Fluke 393 FC Solar Clamp Meter CAT III 1500 V
Compare products: clamp meters and amp meters
- Fluke 323 True RMS Clamp Meter
- Fluke 324 True-RMS Clamp Meter with Temperature & Capacitance
- Fluke 325 True RMS Clamp Meter
- Fluke 373 True-RMS AC Clamp Meter
- Fluke 374 FC True-RMS AC/DC Clamp Meter
- Fluke 375 FC True-RMS AC/DC Clamp Meter
- Fluke 376 FC True-RMS Clamp Meter
- Fluke 377 FC Non-Contact Voltage True-rms AC/DC Clamp Meter with iFlex
- Fluke 378 FC Non-Contact Voltage True-rms AC/DC Clamp Meter with iFlex
- Fluke 353 True RMS 2000 A Clamp Meter
- Fluke 355 True RMS 2000 A Clamp Meter
- Fluke 381 Remote Display True RMS AC/DC Clamp Meter with iFlex®
- Fluke 368 FC Leakage Current Clamp Meter
- Fluke 369 FC Leakage Current Clamp Meter
- Fluke 902 FC True-RMS HVAC Clamp Meter
- Fluke a3000 FC Wireless AC Current Clamp Module
- Fluke a3001 FC Wireless iFlex® AC Current Module
- Fluke a3002 FC Wireless AC/DC Current Module
- Fluke a3003 FC Wireless 2000 A DC Current Clamp Meter
- Fluke a3004 FC Wireless 4-20 mA DC Clamp Meter
- Fluke v3000 FC Wireless AC Voltage Module
- Fluke v3001 FC Wireless DC Voltage Module
- Fluke t3000 FC Wireless Temperature Module
Key features
- Measure safely with CAT III 1500 V rated clamp meter
- Thin jaw for access to cables in crowded combiner boxes
- Sturdy IP54 rated for outdoor use and solar installation
- Work efficiently with dc power measurement, audio polarity and visual continuity
Sale ends soon.
Shop now!
DAYS
HR
MIN
SEC
A$1,496.00
Product overview: Fluke 393 FC Solar Clamp Meter CAT III 1500 V
The 393 FC CAT III 1500 V True-rms Clamp Meter with iFlex is designed for solar photovoltaic (PV) installation technicians and maintenance professionals who work in high voltage dc environments: PV arrays, wind power, electric railways, data centers battery banks for uninterruptible power supplies. The clamp will measure up to 1500 V dc, 1000 V ac, and up to 999.9 A dc or ac through the clamp jaw. The included iFlex flexible current probe extended ac current measurements up to 2500 amps. This clamp has a thin jaw, giving you access to cables in crowded combiner boxes. Test leads are designed with your work in mind, and are also rated to CAT III 1500 V dc.
Key functions of the solar clamp meter:
- IP54 rated, ideal for work outdoors including PV panel testing
- DC power measurement, showing readings in kVA
- Audio Polarity indicator helps prevent accidental miswires
- Visual Continuity turns provide a bright green light in the display, ideal when working in dark and noisy environments
- Logging and reporting of test results via Fluke Connect software
- When measuring ac current the included iFlex flexible current probe gives you unparalleled access to cable is tight spaces. The iFlex probe can be twisted through extremely small spaces and provide accurate current measurements.
