Czech

Fluke 1507 Insulation Resistance Tester

  • Fluke 1507 Insulation Resistance Tester
  • Fluke 1507 Insulation Resistance Tester

Klíčové vlastnosti

  • Rugged, compact advanced insulation resistance tester for electrical contractors and industrial and commercial electricians
  • Automatically calculates Polarization Index and Dielectric Absorption Ratio
  • Makes repetitive tests simple and easy with a Compare (Pass/Fail) function 
  • Offers multiple insulation test voltages: 50 V, 100 V, 250 V, 500 V, and 1000 V

Přehled výrobků: Fluke 1507 Insulation Resistance Tester

The Fluke 1507 is a versatile, compact, handheld insulation tester for advanced industrial and electrical insulation testing. Its multiple test voltages make it the ideal tool for many troubleshooting, commissioning, and preventative maintenance applications.

Take advantage of the 1507 full feature set to easily and quickly perform advanced insulation resistance testing. Its handy size and light weight make it easy to pack and use. Additional features, like the remote probe, save both time and money especially when performing repetitive tests. And its reasonable price and rugged reliability make it an excellent value.

Other useful capabilities:

  • Performs insulation tests from 0.01 MΩ to 10 GΩ
  • Includes live circuit detection to prevent insulation test if voltage >30 V is detected
  • Includes auto-discharge of capacitive voltage for added user protection
  • Measures AC/DC voltage from 0.1 V to 600 V and resistance from 0.01 Ω to 20.00 kΩ
  • Provides lo-ohms earth-bond continuity (200 mA)
  • Simplifies repetitive or hard-to-reach testing with the remote test probe
  • Saves battery power with auto power off
  • Presents results on a large, backlit display
  • Features CAT IV 600 V overvoltage category rating
  • Comes with remote probe, test leads, test probes, alligator clips and one-year warranty
  • Accepts optional Fluke TPAK magnetic hanging system to free your hands for other work
  • Runs on four AA alkaline batteries (NEDA 15 A or IEC LR6) for at least 1000 insulation tests

Useful resources and rugged tools for Solar professionals

Technické údaje: Fluke 1507 Insulation Resistance Tester

AC/DC Voltage Measurement
AccuracyRange600.0 V
Resolution0.1 V
50 Hz to 400 Hz ± (% of Rdg + Digits)±(2% + 3)
Input impedance3 MΩ (nominal), < 100 pF
Common mode rejection ratio (1 kΩ unbalanced):> 60 dB at DC, 50 or 60 Hz
Overload protection600 V rms or DC
Earth Bond Resistance Measurement
Range/Resolution20.00 Ω0.01 Ω
200.0 Ω0.1 Ω
2000 Ω1.0 Ω
20.00 kΩ0.01 kΩ
Accuracy±(1.5% + 3)
Overload protection2 V rms or DC
Open circuit test voltage> 4.0 V, < 8 V
Short circuit current> 200.0 mA
Insulation Specifications
Measurement range0.01 MΩ to 10 GΩ
Test voltage50 V, 100 V, 250 V, 500 V, 1000 V
Test voltage accuracy+ 20%, - 0%
Short circuit current1 mA nominal
Auto dischargeDischarge time < 0.5 second for C = 1 µF or less
Live circuit indicatorInhibit test if terminal voltage > 30 V prior to initialization of test
Maximum capacitive loadOperable with up to 1 µF load
Measure accuracy50 V±(3% + 5)
100 V±(3% + 5)
250 V±(1.5% + 5)
500 V±(1.5% + 5)
1000 V±(1.5% + 5) to 2000 MΩ, ±(10% + 3) above 2000 MΩ
General Specifications
Maximum voltage applied to any terminal:600 V AC rms or DC
Storage temperature-40°C to 60°C (-40°F to 140°F)
Operating temperature-20°C to 55°C (-4°F to 131°F)
Temperature coefficient0.05 x (specified accuracy) per °C for temperatures < 18°C or > 28°C (< 64°F or > 82°F)
Relative humidity
0% to 95% @ 10°C to 30°C (50°F to 86°F)
0% to 75% @ 30°C to 40°C (86°F to 104°F)
0% to 40% @ 40°C to 55°C (104°F to 131°F)
VibrationRandom, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument
Shock1 meter drop per IEC 61010-1 2nd Edition (1 meter drop test, six sides, oak floor)
Electromagnetic compatibilityIn an RF field of 3 V/M, accuracy = specified accuracy (EN 61326-1:1997)
SafetyComplies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement category IV 600 V (CAT IV)
CertificationsCSA per standard CSA/CAN C22.2 No. 61010.1-04; TUV per standard IEC/EN 61010-1 2nd Edition
BatteriesFour AA batteries (NEDA 15A or IEC LR6)
Battery lifeInsulation test use:Tester can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off.
Resistance measurements:Tester can perform at least 2500 earth bond resistance measurements with fresh alkaline batteries at room temperature. These are standard tests of 1 Ω with a duty cycle of 5 seconds on and 25 seconds off.
Size (H x W x L)5.0 x 10.0 x 20.3 cm (1.97 x 3.94 x 8.00 in)
Weight550 g (1.2 lb)
IP ratingIP40
AltitudeOperating2000 m CAT IV 600 V, 3000 m CAT III 600 V
Non-operating (storage)12,000 m
Over-range capability110% of range
Included accessoriesTL224 Test Leads, TP74 Test Probes, clips PN 1958654 (red) and PN 1958646 (black), holster and remote probe

Modely: Fluke 1507 Insulation Resistance Tester

Fluke 1507
Fluke 1507 Insulation Resistance Tester
Koupit
  • Mericí sondy
  • Ochranné pouzdro (holster)
  • Dokumentace uživatele