Fluke 1550C 5 kV Insulation Tester Kit

  • Fluke 1550C 5 KV Insulation Tester Kit | Fluke
  • Fluke 1550C 5 KV Insulation Tester Kit | Fluke

Key features

Features include:

  • Test voltages to up 5 kV and save time by trending on the spot only with Fluke Connect®
  • CAT III 1000 V, CAT IV 600 V safety rating
  • Warning function alerts the user that line voltage is present and gives the voltage reading up to 600 V AC or DC for increased user safety
  • Selectable test voltages in 50 V steps from 250 V to 1000 V, and 100 V steps above 1000 V
  • Measurements can be stored in up to 99 memory locations, with each location assigned a unique, user defined, label for easy recall
  • Long battery life gives the user over 750 tests between charges
  • Automatic calculation of Dielectric Absorption (DAR) and Polarization Index (PI) with no additional setup
  • Guard system eliminates the effect of surface leakage current on high-resistance measurements
  • Large digital/analog LCD for easy viewing
  • Capacitance and leakage current measurement
  • Ramp function for breakdown testing
  • Resistance measurements up to 2 TΩ
  • Timer settings up to 99 minutes for timed tests
  • 3-year warranty
  • bvseo_sdk, p_sdk, 3.2.1
  • CLOUD, getAggregateRating, 35.6ms
  • REVIEWS, PRODUCT
  • bvseo-msg: HTTP status code of 404 was returned; HTTP status code of 404 was returned;
Get a free demo

Product overview

Evaluate the trends, eliminate the doubt

The Fluke 1550C insulation resistance tester offers digital insulation testing up to 5 kV, making it ideal for testing a wide range of high voltage equipment including switchgear, motors, generators and cables.

Fluke insulation testers can now conduct the entire range of test voltages specified in IEEE 43-2000 with a best in class, 3 year warranty and CAT IV 600 V safety rating. With measurement storage and PC interface, the 1550C is the perfect tool for preventative or predictive maintenance programs designed to identify potential equipment failures before they occur.

Models

Fluke 1550C/Kit
Fluke 1550C 5 kV Insulation Tester Kit

Includes:

  • Test cables with alligator clips (red, black, green)
  • Infrared adapter with interface cable
  • FlukeView® Forms Basic CD-ROM
  • AC power cord
  • Soft carrying case
  • English manual
  • User's manual on CD-ROM
  • Quick reference card
  • Software license agreement
  • Registration card
  • FlukeView® Forms installation guide
  • USB-IR cable installation guide
  • Heavy duty alligator clip leads

Specifications

Electrical Specifications
The tester's accuracy is specified for one year after calibration at operating temperatures of 0°C to 35°C. For operating temperatures outside the range (-20°C to 0°C and 35°C to 50°C), add ± .25% per °C, except on the 20% bands add ± 1% per °C.
Insulation Resistance Measurement
Test voltage (DC)
250 VRange< 250 kΩ,
250 kΩ to 5 GΩ
5 GΩ to 50 GΩ
> 50 GΩ
Accuracy (± reading)Unspecified
5%
20%
Unspecified
500 VRange< 500 kΩ
500 kΩ to 10 GΩ
10 GΩ to 100 GΩ
> 100 GΩ
Accuracy (± reading)Unspecified
5%
20%
Unspecified
1000 VRange< 1 MΩ
1 MΩ to 20 GΩ
20 GΩ to 200 GΩ
> 200 GΩ
Accuracy (± reading)Unspecified
5%
20%
Unspecified
2500 VRange< 2.5 MΩ
2.5 MΩ to 50 GΩ
50 GΩ to 500 GΩ
> 500 GΩ
Accuracy (± reading)Unspecified
5%
20%
Unspecified
5000 VRange< 5 MΩ
5 MΩ to 100 GΩ
100 GΩ to 1 TΩ
> 1 TΩ
Accuracy (± reading)Unspecified
5%
20%
Unspecified
Bar graph range0 to 1 TΩ (1550C) - 0 to 2 TΩ (1555)
Insulation test voltage accuracy-0%, +10% at 1 mA load current
Induced AC mains current rejection2 mA maximum
Charging rate for capacitive load5 seconds per μF
Discharge rate for capacitive load1.5 s/μF
Leakage current measurementRange1 nA to 2 mA
Accuracy±(5% + 2 nA)
Capacitance measurementRange0.01 μF to 15.00 μF
Accuracy±(15% rdg + 0.03 μF)
TimerRange0 to 99 minutes
Resolution setting1 minute
Resolution indication1 second
Live circuit warningWarning range30 V to 660 V AC/DC, 50/60 Hz
Voltage accuracy±(15% + 2 V)
Software specificationsFlukeView Forms™ basic software requires a PC running Windows XP, Windows Vista , Windows 7 or Windows 8.
General Specifications
Display75 x 105 mm
Power12 V lead-acid rechargeable battery, Yuasa NP2.8-12
Charger Input (AC)85 V to 250 V AC 50/60 Hz 20 VA
This Class II (double insulated) instrument is supplied with a Class 1 (grounded) power cord. The protective earth terminal (ground pin) is not connected internally. The extra pin is for added plug retention only.
Dimensions269 x 277 x 160 mm (10.6 x 10.9 x 6.3 in)
Weight3.7 kg (8.2 lb)
Temperature (operating)-20°C to 50°C (-4°F to 122°F)
Temperature (storage)-20°C to 65°C (-4°F to 149°F)
Humidity80% to 31°C decreasing linearly to 50% at 50°C
Altitude2000 m
Enclosure sealingIP40
Input overload protection1000 V AC
Electromagnetic compatibilityEN 61326
Safety complianceIEC 61010-1: Overvoltage category II, Pollution Degree 2.
IEC 61010-2-030: Measurement 600V CAT IV / 1000V CAT III
IEC 61557-1, IEC 61557-2

Resources

  • bvseo_sdk, p_sdk, 3.2.1
  • CLOUD, getReviews, 33.4ms
  • REVIEWS, PRODUCT
  • bvseo-msg: HTTP status code of 404 was returned;