The world's first CAT III 1500 V true-RMS solar clamp meter
What's in the box:
- Fluke 393 FC CAT III 1500 V TRMS clamp meter
- Test leads, CAT III 1500 V rated, right angle plugs, with safety caps
- iFlex 18 inch flexible current probe
- TPAK magnetic hanging strap
- Premium carrying case
- 3-year warranty
Specifications: Fluke 393 FC Solar Clamp Meter CAT III 1500 V
Specifications: | |||
General | |||
Maximum voltage between any Terminal and Earth Ground | |||
AC | 1000 V | ||
DC | 1500 V | ||
Batteries | 2 AA IEC LR6 alkaline | ||
Display | Dual display with backlight | ||
Automatic Power Off | 20 minutes | ||
Electrical | |||
Accuracy | |||
Accuracy is specified for 1 year after calibration, at operating temperatures of 18 °C to 28 °C, relative humidity at 0 % to 75 %. Accuracy specifications take the form of: ±([% of Reading] + [Number of Least Significant Digits]). | |||
Temperature Coefficients | Add 0.1 x specified accuracy for each °C > 28 °C or < 18 °C | ||
AC Current: Jaw | |||
Range | 999.9 A | ||
Resolution | 0.1 A | ||
Accuracy | 2 % + 5 digits (10 Hz to 100 Hz) | ||
2.5 % + 5 digits (100 Hz to 500 Hz) | |||
Crest Factor (50/60 Hz) | 2.5 @600.0 A | ||
3.0 @500.0 A | |||
1.42 @999.9 A | |||
Add 2 % for C.F. >2 | |||
AC Current: Flexible Current Probe | |||
Range | 999.9 A | ||
2500 A | |||
Resolution | 0.1 A (≤999.9 A) | ||
1 A (≤2500 A) | |||
Accuracy | 3 % RD + 5 digits (10 Hz to 500 Hz) | ||
Crest Factor (50/60Hz) | 2.5 @1400 A | ||
3.0 @1100 A | |||
1.42@2500 A | |||
Add 2 % for C.F. >2 | |||
Position Sensitivity | |||
Distance from Optimum | i2500-10 Flex | i2500-18 Flex | Error |
A | 0.5 in (12.7 mm) | 1.4 in (35.6 mm) | ±0.5 % |
B | 0.8 in (20.3 mm) | 2.0 in (50.8 mm) | ±1.0 % |
C | 1.4 in (35.6 mm) | 2.5 in (63.5 mm) | ±2.0 % |
Measurement uncertainty assumes centralized primary conductor at optimum position, no external electrical or magnetic field, and within operating temperature range. | |||
DC Current | |||
Range | 999.9 A | ||
Resolution | 0.1 A | ||
Accuracy | 2 % RD + 5 digits[1] | ||
[1] When using the ZERO (B) function to compensate for offsets. | |||
AC Voltage | |||
Range | 600.0 V | ||
1000 V | |||
Resolution | 0.1 V (≤600.0 V) | ||
1 V (≤1000 V) | |||
Accuracy | 1 % RD + 5 digits (20 Hz to 500 Hz) | ||
DC Voltage | |||
Range | 600.0 V | ||
1500 V | |||
Resolution | 0.1 V (≤600.0 V) | ||
1 V (≤1500 V) | |||
Accuracy | 1 % RD + 5 digits | ||
mV dc | |||
Range | 500.0 mV | ||
Resolution | 0.1 mV | ||
Accuracy | 1 % RD + 5 digits | ||
Amps Frequency: Jaw | |||
Range | 5.0 Hz to 500.0 Hz | ||
Resolution | 0.1 Hz | ||
Accuracy | 0.5 % RD + 5 digits | ||
Trigger Level | 5 Hz to 10 Hz, ≥10 A | ||
10 Hz to 100 Hz, ≥5 A | |||
100 Hz to 500 Hz, ≥10 A | |||
Amps Frequency: Flexible Current Probe | |||
Range | 5.0 Hz to 500.0 Hz | ||
Resolution | 0.1 Hz | ||
Accuracy | 0.5 % RD + 5 digits | ||
Trigger Level | 5 Hz to 20 Hz, ≥25 A | ||
20 Hz to 100 Hz, ≥20 A | |||
100 Hz to 500 Hz, ≥25 A | |||
Voltage Frequency | |||
Range | 5.0 Hz to 500.0 Hz | ||
Resolution | 0.1 Hz | ||
Accuracy | 0.5 % RD + 5 digits | ||
Trigger Level | 5 Hz to 20 Hz, ≥5 V | ||
20 Hz to 100 Hz, ≥5 V | |||
100 Hz to 500 Hz, ≥10 V | |||
DC Power | |||
Range | 600.0 kVA (600.0 V dc range) | ||
1500 kVA (1500 V dc range) | |||
Resolution | 0.1 kVA | ||
1 kVA | |||
