Loop Calibration and Maintenance with Fluke Tools
Process instruments require periodic calibration and maintenance to ensure correct operation. This article contains information to help guide technicians through some of the more common loop calibration tasks using Fluke tools.
Fluke loop calibrators are ideal for a wide variety of calibration applications. They include:
- Fluke 707 Loop Calibrator
- Fluke 705 Loop Calibrator
- Fluke 715 Volt/mA Loop Calibrator
- Fluke 787B and 789 ProcessMeter™ tools
The loop-powered isolator and the two-wire isolating transmitter are two of the more prevalent devices in use in 4-20 milliamp (mA) control loops today (see Figure 1). The testing and troubleshooting procedures for each are different and need to be understood by the technicians performing operational checks on these units in the field.
The sections below describe the functionality of these units and how to test them in the field.
Loop-Powered Isolators
The main purpose of a loop isolator is to eliminate ground loops in control systems while sending the control signal current to another part of the system. Loop-powered isolators, unlike two-wire transmitters, draw their operating power from the “input” side of the isolator (see Figure 1), which requires a pickup voltage from 5.5 to 13.5 volts (V) depending on the manufacturer.
The output of the loop isolator is an electrically isolated mirror image of the input side current. The compliance voltage associated with the output is greatly reduced from that of the input side and ranges around 7.5 volts. This produces a total loop loading capability of 350 ohms (Ω). This limited loop drive capability is the primary limitation of the loop isolator.

Two-Wire Transmitters
Isolating two-wire transmitters provide the same isolating functionality as loop isolators with the added advantage that many provide signal conditioning for a variety of inputs such as thermocouple, frequency, DC current, RTD, strain gauge, and other process inputs.
The transmitter uses supply power to convert those input signals to standard four- to 20-milliamp signals for the transmitter output to the loop. Typical power supplies for two-wire transmitters are 24 or 48 volts. Power supplies of this size allow a significant loop load capability on the output.
Field Checking a Loop-Powered Isolator
Fluke loop calibrators have a unique current simulation feature that, when connected to an external power source, allows you to precisely control current between zero and 24 milliamps. When field checking a loop-powered isolator, the two-wire loop transmitter supplying signal current to the isolator for the loop may be removed and the calibrator connected in simulate mode to control loop current (Figure 2).
Connecting the Fluke Loop Calibrator
In this example, we will use the Fluke 789 ProcessMeter™. Although the operating controls vary, this application can also be performed using the Fluke 707, 715, and 705 loop calibrators.
Below are the precise steps for connecting the Fluke 789 for loop calibration:
- Disconnect the main loop transmitter and connect the Fluke 789 to the loop with the test leads plugged into the center or simulate terminals of the calibrator (see Figure 2).
- Set the 789 rotary switch to the mA output mode. Set the Fluke 789 to the 4-20 milliamp output mode. Make connection for simulate mA. The 789 is now outputting a precise four milliamps and is providing operating power to the input of the loop-powered isolator.
- Place a Fluke 187 or equivalent multimeter (one microamp (µA) resolution is ideal; 10 microamps is acceptable) that is set in the mA measurement mode on the output side of the isolator. This will monitor output current (see Figure 2).
- Adjust the zero control on the isolator for a reading of 4.000 milliamps on the output meter (Fluke 187).
- Step the input current to 20 milliamps using the percent step button ▲ on the Fluke 789 (25% or 4 milliamp increase) and adjust the span control on the isolator to read 20.000 milliamps on the output meter connected to the isolator.
- Step input current down to four milliamps using the ▼ button (25% or 4 milliamp decrease), and check for a zero shift. Adjust if necessary.
- At this point, basic zero and span adjustments are complete.

Check Linearity
Fluke loop calibrators can easily check the linearity of your loop isolator using the percent step buttons ▲ and ▼. Pushing these buttons when in the output mode increases or decreases the output current in 25% steps. In the 4-20 mA current mode, these intermediate steps are at eight milliamps (25%), 12 milliamps (50%), and 16 milliamps (75%).
To check the linearity of the isolator, push the associated percent step buttons up and down and confirm that the digital multimeter (DMM) is reading the same value as is shown on the loop calibrator display. If you measure a variation from expected values, compare your findings to the linearity limits stated by the manufacturer of the loop-powered isolator. You may need to replace the isolator.
Testing Valve Positioners
Electronic valve positioners should receive periodic in-field calibrations as part of preventive maintenance programs. Fluke loop calibrators are the ideal test tools for these checks. Valve positioners vary in design and valve type and should be calibrated using specific instructions from the individual manufacturer.
Quick operational checks can be performed using a field calibrator as a signal source while observing the valve stem position, mechanical position indicators, or flow indicators as input changes are made. Fluke loop calibrators provide a convenient source for simulating the controller output to a valve positioner.
The following example shows a general method for an in-field operational check of a valve fitted with an electronic valve positioner.
These methods may be adapted to various types of valves. However, manufacturer-specific instructions should always be consulted for proper and appropriate techniques. In the following example, valve operation and movement is checked either by feel or by observing valve stem movement.
Step 1: Basic Set-Up. Setting the Fluke 707 Loop Calibrator Current Output
Place the calibrator in the 4-20 milliamp output current mode. Connect the 707 to the input terminals of the valve positioner (see Figure 3).

