Fluke 1587 FC Insulation Multimeter
Fluke 1587 FC Insulation Multimeter is rated out of 5 by 31.
Key features
- Safety first. Connect the insulation tester then keep yourself out of harm's way by monitoring your test measurements remotely.
- Prove your job is done right by quickly seeing and sharing insulation resistance test results wirelessly with your smartphone.
- Quickly find problems by saving and comparing measurements over time on a wireless device.
Product overview: Fluke 1587 FC Insulation Multimeter
Keep yourself safe. Find hidden problems faster. Put the paperwork down.
Fluke Connect + Fluke's 1587 FC Insulation Multimeter helps you identify tough problems, fix, and wirelessly communicate your work quickly and easily - all at a safe distance.
Add diagnostics with Fluke Connect
The Fluke 1587 FC is Fluke Connect-enabled so you can download the free Fluke Connect® Measurements app to your smartphone and gain additional functions, including:
- Safety first. Keep yourself out of harm’s way by monitoring your test measurements remotely.
- Prove your job is done right by quickly seeing and sharing measurement results wirelessly with your smartphone.
- Quickly find problems by saving and comparing measurements over time on a wireless device.
- PI/DAR timed ratio tests with TrendIt™ graphs to identify moisture and contaminated insulation problems faster
- Memory storage through Fluke Connect that saves measurements to your phone or the cloud and eliminates the need to write down results. Reduces errors and saves data for historical tracking over time
- Temperature compensation to establish accurate baselines and relevant historical comparisons
- Historical tracking and trending of assets to identify insulation degradation over time and allow real-time decisions to be made in the field with Fluke Connect® Assets (sold separately)
- Provides memory storage through Fluke Connect Measurements to eliminate the need to write down results
- Includes live circuit detection to prevent insulation test if voltage >30 V is detected
- Supports historical tracking and asset trending of assets to identify degradation over time with Fluke Connect® Assets (sold separately)
- Incorporates VFD low-pass filter for accurate variable frequency motor drive measurements
- Includes auto-discharge of capacitive voltage for added user protection
- Measures ac/dc voltage, dc millivolts, ac/dc milliamps, resistance, and continuity
- Includes capacitance, diode test, temperature, min/max, frequency measurements and insulation test smoothing reading
- Automatically powers off to save battery power
- Comes with remote probe, test leads, alligator clips, K-type thermocouple, hard case, and three-year warranty.
Useful resources and rugged tools for Solar professionals
What's in the box:
- Fluke 1587 FC Insulation Multimeter
- Remote probe
- Test leads
- Alligator clips
- K-type thermocouple
- Soft case
- User documentation
Specifications: Fluke 1587 FC Insulation Multimeter
Electrical Specifications | ||
AC voltage measurement | ||
Range | ||
600.0 mV | Resolution | 0.1 mV |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts) | ±(2% + 3) | |
6.000 V | Resolution | 0.001 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts) | ±(2% + 3) | |
60.00 V | Resolution | 0.01 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts) | ±(2% + 3) | |
600.0 V | Resolution | 0.1 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts) | ±(2% + 3)¹ | |
1000 V | Resolution | 1 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(2% + 3) | |
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts) | ±(2% + 3)¹ | |
¹ 1 kHz bandwidth | ||
Low-Pass Filter Voltage | ||
Range | ||
600.0 mV | Resolution | 0.1 mV |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts) | +(2% + 3), -(6% - 3) | |
6.000 V | Resolution | 0.001 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts) | +(2% + 3), -(6% - 3) | |
60.00 V | Resolution | 0.01 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts) | +(2% + 3), -(6% - 3) | |
600.0 V | Resolution | 0.1 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts) | +(2% + 3), -(6% - 3) | |
