English

Fluke 1664 FC Installation Multifunction Testers

  • bvseo_sdk, p_sdk, 3.2.1
  • CLOUD, getAggregateRating, 21.33ms
  • REVIEWS, PRODUCT
  • bvseo-msg: HTTP status code of 404 was returned; HTTP status code of 404 was returned;
  • Fluke 1664 FC Multifunction Installation Tester
  • Fluke 1664 FC Multifunction Installation Tester
  • Fluke 1664 FC Multifunction Installation Tester
  • Fluke 1664 FC Multifunction Installation Tester

Key features

Multifunction tester that tests to all local regulations

  • Includes "Insulation Pre-test" that detects when appliances are connected to the system and stops the test
  • Runs seven installation tests automatically in one sequence with a single connection through Auto Test
  • Allows you to share test results in real time over your smartphone via Fluke Connect Measurements
  • 6 mA RDC-DD testing for EV charging stations
Back order (ships 07/09/2024)
A$4,700.30
Tax included where applicable
Genuine Fluke product
Free shipping

Product overview: Fluke 1664 FC Installation Multifunction Testers

Fluke 1664 FC Multifunction Installation Tester helps expedite installations

The 1664 FC puts a lot of testing power in your hands to quickly and efficiently test to all local regulations, protect appliances, and share test results in real time over your smartphone.

Protect appliances from accidental damage

The Fluke 1664 FC is the only tester with "Insulation PreTest" that stops the insulation test and provides a visual warning if it detects that an appliance is connected to the system under test. This helps you avoid potentially serious and costly mistakes that can cause damage to your customers’ peripheral equipment.

Auto Test reduces test time

Auto Test performs up to seven installation tests in one sequence, ensuring compliance with local installation regulations. This reduces the number of manual connections, thus decreasing the possibility of errors and reducing test time.

Save time and enhance collaboration

Because the 1664 FC is Fluke Connect®-enabled, you can send test results to your smartphone, save them to the cloud, and share measurements in real time with team members through a ShareLive video call. It's the fastest way to let your team see what you see, and to help you get approvals without leaving the field.

Retrieve stored results from anywhere

Fluke Cloud™ storage allows you to retrieve stored results whether you are in the office or in the field to make decisions in real time. You get world-class data protection and you can import the data into Fluke DMS (Data Management Software) to process and generate certificates.

Other helpful features:

  • Compact, lightweight (less than 1.3 kg) with padded neck-strap to free your hands
  • Rotary dial knob clearly indicates which function is selected, all in one spot with no complex multi-level menus.
  • Offers additional high current loop mode for faster measurements than loop tests with non-trip mode for RCDs
  • Includes Z-max memory for loop tests to support easy evaluation of the highest loop test value
  • Provides unique zero adapter for fast, reliable and accurate test lead and mains cord compensation
  • Performs fast voltage measurement between L-N, L-PE, and N-PE using the mains cord. No need to change measurement connections
  • Measures RCD trip current and trip time in parallel (RCD type AC and A)
  • Measures PEFC or PSC and loop impedance in parallel and displays them together on the dual display
  • Offers ring testing so you can select the required input sockets with soft keys and not have to exchange test leads
  • Uses continuity test currents to measure motor windings
  • Detects raised earth voltages > 50 V with Earth Volt Touchpad, indicating potential dangerous situations
  • Features large display with backlight, clear symbols, and exceptionally wide viewing angle for easy and safe readings
  • Offers extended three-layer memory