Step 2: Zero Adjustment
Set the 707 to an output of four milliamps and allow some time for valve stem movement to stabilize. Quickly decrease the current from 4.0 to 3.9 milliamps by pressing and turning the vernier knob in a counter-clockwise direction.
You can operate the 707 with one hand while feeling the valve stem with your free hand to check for any sign of movement. Adjust for zero movement between these two current settings by using the zero adjustment on the positioner.
Increase and decrease current from 4.0 to 4.1 milliamps using the vernier knob in the depressed position. Ensure that the valve stem just begins movement above the 4.1 milliamp setting and is fully closed at 4.0 milliamps.
Step 3: Span (Full Open) Position Check
Using the 25% button, step the calibrator output value to 20 milliamps and allow the valve to stabilize.
Step the input to 20.1 milliamps using the vernier knob in the depressed position, turning clockwise while watching or feeling for movement of the valve stem. Minimize this movement using the span adjustment on the valve positioner.
Using the vernier knob in the depressed position, adjust the current up and down between 20.10 and 19.9 milliamps. There should be no movement of the valve stem above 20 milliamps and a slight movement below 20 milliamps.
Step 4: Check Zero and Span Again
Many positioners have interactive zero and span controls. And for such positioners, the adjustment you just made has likely thrown the zero adjustment out of calibration.
To ensure proper valve position adjustment, repeat Step 2 and Step 3. You may need to use the technique detailed in the “Making Fine Adjustments” section below.
Step 5: Linearity Check
For valves with linear action, linearity can be checked by setting the 707 to four milliamps and stepping current to 12 milliamps (50%) while observing valve travel. If your valve is of a non-linear type, refer to the valve manual for proper operational checks.
Step 6: Stroking the Valve
Checking for smooth valve operation is easy to accomplish using the slow ramp function of the 707.
- Set the calibrator to mA source mode and select the slow ramp function (˄) by pressing the 25% and 0-100% buttons simultaneously.
- Allow the calibrator to ramp through several cycles while watching or feeling for any abnormal operation of the valve, such as sticking in one position momentarily or making erratic movements.
Calibrating Voltage Input Signal Conditioners
The precision current sourcing and simulation capabilities of Fluke loop calibrators make them ideal for calibrating many 4-20 milliamp signal conditioners. However, there are many signal conditioners that require a precision voltage source for proper calibration.
Using a simple precision resistor and standard connector, Fluke loop calibrators can field calibrate many standard and non-standard voltage input signal conditioners. This approach works well for the 705, 707, 787B, and 789 loop calibration tools (this is not necessary with the 715 loop calibrator as it has a precision direct voltage output).
Voltage input signal conditioners come in many varieties. The most common are zero- to 10-volt, zero- to five-volt, and one to five-volt input levels. Typical outputs of these devices are an isolated or non-isolated zero- to 10-volt or four- to 20-milliamp current. Resistors with values of 250 to 500 ohms are common loop load resistors and provide voltage input levels as a function of the loop current (see Figure 4).

Using Fluke Loop Calibrators as a Voltage Source
A precision shunt resistor may be used to derive voltages for calibration using the calibrator’s current source mode. Using this system, Fluke loop calibrators are capable of generating voltages for devices with input spans as low as 10 millivolts to as high as 24 volts.
The table below gives values of precision resistors to accommodate a variety of voltage calibrations and the ideal Fluke calibrator for each application.
Resistor value | Sourced application | Generated current value | Fluke loop voltage | Calibrator |
10 Ω | mV transducer | 0-20.000 mA | 0-200.00 mV | 707, 705, 787, 789 |
250 Ω | 0-5 V Source | 0-20.000 mA | 0-5.000 V | 705, 707 |
1000 Ω | 0-10 V Source | 0-10.000 mA | 0-10.000 V | 705, 707, 787, 789 |
Note: Input impedance of the device under test should be ≥ 1 MΩ |
Table 1. Values of precision resistors to accommodate a variety of voltage calibrations
Constructing a Precision Load Resistor Assembly
A simple precision current shunt can be constructed using a precision RN60, a one-watt resistor (see table above for the correct value), a dual banana jack connector, and some test leads with alligator clips (see Figure 5). The RN60 class resistor is available from many commercial sources.
Construct the assembly as shown in Figure 5. This precision resistor assembly, coupled with the precision current sourcing capabilities of Fluke loop calibrators, generates precision voltages to cover one- to five-volt or two- to 10-volt applications.
The 1000-ohm assembly has an advantage in that it allows a direct one-to-one display correlation to voltage when sourcing current from the Fluke loop calibrator during calibration (one milliamp = one volt). The following example will utilize a 250-ohm assembly to take advantage of the zero to 100% and 25% buttons on the Fluke 707 (25% or four milliamps = one volt).
Calibrating the Signal Conditioner
The following is a procedure for calibrating a one- to five-volt input, four- to 20-milliamp output signal conditioner using the precision current shunt constructed in Figure 5.

