Step-by-Step Guide to Troubleshooting PV Systems Using I-V Curve Tracers
Ensuring the optimal performance of photovoltaic (PV) systems requires regular maintenance and effective troubleshooting methods. One of the most valuable tools for diagnosing issues in PV systems is the I-V curve tracer. This article provides a practical, step-by-step guide to troubleshooting PV systems using I-V curve tracers, helping technicians identify and resolve performance problems efficiently.

Getting Started with I-V Curve Tracing
Before beginning the troubleshooting process, it’s essential to understand the basics of I-V curve tracing and ensure you have the necessary equipment and safety measures in place.
Essential Equipment and Safety Precautions
- I-V Curve Tracer: Ensure you have a reliable and well-calibrated I-V curve tracer with the appropriate voltage and current rating.
- Irradiance Sensor: For measuring the solar irradiance in the plane of the array.
- Temperature Sensor: For accurate module temperature measurements.
- Personal Protective Equipment (PPE): Follow NFPA 70E guidelines for electrical safety, including gloves, arc flash face shield, and appropriate clothing.
- Lockout/Tagout (LOTO) Kit: To safely isolate electrical components during testing.
Step 1: Preparing for I-V Curve Tracing
- Safety First: Ensure that you are familiar with the PV system layout and operation. Verify that the I-V curve tracer and all other equipment are rated for the expected current and voltage.
- Environmental Conditions: Perform tests under stable weather conditions with minimal wind and irradiance levels above 700 W/m² to minimize measurement errors. Aim to conduct tests between 10:00 AM to 3:00 PM for the most accurate results.
Step 2: Setting Up the I-V Curve Tracer
- Install Sensors: Mount the irradiance sensor in the plane of the array and attach the temperature sensor to a representative module using high-temperature tape. Ensure good thermal contact for accurate readings.
- Electrical Isolation: Use the LOTO kit to isolate the combiner box or other test points from the rest of the PV system. Check that there is no current running through the circuit with a non-contact clamp meter. Open touch-safe fuse holders to isolate individual source circuits.
Step 3: Conducting the I-V Curve Test
- Connecting the Tracer: Attach the I-V curve tracer’s test leads to the positive and negative busbars of the PV source circuit. Ensure secure and intact connections.
- Connect the Circuit: Close one fuse holder to connect the circuit to be tested to the bus bars.
- Performing the Sweep: Initiate the I-V curve sweep, allowing the tracer to measure current and voltage at various points. The process typically takes 10 to 15 seconds per source circuit.
- Saving the Data: Store the measured I-V curves electronically for analysis. Repeat the process for each PV source circuit in the combiner box.
Step 4: Analyzing I-V Curve Data
- Compare with Expected Curves: Use the module’s datasheet and environmental measurements to generate a predicted I-V curve. Compare the measured curve to the predicted one to identify deviations.
- Identify Deviations: Look for common I-V curve deviations such as stepped curves, low Isc, low Voc, and rounded knees. Each type of deviation points to specific issues, as detailed in the previous article.
Step 5: Troubleshooting Common I-V Curve Deviations
Here’s a detailed troubleshooting guide for the most common I-V curve deviations:
Stepped I-V Curves

This graph illustrates a stepped I-V curve, highlighting the notches caused by shading or soiling
Cause: Typically caused by shading, soiling, or bypass diode activation.
Troubleshooting Steps:
- Visual Inspection: Check for visible shading (e.g., tree branches, debris) and clean any soiling (e.g., dust, bird droppings).
- Bypass Diode Check: Use a multimeter to test the bypass diodes. Replace any faulty diodes or modules.
- Module Inspection: Look for physical damage or cracked cells that might cause shading effects.
Low Short-Circuit Current (Isc)
Cause: Can result from shading, soiling, poor irradiance measurement, or module degradation.
Troubleshooting Steps:
- Environmental Check: Ensure the irradiance sensor is correctly positioned and calibrated.
- Cleaning: Clean the PV modules to remove any dirt or debris.
- Inspect for Degradation: Look for signs of aging or damage on the modules. Compare current performance with historical data.
Low Open-Circuit Voltage (Voc)
Cause: Often caused by temperature measurement errors, shading, or hardware issues like shorted bypass diodes.
Troubleshooting Steps:
- Temperature Measurement: Verify that the temperature sensor is correctly placed and providing accurate readings.
