth ground | 1000 V RMS | ||
| Storage temperature | -40 °C to 60 °C | ||
| Operating temperature | -20 °C to 55 °C | ||
| Temperature coefficient | 0.05 x (specified accuracy) per °C (for temperatures < 18 °C or > 28 °C) | ||
| Relative humidity | 95% up to 30 °C; 75% up to 40 °C; 45% up to 50 °C; 35% up to 55 °C | ||
| Vibration | Random, 2 g, 5-500 Hz | ||
| Shock | 1 meter drop test | ||
| Safety | IEC61010-1, Pollution Degree 2/IEC61010-2-033, CAT IV 600 V/CAT III 1000 V | ||
| Size (HxWxL) | 50 x 100 x 203 mm (1.97 x 3.94 x 8.00 in) | ||
| Weight | 600 g (1.3 lbs) | ||
| Battery | Four AA alkaline batteries | ||
| Battery life | 140 hours typical (measurement), 10 hours typical (sourcing 12 mA) | ||
| Warranty | Three years | ||
Models: Fluke 789 ProcessMeter™
Fluke 789 ProcessMeter™
UPC#: 0 95969 11219 2
Includes:
- AC175 Alligator Clips
- Four (4) AA 1.5 V alkaline batteries (installed)
- TL71 safety-designed test lead set
Fluke 789 ProcessMeter™, with a traceable certificate of calibration with data from Fluke
UPC#: 0 95969 94687 2
Includes:
- AC175 Alligator Clips
- Four (4) AA 1.5 V alkaline batteries (installed)
- TL71 safety-designed test lead set
- A traceable certificate of calibration with data from Fluke