Step 1: Setting the Fluke 707 to Source 4-20 mA
- With the shunt assembly in the “source” jacks, power the 707 on.
- Check the display. If the display does not read 4 mA, turn the 707 off and on again while holding the mode button for two seconds. The display should now read 4.000 mA.
Step 2: Calibrating
- Place a precision multimeter, such as the Fluke 187 DMM, set to DC current mode, in series with the output of the signal conditioner as shown in Figure 6.
- Connect the test leads from the precision shunt assembly to the signal conditioner input terminals, observing proper polarity.
- With the 707 set in the mA source mode, the display should read 4 mA (1.00 V across the shunt).
- Adjust the zero control on the signal conditioner for an indication of 4 mA on the DMM.
- Press the 0-100 % button on the 707 until the display reads 20 mA. Then adjust the span adjustment on the signal conditioner until the display on the DMM reads 20 mA.
- Push the 0-100 % button and the 707 should read 4. Verify the meter connected to the output signal conditioner reads 4 mA.1
- Calibration is now complete.

Step 3: Checking Linearity
Once zero and span controls have been properly set, signal conditioner linearity may be verified using the following procedure. This procedure will check zero, 25%, 50%, 75%, and span settings for signal conditioner linearity.
- With the precision resistor assembly in place, adjust the source current of the Fluke loop calibrator to 4 mA (1.0 V) using the 25% button. The DMM displays 4 mA.
- Using the 25% button, step the source current to 25%, 50%, 75%, and 100% and note the corresponding values. Table 2 below shows the correct values of output for a linear signal conditioner. (If values differ from that shown in the table by more than the linearity specification of the signal conditioner, contact the signal conditioner manufacturer or replace the device.)
Fluke display reading | % Input | Input voltage | Output current |
4.000 | 0 | 1.000 V | 4.000 mA |
8.000 | 25 | 2.000 V | 8.000 mA |
12.000 | 50 | 3.000 V | 12.000 mA |
16.000 | 75 | 4.000 V | 16.000 mA |
20.000 | 100 | 5.000 V | 20.000 mA |
Table 2. Correct value of output for a linear signal conditioner
Making Fine Adjustments
Many signal conditioners with zero- to 20-milliamp and four- to 20-milliamp outputs are notorious for zero and span control interaction. If, when checking linearity in the calibration section, your output meter displayed a value higher or lower than four milliamps, perform the following steps to affect the required four and 20-milliamp display on the output meter.
Some signal conditioners have non-interactive controls and do not require this procedure.
- Note the value above or below four milliamps that was displayed on the output meter when you returned to a source value of four milliamps on the 707. Adjust the zero control on the signal conditioner so the value of the output meter shows one-half the difference of the remaining milliamp value to four milliamps.
Example: If your display reading at zero input in Step 7 was 3.50 milliamps, adjust the output (with 4.00 mA source current) to display a reading of 3.75 mA. This is one-half the delta toward the desired value of four milliamps:
4.00 - 3.50 = 0.50
0.05 / 2 + 3.50 = 3.75 (or one-half the difference between the reading and the desired value.) - Set the source current of the 707 to 20 milliamps using the 0-100% button. Note the “output” meter display reading. Adjust the span control of the signal conditioner one-half the delta from 20 milliamps.
Example: If the output display reads 21.00 mA, adjust the span control to 20.50 mA (one-half the delta to the required value of 20.00 mA). - Repeat this “one-half step” process until the required output is obtained. There are signal conditioners that have non-interactive controls that do not require this procedure.
Verifying Process Scaled for Indicators
Scaled process indicators are used to provide information about a process either locally or to a control room located a distance away.
These indicators typically take a milliamp measurement in series with the four- to 20-milliamp loop signal. Or, they measure a one- to five-volt drop across a 250-ohm resistor in series with the four- to 20-milliamp signal. (Note that a four- to 20-milliamp signal through a 250-ohm resistor produces a one- to five-volt drop).
For indicators with a mA input, the direct mA current output of a Fluke 705, 707, 715, 787, or 789 can be applied directly to the input of the indicator.
For voltage input indicators, a 715 is ideal with its direct voltage output. Or use a resistor across the output of a 705, 707, 787, or 789 as described earlier in this article (“Using Fluke loop calibrators as a voltage source”).
This example shows how to use the 707 to verify an mA input indicator. Make connections as shown in Figure 7.