Specifications: Fluke 1664 FC Installation Multifunction Testers

Specifications: Fluke 1663 and 1664 FC Installation Multifunction Testers

AC voltage measurement
Range500 V
Resolution0.1 V
Accuracy 45 Hz – 66 Hz0.8% + 3
Input impedance360 kΩ
Overload protection660 V rms
Continuity testing (RLO)
Range (autoranging)20 Ω / 200 Ω / 2000 Ω
Resolution0.01 Ω / 0.1 Ω / 1 Ω
Open Circuit Voltage>4 V
Insulation resistance measurement (RISO)
Test voltages50-100-250-500-1000 V
Accuracy of test voltage (at rated test current)+10%, -0%
Test voltage50 V
100 V
250 V
500 V
1000 V
Insulation resistance range20 MΩ / 50 MΩ
20 MΩ / 100 MΩ
20 MΩ / 200 MΩ
20 MΩ / 200 MΩ / 500 MΩ
20 MΩ / 200 MΩ / 1000 MΩ
Resolution0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ / 1 MΩ
0.01 MΩ / 0.1 MΩ / 1 MΩ
Test current1 mA @ 50 kΩ
1 mA @ 100 kΩ
1 mA @ 250 kΩ
1 mA @ 500 kΩ
1 mA @ 1 MΩ
Loop and line impedance (ZI)
Range10 Ω (Hi current mΩ mode)/20 Ω/200 Ω/2000 Ω
Resolution0.001 Ω/ 0.01 Ω/ 0.1 Ω/1 Ω
Prospective earth fault current, PSC test 
Range1000 A / 10 kA (50 kA)
Resolution1 A / 0.1 kA
ComputationProspective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.
RCD testing, RCD types tested
RCD TypeAC¹
G²,S³
Model 1663A4, AC¹, G²,S³
Model 1664 FCA, AC, B5, S
Notes¹Responds to AC
²General, no delay
³Time delay
⁴Responds to pulsed signal
⁵Responds to smooth DC signal
Tripping speed test (ΔT)
Current settings¹10-30-100-300-500-1000 mA – VAR
10-30-100 mA
Multiplierx ½, x 1
x 5
VAR Mode Type B - 6, 60, 200 mA
Measurement rangeRCD Type G310 ms
50 ms
RCD Type S510 ms
160 ms
EV / RDC-DD6 mA - 10s
60 mA - 0.3s
200 mA - 0.1s
Notes¹1000 mA type AC only
700 mA maximum type A in VAR mode
The VAR Mode at RCD type B (smooth DC currents) generates the test currents acc. to IEC 62955 for RCD type A-EV or RDC-DD (6/60/200 mA and ramp <2 to 6 mA).
RCD/FI-Tripping Current Measurement/Ramp Test (IΔN)
Current range30% to 110% of RCD rated current¹
<2 mA to 6 mA smooth DC³
Step size10% of IΔN²
Linear rising within 30 s
Dwell timeRCD Type G300 ms/step
RCD Type S500 ms/step
Measurement accuracy±5%
Specified trip current ranges (EN 61008-1)50% to 100% for Type AC
35% to 140% for Type A (>10 mA)
35% to 200% for Type A (≤10 mA)
50% to 200% for Type B
Notes¹30% to 150% for Type A IΔN > 10 mA
30% to 210% for Type A IΔN = 10 mA
20% to 210% for Type B
²5% for Type B
³For RCD type A-EV/RDC-DD acc. to IEC 62955 
Earth Resistance Test (RE)
Range200 Ω / 2000 Ω
Resolution0.1 Ω / 1Ω
Frequency128 Hz
Output Voltage25 V
Phase Sequence Indication
Icon  icon phase sequence indicator    Phase Sequence indicator is active.
General Specifications
Size (L x W x H)10 x 25 x 12.5 cm
Weight (incl. batteries)1.3 Kg
Battery size, quantityType AA, 6 ea.
SealingIP-40
SafetyComplies with EN/IEC 61010-1 and EN/IEC 61010-2-034
OvervoltageCAT III / 500V; CAT IV 300V
PerformanceEN61557-1 to EN61557-7 and EN61557-10

Models: Fluke 1664 FC Installation Multifunction Testers

FLK-1664FC
Fluke 1664 FC Installation Multifunction Tester
Find a distributor

Includes:

  • 6x AA (IEC LR6) cell batteries
  • C1600 hard carrying case
  • Zero adapter
  • Heavy duty mains cord
  • STD standard test lead set
  • Padded carrying and waist strap
  • Quick reference guide
  • TP165X remote control probe and lead
FLK-1664 FC/FVF AU
Find a distributor
  • bvseo_sdk, p_sdk, 3.2.1
  • CLOUD, getContent, 22.1ms
  • QUESTIONS, PRODUCT
  • bvseo-msg: HTTP status code of 404 was returned;
  • bvseo_sdk, p_sdk, 3.2.1
  • CLOUD, getReviews, 23.81ms
  • REVIEWS, PRODUCT
  • bvseo-msg: HTTP status code of 404 was returned;
Please enable cookies to view product reviews.