Fluke FEV300 EV Charging Station Test Adapter Kit: 1664 FC+ Installation Tester and Type 2 Connector
Key features
- Safely test the PE conductor for possible presence of dangerous voltage against earth
- Simulate various current capabilities of charging cables
- Simulate vehicle charging states
- Simulate PE error (earth fault)
- Includes Fluke 1664 FC to perform installation tests and Type 2 connector
Product overview: Fluke FEV300 EV Charging Station Test Adapter Kit: 1664 FC+ Installation Tester and Type 2 Connector
The FEV300 with 1664 FC Multifunction Installation Tester is a complete kit designed to test the function and safety of charging stations mode 3 for AC charging. This test adapter simulates the presence of an electrical vehicle, allowing you to conduct tests in combination with the Fluke 1664 FC installation tester to quickly and efficiently test to all local regulations without opening the charging station. Use the FEV300 to verify a charging station is working properly after install, during periodic maintenance or troubleshoot a charging station if it is not delivering the appropriate charge. With the adapter kit, charging stations can be tested in accordance with IEC/EN 61851-1 and IEC/HD 60364-7-722.
Run seven installation tests in one sequence
The FEV300 PE grounding protection pre-test verifies that there is no presence of dangerous voltage at the ground terminal. Connect the 1664 FC to the FEV300 to run seven installation tests automatically in one sequence through a single connection. The 1664 FC tests to all local regulations and allows you to share test results in real time over your smartphone via Fluke Connect Measurements.
Safety, simplicity and convenience
Perform a variety of tests including ground fault checks, insulation of wires, measuring voltage and duty cycle to see max current available for charging all in one adapter that safely integrates with the Fluke portfolio of test and measurement tools. There is no need to bring an electric vehicle onsite for charging station troubleshooting: the FEV300 adapter acts as an electric vehicle when connected to a charging station for easy performance and maintenance testing.
- PE Pre-Test: Safely pre-test the PE conductor for possible presence of dangerous voltage against earth
- Proximity Pilot (PP) state “Cable Simulation”: The PP State rotary switch enables the adapter to simulate various current capabilities of charging cables
- Control Pilot (CP) state “Vehicle Simulation”: Use the CP State rotary switch selector to simulate various charging states
- Simulation of CP error “E”: Simulate PE error (Earth fault)
Test EV charging station RCD type A-EV or RDC-DD DC protection devices
Perform tests with the 1664 FC on EV charging station DC protection devices using the RCD type B (smooth DC currents) VAR mode, which generates the test currents for RCD type A-EV or RDC-DD acc. to IEC 62955 (6/60/200 mA and ramp <2 to 6 mA ramp). This allows the quick an easy testing of additional 6 mA DC monitors on charging points.
Save time and enhance collaboration
Because the 1664 FC is Fluke Connect®-enabled, you can send test results to your smartphone, save them to the cloud, and share measurements in real time with team members through a ShareLive video call. It's the fastest way to let your team see what you see, and to help you get approvals without leaving the field. Fluke Cloud™ storage allows you to retrieve stored results whether you are in the office or in the field to make decisions in real time. You get world-class data protection and can import the data, manage files transferred from instruments, or manually enter data as needed into TruTest™ Software to process and generate certificates quickly and easily. Designed to eliminate the hassle associated with traditional electrical system data management and reporting, TruTest™ Software is an ideal solution for producing easy-to-understand reports for clients.
Compatible products:
- Fluke 1663 Multifunction Testers
- Fluke 1664 FC Installation Multifunction Testers
- Fluke 87V Industrial Multimeter
- Fluke 120B Series Industrial ScopeMeter® handheld Oscilloscopes
- Fluke 1587 FC Insulation Multimeter
- Fluke 1732 and 1734 Three Phase Power Measurement Logger
- Fluke 1735 Three-Phase Power Quality Logger
- Fluke 1736 and 1738 Three-Phase Power Quality Loggers
What's in the box:
- FEV300/BASIC Test Adapter
- 1664 FC Installation Multifunction Tester
- FEV300-CON-TY2 Type 2 Plug
- Carrying case
Specifications: Fluke FEV300 EV Charging Station Test Adapter Kit: 1664 FC+ Installation Tester and Type 2 Connector
Specifications: Fluke FEV300 EV Charging Station Test Adapter Kit with 1664 FC Installation Tester and Type 2 Connector
General features | |
Input voltage | Up to 250 V (single phase system) / up to 480 V (three phase system), 50/60 Hz, max 10 A |
Internal power consumption | 3 W max. |