Accuracy | 2 % RD + 2.0 kVA | ||
2 % RD + 20 kVA | |||
Resistance | |||
Range | 600.0 Ω | ||
6000 Ω | |||
60.00 kΩ | |||
Resolution | 0.1 Ω (≤600.0 Ω) | ||
1 Ω (≤6000 Ω) | |||
0.01 kΩ (≤60.00 kΩ) | |||
Accuracy | 1 % RD + 5 digits | ||
Capacitance | |||
Range | 100.0 μF | ||
1000 μF | |||
Resolution | 0.1 μF (≤100.0 μF) | ||
1 μF (≤1000 μF) | |||
Accuracy | 1 % RD + 5 digits | ||
Inrush Trigger Level | 5 A | ||
Mechanical | |||
Size (L x W x H) | 281 mm x 84 mm x 49 mm | ||
Weight (with batteries) | 520 g | ||
Jaw Opening | 34 mm | ||
Flexible Current Probe Diameter | 7.5 mm | ||
Flexible Current Probe Cable Length | |||
(head to electronics connector) | 1.8 m | ||
Environmental | |||
Operating Temperature | -10 °C to 50 °C | ||
Storage Temperature | -40 °C to 60 °C | ||
Operating Humidity | Non condensing (<10°C) | ||
≤90 % RH (at 10 °C to 30 °C) | |||
≤75 % RH (at 30 °C to 40 °C) | |||
≤45 % RH (at 40 °C to 50 °C) | |||
Operating Altitude | 2000 m | ||
Storage Altitude | 12 000 m | ||
Ingress Protection (IP) Rating | IEC 60529: IP54 non-operating | ||
Electromagnetic Compatibility (EMC) | |||
International | IEC 61326-1: Portable, Electromagnetic Environment, IEC 61326-2-2 CISPR 11: Group 1, Class A | ||
Group 1: Equipment has intentionally generated and/or uses conductively-coupled radio frequency energy that is necessary for the internal function of the equipment itself. | |||
Class A: Equipment is suitable for use in all establishments other than domestic and those directly connected to a low-voltage power supply network that supplies buildings used for domestic purposes. There may be potential difficulties in ensuring electromagnetic compatibility in other environments due to conducted and radiated disturbances. | |||
Caution: This equipment is not intended for use in residential environments and may not provide adequate protection to radio reception in such environments. | |||
Korea (KCC) | Class A equipment (Industrial Broadcast & Communications Equipment) | ||
Class A: Equipment meets requirements for industrial electromagnetic wave equipment and the seller or user should take notice of it. This equipment is intended for use in business environments and not to be used in homes. | |||
USA (FCC) | 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103. | ||
Safety | |||
General | IEC 61010-1, Pollution Degree 2 | ||
Measurement | IEC 61010-2-032: CAT III 1500 V / CAT IV 600 V | ||
IEC 61010-2-033: CAT III 1500 V / CAT IV 600 V | |||
Wireless Radio | |||
Radio frequency certification | FCC ID: T68-FBLE, IC: 6627A-FBLE | ||
Wireless Radio Frequency Range | 2400 MHz to 2483.5 MHz | ||
Output Power | <100 mW | ||
SIMPLIFIED EU DECLARATION OF CONFORMITY | |||
Hereby, Fluke declares that the radio equipment contained in this Product is in compliance with Directive 2014/53/EU. | |||
The full text of the EU declaration is available at the following Internet address: | |||
www.fluke.com/en-us/declaration-of-conformity |
Models: Fluke 393 FC Solar Clamp Meter CAT III 1500 V
393 FC
393 FC CAT III 1500 V True-rms Clamp Meter with iFlex
Included:
- Fluke 393 FC CAT III 1500 V True-rms Clamp Meter with iFlex
- Test leads, CAT III 1500 V rated, right angle plugs, with safety caps
- iFlex 18 inch flexible current probe
- TPAK magnetic hanging strap
- Premium carrying case
- 3-year warranty