| Detailed Specifications |
| General |
| Display:1999 digit LCD | Display with special symbols, digit height 25 mm, fluorescent backlight |
| User interface | Instant measurement through TURN and START one button concept. The only operating elements are rotary switch and START button |
| Robust, water and dust resistant | Instrument is designed for tough environmental conditions (rubber protective cover, IP56) |
| Memory | Internal memory storage up to 1500 records accessible via USB port |
| Temperature Range |
| Operating temperature | -10 °C to 50 °C (14 °F to 122 °F) |
| Storage temperature | -30 °C to 60 °C (-22 °F to 140 °F) |
| Temperature coefficient | ± 0.1 % of reading/°C <18 °C >28 °C |
| Intrinsic error | Refers to the reference temperature range and is guaranteed for 1 year |
| Operating error | Refers to the operating temperature range and is guaranteed for 1 year |
| Climatic class | C1 (IEC 654-1), -5 °C to +45 °C (23° to +115° F), 5 % to 95 % RH |
| Protective type | IP56 for case, IP40 for battery door according to EN60529 |
| Safety | Protection by double and/or reinforced insulation. max. 50 V to earth. IEC61010-1: Pollution degree 2 |
| EMC (emission immunity) | IEC61326-1: Portable |
| Quality system | Developed, designed and manufactured according to DIN ISO 9001 |
| External voltage | V ext, max = 24 V (dc, ac < 400 Hz), measurement inhibited for higher values |
| V ext rejection | > 120 dB (162⁄3, 50, 60, 400 Hz) |
| Measuring time | Typical 6 seconds |
| Max. overload | 250 V rms (pertains to misuse) |
| Auxiliary power | 6 x 1.5 V Alkaline (type AA LR6) |
| Battery life span | Typical > 3,000 measurements |
| Dimensions (WxHxD) | 250 mm x 133 mm x 187 mm (9.75 in x 5.25 in x 7.35 in) |
| Weight | 1.1 kg (2.43 lb) including batteries 7.6 kg (16.8 lb) incl. accessories and batteries in carrying case |
| RA 3-Pole Ground Resistance Measurement (IEC 1557-5) |
| Switch position | RA 3-pole |
| Resolution | 0.001 Ω to 10 Ω |
| Measuring range | 0.020 Ω to 19.99 kΩ |
| Accuracy | ± (2 % rdg + 3 d) |
| Operating error | ± (5 % rdg + 3 d) |
|
| Measuring Principle: Current and Voltage Measurement |
| Measuring voltage | Vm = 48 V ac |
| Short-circuit current | > 50 mA |
| Measure frequency | 128 Hz |
| Probe resistance (RS) | Max 100 kΩ |
| Auxiliary earth electrode resistance (RH) | Max 100 kΩ |
| Additional error from RH and RS | RH[kΩ]•••RS[kΩ]/RA[Ω]•••0.2 % |
Monitoring of RS and RH with error indicator. Automatic range selection. Measurement is not performed if the current through the current clamp is too low. |
| RA 4-Pole Ground Resistance Measurement (IEC 1557-5) |
| Switch position | RA 4-pole |
| Resolution | 0.001 Ω to 10 Ω |
| Measuring range | 0.020 Ω to 19.99 kΩ |
| Accuracy | ± (2 % rdg + 3 d) |
| Operating error | ± (5 % rdg + 3 d) |
| Measuring Principle: Current and voltage Measurement |
| Measuring voltage | Vm = 48 V ac |
| Short-circuit current | > 50 mA |
| Measure frequency | 128 Hz |
| Probe resistance (RS + RES) | Max 100 kΩ |
| Auxiliary earth electrode resistance (RH) | Max 100 kΩ |
| Additional error from RH and RS | RH[kΩ]•••RS[kΩ]/RA[Ω]•••0.2 % |
Monitoring of RS and RH with error indicator. Automatic range selection. |
| RA 3-Pole Selective Ground Resistance Measurement with Current Clamp (RA with Clamp ) |
| Switch position | RA 3-pole with clamp |
| Resolution | 0.001 Ω to 10 Ω |
| Measuring range | 0.020 Ω to 19.99 kΩ |
| Accuracy | ± (7 % rdg + 3 d) |
| Operating error | ± (10 % rdg + 5 d) |
Measuring Principle: Current/Voltage Measurement (with External Current Clamp) |
| Measuring voltage | Vm = 48 V ac |
| Short-circuit current | > 50 mA |
| Measure frequency | 128 Hz |
| Probe resistance (RS) | Max 100 kΩ |
| Auxiliary earth electrode resistance (RH) | Max 100 kΩ |
Monitoring of RS and RH with error indicator. Automatic range selection. Measurement is not performed if the current through the current clamp is too low. |
| RA 4-Pole Selective Ground Resistance Measurement with Current Clamp (RA with Clamp ) |
| Switch position | RA 4-pole with clamp |
| Resolution | 0.001 Ω to 10 Ω |
| Measuring range | 0.020 Ω to 19.99 kΩ |
| Accuracy | ± (7 % rdg + 3 d) |
| Operating error | ± (10 % rdg + 5 d) |
| Measuring Principle: Current/Voltage Measurement (with External Current Clamp) |
| Measuring voltage | Vm = 48 V ac |
| Short-circuit current | > 50 mA |
| Measure frequency | 128 Hz |
| Probe resistance (RS) | Max 100 kΩ |
| Auxiliary earth electrode resistance (RH) | Max 100 kΩ |
Monitoring of RS and RH with error indicator. Automatic range selection. Measurement is not performed if the current through the current clamp is too low. |
| Stakeless Ground Loop Measurement (2 Clamps ) |
| Switch position | RA 4-pole 2 clamps |
| Resolution | 0.001 Ω to 10 Ω |
| Measuring range | 0.020 Ω to 19.99 kΩ |
| Accuracy | ± (7 % rdg + 3 d) |
| Operating error | ± (10 % rdg + 5 d) |
| Measuring Principle: Stakeless Measurement of Resistance in Closed Loops Using Two Current Transformers |
| Measuring voltage | Vm = 48 V ac |
| Measure frequency | 128 Hz |
| Noise current (IEXT) | Max. IEXT = 10 A (ac) (RA < 20 Ω) |
| Max. IEXT = 2 A (ac) (RA > 20 Ω) |
Automatic range selection. The information regarding stakeless ground loop measurements is only valid when used in conjunction with the recommended current clamps at the minimum distance specified. |