All power quality articles
Electronics in your building don't like power problems
As we have seen, power problems have a bad effect on electronic devices. To detect a power problem, a technician will first check out the power supply to a device to make sure it is functioning properly.
Determining Load Horsepower, Wiring, and Breaker Size for Safe and Efficient Installations
“Let's just oversize the motor and we can run it lightly loaded—that will save us some money and be easier on the motor.” This is a false belief among some who select and install motors. Properly sizing motors for a given load results in driving loads more efficiently, saving energy, and saving dollars. Motors typically are most efficient when they are 90 % to 95 % loaded. Just because a motor says “25 Hp” on the nameplate does not mean the motor is producing twenty-five horsepower as it operates.Clamp meter readings: Problems and Solutions
Diagnosing Power Quality Issues in Older Electrical Systems
Learn how to diagnose power quality issues in older electrical systems using a Fluke multimeters and oscilloscope.
5 Reasons to Monitor Power Consumption
Why monitor power consumption with a power logger? Get the data you need to make important energy management decisions including plant safety, cost savings, and power quality troubleshooting.
Why clean power is critical to smooth operations
When optimizing productivity in industry, energy use is one of the few inputs you can readily control.
4 ways maintenance teams benefit from remote power monitoring
Ensure that your team has the tools it needs to reduce unnecessary repairs and increase uptime by integrating power monitoring sensors into your maintenance program.
3 asset diagnostic challenges condition monitoring helps solve
Limited resources can make monitoring all vital plant equipment difficult, if not impossible. That’s where a condition monitoring system with wireless sensors monitoring comes in.
5 ways condition monitoring can improve your maintenance program
Wireless sensors paired with condition monitoring software can improve reliability programs, decrease costs and increase uptime.
Power monitoring improves real-world maintenance programs
Three organizations found cost and time savings after implementing the Fluke 3540 FC Three-Phase Power Monitor into their maintenance programs.
Top 5 power quality issues you can solve with the Fluke 1770 power quality analyzers
Troubleshooting the most common power quality problems—voltage distortion and harmonics. Tools needed, types of problems
Case study: Remote power monitoring helps prevent football power failures
Filmwerks International is one company that has implemented a better way to monitor utility power for their backup UPS systems and generators
Electrical Panel Overheating for No Apparent Reason?
Troubleshooting an electrical panel overheating problem from unusual causes; testing with the power on, ruling out harmonics—and the resolution.
Case study: Texas power consultant keeps uninterruptible power supplies up and running
Critical systems run smoothly with regular maintenance and reliable tools Everybody knows that consistent, dependable electrical power is critical to any plant's function. But perhaps even more critical is a reliable uninterruptible power supply (UPS) system. UPS systems are the silent partners that just sit and wait until there's a break in power. At that point, the UPS system is the most important system in the plant. It has to be ready to spring into action in milliseconds to keeps things running for anywhere from seconds to hours.
Reliable backup power
Since information technology (IT) installations are particularly sensitive to power supply fluctuations and distortions, they typically rely on an uninterruptible power supply (UPS) to compensate. Some installations even include a second UPS supplied by a separate feeder, and a standby generator that can be set to start automatically three minutes after detecting a power interruption.
Power Reliability for Facility Managers
Power reliability for facility managers (bottom line): top issues; adds, moves, changes; electrical and electronic loads; emergency power; older facilities
Troubleshooting power factor correction capacitors
Power factor correction capacitors reduce energy costs by avoiding the premium rates that utilities charge when power factor falls below specified values.
Seven steps to mitigate VFD harmonic issues
To determine the best solution for mitigating unwanted harmonics, start by investigating the equipment suspected of producing the bulk of the harmonic currents. Most often these are Variable Frequency Drives (VFD's). Use measuring equipment to measure and analyze the frequencies and amplitudes of the harmonics. This is much simpler than it sounds.
Practical applications for single-phase voltage recording
Voltage stability may be a problem in areas where loads are cycling on and off during the day. Large compressors, motors, welding machines, arc furnaces, power factor correction capacitors and other large electrical machinery along with system impedance can easily cause voltage dips, swells, and transients.
Moving up to three-phase power quality measurements
Monitoring three-phase power quality is a must. Whether you troubleshoot mysterious electrical problems or provide additional services to a client, it is three-phase power that is provided to commercial and industrial customers and three-phase power that is distributed throughout a facility.
