Troubleshooting 10 Common Issues with the Fluke 116 HVAC Multimeter: An FAQ Guide

HVAC technicians rely on their tools to diagnose and repair issues quickly and accurately. The Fluke 116 HVAC Digital Multimeter is built specifically for HVAC professionals, offering measurement capabilities like voltage, resistance, capacitance, temperature, and microamps. Below are 10 common HVAC issues and how to troubleshoot them effectively using the Fluke 116.

Fluke 116 HVAC Digital Multimeter testing DC microamps
Fluke 116 HVAC Digital Multimeter testing DC microamps.

Need better tools for your HVAC toolkit? Get the list of top Fluke devices for HVAC pros.

1. Why Won’t My HVAC System Turn On?

If an HVAC system isn’t powering up, electrical supply issues are often to blame. The Fluke 116 can help you determine where electrical interruptions may be happening within the system. 

Setup and Testing

  • Set device to AC voltage (V~)
  • Check voltage at:
    • Power terminals (should read 120V or 240V depending on the system)
    • Control board connections
    • Transformer primary and secondary (should show 120V/24V)

If the device does not detect power, check the breaker, wiring, or transformer next.

2. How Do I Troubleshoot a Faulty Thermostat?

A thermostat that isn’t responding or triggering the system may have a wiring or power issue. 

Setup and Testing

  • Set the device to AC voltage (V~)
  • Measure at thermostat terminals:
    • R to C: Should read 24V
    • R to W (heat) or R to Y (cooling): Should read 24V when calling for heating/cooling
  • Set the device to continuity mode (⚠️ Power Off First!):
    • Check for continuity across terminals

If the DMM locates an area with continuity interruptions, you’ve found the location of the electrical fault. 

3. Why Does My Furnace Shut Off Right After Ignition?

The flame sensor may be dirty or malfunctioning, preventing proper operation. Use the Fluke 116 to troubleshoot if you suspect this may be an issue with the furnace.

Setup and Testing

  • Set the device to microamps (µA)
  • Connect in series with the flame sensor wire
  • Expected reading: 0.5 to 10 µA

If the reading is low or zero, this indicates that the flame sensor may need to be cleaned or replaced.

4. How Can I Detect Ghost Voltage in My HVAC System?

Ghost voltage can mislead troubleshooting efforts, making it seem like power is present when it isn’t. The Fluke 116 can distinguish between ghost voltages and real power.

Setup and Testing

  • Set the device to LoZ AC voltage (V~ LoZ)
  • Measure suspect circuit points
  • Compare with standard AC voltage (V~) reading

If the LoZ reading is significantly lower, it’s ghost voltage, not actual power.

5. Why Is My HVAC Transformer Not Working?

Transformers, which normally convert high-voltage electricity to a lower 24-volt power supply to the HVAC system, sometimes fail. Complete transformer failures can cut power from the system. A DMM can help confirm transformer failure and troubleshoot issues within the device.

Setup and Testing

  • Set to AC Voltage (V~)
  • Measure across transformer primary terminals (should be 120V or 240V depending on system)
  • Measure across secondary terminals (should read ~24V)
  • Set to Resistance Mode (Ω, power off first!):
    • Check for open windings (should not read OL)

6. Why Won’t My HVAC Fan or Compressor Start?

A failed capacitor can prevent motors from starting. Use the Fluke 116 to figure out if the capacitor is to blame for a malfunctioning fan or compressor.

Setup and Testing

  • Set the device to capacitance (µF)
  • Remove capacitor (discharge first!)
  • Check against rated value (should be within 6% of rating)

If the DMM displays 0 µF or OL, replace capacitor

7. How Do I Diagnose a Faulty Blower or Compressor Motor?

A motor that won’t run could have an open or shorted winding. Test the windings with the Fluke 116 to troubleshoot.

Setup and Testing

  • Set the device to resistance (Ω,)
  • Measure across windings: 
    • Open winding: Reads OL
    • Shorted winding: Reads near 0Ω
  • Set the device to AC voltage (V~):
    • Measure voltage to motor (should match rated voltage)
  • Check amp draw with a clamp meter (if available)

If windings are open or shortened, replace them.

8. How Can I Test HVAC Relays, Fuses, and Wiring?

Faulty relays or open fuses can disrupt HVAC operation. Use the Fluke 116 to detect them.

Setup and Testing

  • Set tester to continuity mode
  • Check for continuity across fuses and relay contacts

Replace relays, fuses, and wiring if there is no beep or OL reading.

9. Why Is My HVAC System Not Cooling Properly?

Airflow and refrigerant issues can cause inefficiency. Identify the root cause by troubleshooting with the Fluke 116.

Setup and Testing

  • Set the device to temperature mode (°F or °C) and attach temperature probe
  • Measure supply and return air temps 
    • Target temp drop: 16-22°F
  • Measure refrigerant line temperature

Abnormal readings indicate airflow or refrigerant issues requiring further diagnosis.

10. How Do I Test a Variable Frequency Drive (VFD) in My HVAC System?

VFDs control fan and compressor speeds but can fail or have incorrect signals. The Fluke 116 can determine if they are working properly.

Setup and Testing

  • Set the device to frequency mode (Hz)
  • Measure at VFD output terminals
  • Compare reading to expected drive frequency

If VFD frequency is way off from the expected measurement or fluctuating abnormally, the drive may need reprogramming or replacement.

Conclusion

The Fluke 116 HVAC Multimeter provides precise, fast, and reliable measurements for diagnosing electrical and system faults. HVAC technicians can rely on this tool to efficiently resolve common issues and keep systems running smoothly. 

You might also be interested in

Chat with ourFluke assistant
Clear Chat