- Power the 707 up; the default output should be 4 mA. Note the indication, (digital or analog) which should be approximately 0%.
- Press the 0-100% button on the 707; it is now in the span check mode and is outputting 20 milliamps. Note the indication (approximately 100%).
- If testing the linearity is necessary, use the 25% button to step the mA output in four-milliamp steps and record the indications.
- To calculate the errors in percent, use the formula:
Nominal - actual/span x 100
Nominal is the ideal value, actual is the recorded measurement and span is 16 (4-20 mA = a 16 mA span).
Example: If the indication with 0% applied is 1%, calculate error as such:
0-1/16 = .0625 X 100 = 6.25% error
Calculate error based on the recorded indications and compare to the tolerances for the indicator. If any of the calculated errors are too large, adjustment may be necessary. Normally, there are at least two adjustments for analog indicators: zero and span. The zero adjustment is typically on the faceplate of the indicator. - With an output of four milliamps from the 707, adjust the zero indication. Span adjustment is either a hard adjustment or accomplished by bending a linkage on the meter movement. Refer to the manufacturer’s procedure for this adjustment.
- Apply a 20-milliamp signal to the indicator and make the adjustment as specified. Once the adjustment is completed, re-verify the indicator and confirm the adjustments had the desired effect. If the indicator still fails the test, it will either need to be readjusted until a satisfactory result is attained, or replaced.
Voltage Input Indicators
The procedure for using the 707 to verify voltage input indicators is almost identical to the procedure outlined. The primary difference is the addition of the precision 250-ohm adapter.
Glossary of Terms
Four- to 20-milliamp (4-20 mA) loop: A process control circuit in which the devices communicate process variable signals and control signals in a range from a low of four milliamps (mA) mA to a high of 20 milliamps. This corresponds to the older pneumatic system, which ranged from three to 15 pound-force per square inch (psi).
Compliance voltage: The voltage a current source develops when attempting to drive a milliamp signal through a resistive load.
DMM: Digital multimeter. A meter that measures multiple electrical quantities, such as voltage, current, and resistance.
Electronic valve positioners: A device that controls the position of a valve, based on an analog or digital electrical input. Many applications use, alternatively, pneumatic valve positioners to control valve position based on a pneumatic input signal (three to 15 psi).
ATEX/Ex: ATmospheric EXplosibles (French for explosive atmospheres) rating. The European ATEX directive (94/9/EC) applies to all industrial equipment that will or may be used in an explosive atmosphere. Regulations state that measures must be taken to protect personnel, plants, and the environment by ensuring that potentially explosive atmospheres cannot be ignited.
FM approval: Factory Mutual (FM) is a regulatory agency that provides third-party product certification for intrinsically safe equipment used in the United States. FM verifies electrical equipment compliance based on accepted standards from FM, the American National Standards Institute (ANSI), and the International Electrotechnical Commission (IEC).
Ground loop: An undesirable circuit that develops because individual grounding points or paths are tied to different earth potentials instead of to the common grounding or bonding points (e.g., the main bonding jumper). This results in a difference of potential (voltage) between the grounds and allows current to flow between them via the process loop.
Linearity: The closeness of a calibration curve to a specified straight line. Linearity is expressed as the maximum deviation of any calibration point from a specified straight line.
Intrinsically safe: An apparatus containing circuits in which any spark or thermal effect is incapable of causing ignition of a mixture of flammable or combustible material in air under prescribed test conditions.
Loop-powered isolator: A device that produces an electrically isolated mirror image of the input side 4-20 mA current.
mA: Milliamp; a unit of electric current equal to one-thousandth of an ampere.
Precision current shunt: A conductor joining two points in a circuit to form a parallel circuit, through which a precision voltage can be measured or derived.
RTD: A temperature measurement sensor whose resistance corresponds to a specific temperature. This device will change its resistance in response to a change in temperature.
Signal conditioner: A circuit to modulate a signal so as to make it intelligible to, or compatible with, another device, including such manipulation as pulse shaping, pulse clipping, compensating, digitizing, and linearizing. The input side of a signal conditioner might be the output of a sensor — in fractions of a millivolt — while the output side of the signal conditioner is 4-20 mA.
Strain gauge: A measuring element for converting force, pressure, tension, etc., into an electrical signal.
Thermocouple: A junction of dissimilar metals that generates a small voltage correlated to the temperature of the junction.
µA or uA: Microamp; a unit of electric current equal to one-millionth of an ampere.
Vernier: A small, movable, graduated scale running parallel to the fixed graduated scale and used for measuring a fractional part of one of the divisions of the fixed scale.