Case study: A hospital tech develops his power quality knowledge
Downtime is costly, both in terms of patient wellbeing and monetary costs - the X-Ray, mammography, and other systems themselves cost millions and a failure can also idle technicians or surgical teams. Most of the facilities have motor/generators and can maintain operations independent of the utility, making the power system robust but also complex.
Why is there an arrow on your current clamp?
Learn why on all current clamps and current clamp accessories, there is an arrow placed close to the beak or inside the beak opening.
How to diagnose high-voltage surge arresters
How to diagnose a high voltage surge arrester with a Fluke thermal imaging camera.
How to set up the 1748 power quality logger
The most important step in any measurement process is setting up your measurement device correctly. Do this incorrectly and you can find out your data is useless after a measurement cycle of days or weeks. That means starting all over again—if you can.
How to find the root cause of intermittent production stops
How to find the root cause of production line stoppage and reduce downtime in manufacturing.
Make better energy consumption decisions
The Fluke 1738 Advanced Three-Phase Power Logger automatically captures and logs more than 500 power quality parameters to give electricians and technicians more visibility into the data needed to make better power quality and energy consumption decisions.
Case study: Fluke power monitor saves California wastewater plant thousands of dollars
Read the wastewater plant case study on how the Fluke 3540 Power Monitor paid for itself in five months by eliminating the need to use contractors.
How to improve power factor
Learn how to improve power factor, including specific solutions for different root causes of poor power factor.
What is the difference between single-phase and three-phase power?
Learn the difference between single-phase and 3-phase power supplies, including uses and configurations.
Comparing the Fluke 438-II and Fluke MDA-500
Extend motor drive production performance, trend data over time and troubleshoot excess energy consumption. Compare the 438-II Power Quality and Motor Analyzer and the Fluke MDA-550 Motor Drive Analyzer.
Power Factor: What it is and How to Calculate it
What is power factor and why is it important? Learn how to calculate the power factor formula, each component of the equation, and why it matters.
Case study: Finding a Power Quality Needle in a 30-Mile Haystack
At the end of April 2005, Crystal Mountain Resort in Washington suffered catastrophic failure of two power filters associated with their chair lifts.
Case study: Clean Power Delivers Clean Water
Maintenance electrical specialist Mark Newport was in the process of installing new electronic power factor correction units at multiple motor control centers (MCCs) to improve power quality, protect equipment and reduce costs.
Troubleshooting power quality issues in critical medical diagnostic equipment
Diagnosing and troubleshooting power quality issues in medical equipment in hospitals and health care facilities.
Case study: Overheated Transformer
You could almost call it a happy accident. During a routine job at a large industrial facility, an electrical maintenance worker set a plastic kit on top of a nearby transformer.
Case study: Network Hub Failure
Ever fixed something and still not solved the problem? Sometimes multiple deficiencies can all cause the same symptoms.
Case study: Elevator Trips Emergency Generator Breaker
A large commercial building had just finished an elevator equipment upgrade - but they hadn't been able to bring the elevator back into normal operation.
Case study: The Vibrating Transformer
This case history comes from an electrical contractor. Several of this contractor's clients operate large commercial buildings.
The Power Of A Waveform: Expanded Troubleshooting Options With The Fluke 345 Power Quality Clamp Meter
Electricians are discovering that the new Fluke 345 goes beyond simply monitoring voltage or current. It displays waveforms and harmonics, performs power measurements for power-factor evaluations, measures inrush current, and logs data over time for later analysis.
Case study: Performing Power Quality Studies and Troubleshooting Loads
Mac McArthur performs power quality studies for commercial, industrial, and residential clients.
Case study: Instant Power Replay Solves a Breaker Trip
After experiencing some nuisance tripping of breakers in the subpanel feeding the second floor of this industrial building, we installed a Fluke 1750 Power Recorder at the subpanel to gather information about power usage.
Case study: Fluke Instruments Add Reliability to Oceanographic Research
It was in his capacity as an electrical troubleshooter and an electronics expert that Gagne, almost two years ago, first began to use a Fluke 434 Power Quality Analyzer and a Ti30 Thermal Imager.
Case study: More Snow With Power Quality
A ski resort near Silverthorn, CO., depends on its snowmaking capacity to augment nature's snowfall, especially during drought years.
Case study: Rural Transformer Failure
This case history involves the investigation of a utility transformer failure that occurred in a rural area surrounded mostly by farmland and open space. The failure occurred in a location where power quality problems are rare.
Case study: Half Wave Rectifier
One winter morning, the electrician received a call from a local school. The caller said a transformer supplying power to three portable classrooms was making a chattering noise, as if something were loose inside.