FEV300-CON-TY2 Plug | AC charging mode 3, suitable to IEC 62196-2 type 2 socket outlet or fixed cable with vehicle connector (type 2, 7P three-phase) |
FEV300-CON-TY1 Plug | AC charging mode 3, suitable to IEC 62196-2 type 1 or SAE J1772 with vehicle connector (type 1, 5P single-phase) |
Dimensions (H × W × D) | 110 × 45 × 220 mm length without connection cable and test cable |
Weight (including type 1 or type 2 connection cable) | Approx. 1 kg |
Safety standards | IEC/EN 61010-1, pollution degree 2 IEC/EN 61010-2-030, CAT II 300 V, protection class II |
Ingress protection | IEC 60529: IP54 (housing) IEC 60529: IP54 (sockets with protection caps in place, connectors in connected condition or with protection caps in place, otherwise IP20) |
Operating temperature | -20 °C to 40 °C |
Storage temperature | -20 °C to 50 °C |
Operating humidity range | 10 % to 85 % relative humidity non-condensing |
Storage relative humidity | 0 % to 85 % non-condensing |
Operating altitude | 2000 m max. |
Functions | |
PE Pre-Test | Visible indication >50 V AC/DC between PE conductor and touch sensor |
PP Simulation | Open, 13 A, 20 A, 32 A, 63 A |
CP States | State A, B, C, D |
CP Error state “E” | On/off (CP signal short-circuited to PE) |
PE Error state "F" (Earth fault) | On/off (interruption of PE conductor) |
Outputs (for test purpose only) | |
Measuring terminals L1, L2, L3, N, PE | Max. 250/480 V, max. 10 A |
CP signal output terminals | Approx. +/-12 V |
Caution: In case of wrong wiring or error of the charging station these terminals may be hazardous. |
AC voltage measurement | ||
Range | 500 V | |
Resolution | 0.1 V | |
Accuracy 45 Hz – 66 Hz | 0.8% + 3 | |
Input impedance | 360 kΩ | |
Overload protection | 660 V rms | |
Continuity testing (RLO) | ||
Range (autoranging) | 20 Ω / 200 Ω / 2000 Ω | |
Resolution | 0.01 Ω / 0.1 Ω / 1 Ω | |
Open Circuit Voltage | >4 V | |
Insulation resistance measurement (RISO) | ||
Test voltages | 50-100-250-500-1000 V | |
Accuracy of test voltage (at rated test current) | +10%, -0% | |
Test voltage | 50 V 100 V 250 V 500 V 1000 V | |
Insulation resistance range | 20 MΩ / 50 MΩ 20 MΩ / 100 MΩ 20 MΩ / 200 MΩ 20 MΩ / 200 MΩ / 500 MΩ 20 MΩ / 200 MΩ / 1000 MΩ | |
Resolution | 0.01 MΩ / 0.1 MΩ 0.01 MΩ / 0.1 MΩ 0.01 MΩ / 0.1 MΩ 0.01 MΩ / 0.1 MΩ / 1 MΩ 0.01 MΩ / 0.1 MΩ / 1 MΩ | |
Test current | 1 mA @ 50 kΩ 1 mA @ 100 kΩ 1 mA @ 250 kΩ 1 mA @ 500 kΩ 1 mA @ 1 MΩ | |
Loop and line impedance (ZI) | ||
Range | 10 Ω (Hi current mΩ mode)/20 Ω/200 Ω/2000 Ω | |
Resolution | 0.001 Ω/ 0.01 Ω/ 0.1 Ω/1 Ω | |
Prospective earth fault current, PSC test | ||
Range | 1000 A / 10 kA (50 kA) | |
Resolution | 1 A / 0.1 kA | |
Computation | Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively. | |
RCD testing, RCD types tested | ||
RCD Type | AC¹ G²,S³ | |
Model 1663 | A4, AC¹, G²,S³ | |
Model 1664 FC | A, AC, B5, S | |
Notes | ¹Responds to AC ²General, no delay ³Time delay ⁴Responds to pulsed signal ⁵Responds to smooth DC signal | |
Tripping speed test (ΔT) | ||
Current settings¹ | 10-30-100-300-500-1000 mA – VAR 10-30-100 mA | |
Multiplier | x ½, x 1 x 5 VAR Mode Type B - 6, 60, 200 mA | |
Measurement range | RCD Type G | 310 ms 50 ms |
RCD Type S | 510 ms 160 ms | |
EV / RDC-DD | 6 mA - 10s 60 mA - 0.3s 200 mA - 0.1s | |
Notes | ¹1000 mA type AC only 700 mA maximum type A in VAR mode The VAR Mode at RCD type B (smooth DC currents) generates the test currents acc. to IEC 62955 for RCD type A-EV or RDC-DD (6/60/200 mA and ramp <2 to 6 mA). | |
RCD/FI-Tripping Current Measurement/Ramp Test (IΔN) | ||
Current range | 30% to 110% of RCD rated current¹ <2 mA to 6 mA smooth DC³ | |
Step size | 10% of IΔN² Linear rising within 30 s | |
Dwell time | RCD Type G | 300 ms/step |
RCD Type S | 500 ms/step | |
Measurement accuracy | ±5% | |
Specified trip current ranges (EN 61008-1) | 50% to 100% for Type AC 35% to 140% for Type A (>10 mA) 35% to 200% for Type A (≤10 mA) 50% to 200% for Type B | |
Notes | ¹30% to 150% for Type A IΔN > 10 mA 30% to 210% for Type A IΔN = 10 mA 20% to 210% for Type B ²5% for Type B ³For RCD type A-EV/RDC-DD acc. to IEC 62955 | |
Earth Resistance Test (RE) | ||
Range | 200 Ω / 2000 Ω | |
Resolution | 0.1 Ω / 1Ω | |
Frequency | 128 Hz | |
Output Voltage | 25 V | |
Phase Sequence Indication | ||
Icon | Phase Sequence indicator is active. | |
General Specifications | ||
Size (L x W x H) | 10 x 25 x 12.5 cm | |
Weight (incl. batteries) | 1.3 Kg | |
Battery size, quantity | Type AA, 6 ea. | |
Sealing | IP-40 | |
Safety | Complies with EN/IEC 61010-1 and EN/IEC 61010-2-034 | |
Overvoltage | CAT III / 500V; CAT IV 300V | |
Performance | EN61557-1 to EN61557-7 and EN61557-10 |
Models: Fluke FEV300 EV Charging Station Test Adapter Kit: 1664 FC+ Installation Tester and Type 2 Connector
Includes:
- FEV300/BASIC Test Adapter
- 1664 FC Installation Multifunction Tester
- FEV300-CON-TY2 Type 2 Plug
- Carrying case