- Shade Removal: Identify and remove any shading sources.
- Hardware Check: Inspect for shorted bypass diodes or pinched conductors and repair or replace as necessary.
Rounded Knees
Cause: Indicates performance degradation due to aging or increased series resistance.
Troubleshooting Steps:
- Trend Analysis: Monitor I-V curves over time to track gradual performance changes.
- Inspect Connections: Check for corrosion or poor connections that could increase series resistance.
Low Voltage Ratio
Cause: Caused by increased series resistance due to corroded connectors, damaged solder joints, or undersized conductors.
Troubleshooting Steps:
- Connection Inspection: Examine all connections for signs of corrosion or damage.
- Conductor Check: Ensure that conductors are appropriately sized for the current they carry.
Low Current Ratio
Cause: Due to decreased shunt resistance or localized shunts.
Troubleshooting Steps:
- Shading and Soiling Check: Rule out shading or soiling issues first.
- Infrared Imaging: Use an IR camera to detect localized shunts or hot spots that indicate performance problems.
Step 6: Documenting and Addressing Issues
- Record Findings: Document all findings, including the types of deviations identified, probable causes, and the steps taken to resolve the issues.
- Report and Repair: Generate a report for asset managers or maintenance teams. Schedule repairs or replacements based on the findings.
- Follow-Up Testing: After making repairs, conduct follow-up I-V curve tests to ensure that the issues have been resolved and the system is performing optimally.
Example: Resolving Low Isc in a Utility-Scale PV System
A utility-scale PV system was underperforming, with several source circuits showing low Isc values. Using an I-V curve tracer, technicians identified that the issue was due to uniform soiling across multiple modules. After cleaning the modules, follow-up I-V curve tests showed restored Isc values, confirming that soiling was the primary cause of the performance issue.
Best Practices for Effective Troubleshooting
- Regular Maintenance: Incorporate I-V curve tracing into routine maintenance schedules to detect and address issues early.
- Consistent Documentation: Keep detailed records of all I-V curve tests, environmental conditions, and corrective actions taken.
- Training and Safety: Ensure that all personnel are trained in using I-V curve tracers and follow safety protocols rigorously.
Troubleshooting Guide for Common I-V Curve Deviations
| Deviation Type | Description | Troubleshooting Steps |
|---|---|---|
| Stepped I-V Curves | Notches or steps in the curve | Inspect for shading, soiling, and check bypass diodes |
| Low Isc | Lower-than-expected short-circuit current | Ensure accurate irradiance measurement, clean modules |
| Low Voc | Lower-than-expected open-circuit voltage | Verify temperature measurements, inspect for shading |
| Rounded Knees | Gradual slope change at the maximum power point | Monitor trends, inspect for increased series resistance |
| Low Voltage Ratio | Lower-than-expected vertical slope | Inspect connections for corrosion, check conductor sizes |
| Low Current Ratio | Higher-than-expected horizontal slope | Rule out shading/soiling, use IR imaging for localized shunts |
Conclusion
I-V curve tracing is an invaluable tool for troubleshooting and maintaining PV systems. By following a systematic approach to preparing, conducting, and analyzing I-V curve tests, technicians can effectively diagnose and resolve performance issues, ensuring that PV systems operate at their peak efficiency. Regular use of I-V curve tracers, combined with thorough documentation and adherence to safety protocols, will lead to more reliable and efficient solar power generation.
Frequently Asked Questions (FAQs)
What equipment do I need for I-V curve tracing?
You will need an I-V curve tracer, irradiance sensor, temperature sensor, personal protective equipment (PPE), and a lockout/tagout (LOTO) kit.
How do I prepare for an I-V curve test?
Ensure safety first, perform tests under stable weather conditions, install sensors accurately, and isolate the electrical components to be tested.
What are common I-V curve deviations?
Common deviations include stepped I-V curves, low Isc, low Voc, rounded knees, low voltage ratio, and low current ratio, each indicating specific performance issues.
How do I troubleshoot low Isc?
Check for shading, soiling, poor irradiance measurement, and module degradation. Clean the modules and verify sensor accuracy.
How do I document and address issues found during I-V curve tracing?
Record all findings, generate reports, schedule necessary repairs, and conduct follow-up tests to ensure issues are resolved.