Case study: 5th Harmonic Resonance
A small city gets its water from a mountain lake 30 miles away. A pumping system at the lake brings water up a short incline and into a long gravity pipeline that feeds the city's water distribution system.
Case study: Malfunctioning Traffic Light
The engineer carries a Fluke 43B on all trouble calls, because it provides a graphical display that allows customers to see a picture of the problem.
Case study: Lighting Ballast Evaluation
In most facilities, lighting is a major element of operating cost. Part of that cost is due to energy, and part is due to maintenance.
Case study: The Malfunctioning Medical Machine
This case history is a classic example of the importance of a systematic approach to solving a problem. It involves a contractor who works with several high-technology manufacturing plants.
Is it the Motor, the Drive, or the Load?
In troubleshooting situations involving a motor, more than half the battle is simply isolating the problem.
Power Quality at the Service Panel
Voltage sags, tripping breakers, overheated electrical panels, and excessive voltage levels are all indications of possible trouble in an electrical distribution system.
Power Quality Measurements at Receptacle Branch Circuits
Many power quality problems show up at the branch circuit level. There's a simple reason for this: that's where most of the sensitive loads (and sensitive employees) are located.
How Adjustable Speed Drives Affect Power Distribution
Adjustable speed drives (ASDs) can be both a source and a victim of poor power quality.
Making Watt-Hour Measurements with Fluke Power Quality Analyzers
The need to manage power is never more critical than when power prices skyrocket and power quality becomes suspect.
Common Power Quality Factors Affecting Transformers
Transformers supplying nonlinear loads should be checked periodically to verify operation within acceptable limits. Transformers are also critical to the integrity of the grounding system.
Troubleshooting Power Harmonics: Basic Troubleshooting Using Multimeters and Current Clamps
This application note details the procedures for using Fluke power quality analyzers for average watt measurements and converting those to watt-hours.
Electrical Noise and Transients
Electrical noise is the result of more or less random electrical signals getting coupled into circuits where they are unwanted, i.e., where they disrupt information-carrying signals.
What Does Class A Mean To Me?
Power quality measurement is still a relatively new and quickly evolving field. Whereas basic electrical measurements like RMS voltage and current were defined long ago, many power quality parameters have not been previously defined, forcing manufacturers to develop their own algorithms.
Measuring output torque without mechanical sensors
Measuring output torque without mechanical sensors
Simplify troubleshooting: Making sense of electrical signals
Rely on the Fluke 120B Series Industrial ScopeMeter® Handheld Oscilloscopes when your work calls for detailed and accurate signal measurements.
Recommended battery tests and testing schedule for battery back-up systems
Healthy batteries should main¬tain a capacity above 90 % of the manufacturer’s rating; most manufacturers recommend replacing the battery if it falls below 80 %. A series of regular tests are recommended for ensuring that batteries are maintaining capacit
Electric motor efficiency and reliability: New testing approach matches real world conditions
Measure torque while motors are still in service using an advanced tool that eliminates external torque and speed sensors.
How to use the power quality indicator on the 378 FC clamp meter
Detect basic 3 phase power quality issues with the versatile Fluke 378 FC clamp meter for industrial electricians. Increase productivity and safety without test leads.
Case study: Three-Phase Motor Failure
For three years in a row, a particularly large three-phase motor would fail twice a year. The facility maintenance manager called in both the electrical contractor and the motor manufacturer, who pointed fingers at each other but failed to resolve anything on site.
Case study: Machine Shop Motor Failures
Motor failures can be mysterious. Often, the mechanical loads on the motors have not changed and other loads connected to the same service appear to work normally - yet, the motors just fail.
Case study: Low Power Factor
Because power quality issues are difficult to pinpoint, clients often reach the wrong conclusions about their power issues. That often leads to expensive solutions that don't actually correct the underlying problem.
Case study: See how the 438-II Motor Analyzer is building an underwater fan club
Watch the video to see how the Point Defiance Zoo and Aquarium uses the Fluke 438-ii power quality analyzer and motor analyzer to reduce water and energy use.
Case study: How a power facility reduced 40% of calibration time
Many facilities, such as power plants or production facilities, depend on a strong preventive maintenance program. These programs are essential to keep processes running safely and efficiently.
Detecting power quality issues
The electrical power issues that most frequently affect industrial plants include voltage sags and swells, harmonics, transients, and voltage and current unbalance. The proper tools to correct these issues include knowledge and electrical test instruments ideally suited for each task.