1000 V | Resolution | 1 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(2% + 3) | |
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts) | +(2% + 3), -(6% - 3) | |
DC Voltage Measurement | ||
Range | Resolution | Accuracy ±(% of Rdg + Counts) |
6.000 V dc | 0.001 V | ±(0.09% + 2) |
60.00 V dc | 0.01 V | ±(0.09% + 2) |
600.0 V dc | 0.1 V | ±(0.09% + 2) |
1000 V dc | 1 V | ±(0.09% + 2) |
Input impedance | 10 MΩ (nominal), <100 pF | |
Normal mode rejection ratio | >60 dB @ 50 Hz or 60 Hz | |
Common mode rejection ratio | >120 dB @ dc, 50 Hz or 60 Hz (1 k unbalance) | |
Accuracies apply to ± 100% of range | ||
DC Millivolts Measurement | ||
Range | Resolution | Accuracy ±(% of Rdg + Counts) |
600.0 mVdc | 0.1 mV | ±(0.1% + 1) |
DC and AC Current Measurement | ||
AC 45 Hz to 1000 Hz | ||
Range | 400 mA | |
Resolution | 0.1 mA | |
Accuracy ±(% of Rdg+Counts) | ±(1.5% + 2)¹ | |
Burden voltage (Typical) | 2 mV/mA | |
Range | 60 mA | |
Resolution | 0.01 mA | |
Accuracy ±(% of Rdg+Counts) | ±(1.5% + 2)¹ | |
Burden voltage (Typical) | 2 mV/mA | |
DC | ||
Range | 400 mA | |
Resolution | 0.1 mA | |
Accuracy ±(% of Rdg+Counts) | ±(0.2% + 2) | |
Burden voltage (Typical) | 2 mV/mA | |
Range | 60 mA | |
Resolution | 0.01 mA | |
Accuracy ±(% of Rdg+Counts) | ±(0.2% + 2) | |
Burden voltage (Typical) | 2 mV/mA | |
Overload | 600 mA for 2 minutes maximum | |
Fuse protection for mA input | 0.44 mA, 1000 V, IR 10 kA | |
AC conversion | Inputs are ac-coupled and calibrated to the rms value of sine wave input | |
Conversions are true-rms responding and specified from 5% to 100% of range. Input signal crest factor can be up to 3 up to 300 mA, decreasing linearly to crest factor ≤1.5 at 600 mA. For non-sinusoidal waveforms add +(2% reading + 2% FS) typical, for a crest factor up to 3. | ||
¹ 1 kHz bandwidth | ||
Ohms Measurement | ||
Range | Resolution | Accuracy +(% of Rdg+Counts)¹ |
600.0 Ω | 0.1 Ω | ±(0.9% + 2) |
6.000 kΩ | 0.001 kΩ | ±(0.9% + 2) |
60.00 kΩ | 0.01 kΩ | ±(0.9% + 2) |
600.0 kΩ | 0.1 KΩ | ±(0.9% + 2) |
6.000 MΩ | 0.001 MΩ | ±(0.9% + 2) |
50.0 MΩ ² | 0.01 MΩ | ±(1.5% + 3) |
Overload protection | 1000 V rms or dc | |
Open circuit test voltage | <8.0 V dc | |
Short circuit current | <1.1 mA | |
¹ Accuracies apply from 0% to 100% of range ² Up to 80% relative humidity | ||
Diode Test | ||
Diode test indication | Display voltage drop: 0.6 V at1.0 mA nominal test current: | |
Accuracy | ±(2% + 3) | |
Continuity Test | ||
Continuity indication | Continuous audible tone for testresistance below 25 Ω and off above 100 Ω. Maximum Reading; 1000 Ω | |
Open circuit voltage | <8.0 V | |
Short circuit current | 1.0 mA typical | |
Overload protection | 1000 V rms | |
Response time | >1 m sec | |
Frequency Measurement | ||
Range | Resolution | Accuracy ±(% of Rdg+Counts) |
99.99 Hz | 0.01 Hz | ±(0.1% + 1) |
999.9 Hz | 0.1 Hz | ±(0.1% + 1) |
9.999 kHz | 0.001 kHz | ±(0.1% + 1) |
99.99 kHz | 0.01 kHz | ±(0.1% + 1) |
Frequency Counter Sensitivity | ||
600.0 mV ac | V ac Sensitivity (RMS Sine Wave)¹ 5 Hz to 20 kHz | 100.0 mV |
V ac Sensitivity (RMS Sine Wave)¹ 20 kHz to 100 kHz | 150.0 mV | |
DC Trigger Levels¹ to 20 kHz² | NA | |
6.0 V | V ac Sensitivity (RMS Sine Wave)¹ 5 Hz to 20 kHz | 1.0 V |
V ac Sensitivity (RMS Sine Wave)¹ 20 kHz to 100 kHz | 1.5 V | |
DC Trigger Levels¹ to 20 kHz² | -400.0 mV and 2.5 V | |
60.0 V | V ac Sensitivity (RMS Sine Wave)¹ 5 Hz to 20 kHz | 10.0 V |
V ac Sensitivity (RMS Sine Wave)¹ 20 kHz to 100 kHz | 36.0 V | |
DC Trigger Levels¹ to 20 kHz² | 1.2 V and 4.0 V | |
600.0 V | V ac Sensitivity (RMS Sine Wave)¹ 5 Hz to 20 kHz | 100.0 V |
V ac Sensitivity (RMS Sine Wave)¹ 20 kHz to 100 kHz | - | |
DC Trigger Levels¹ to 20 kHz² | 12.0 V and 40.0 V | |
1000.0 V | V ac Sensitivity (RMS Sine Wave)¹ 5 Hz to 20 kHz | 300.0 V |
V ac Sensitivity (RMS Sine Wave)¹ 20 kHz to 100 kHz | - | |
DC Trigger Levels¹ to 20 kHz² | 12.0 V and 40.0 V | |
¹ Maximum input for specified accuracy = 10x range (1000 V max). Noise at low frequencies and amplitudes may affect accuracy ² Usable to 100 kHz with full scale input | ||
Capacitance | ||
Range | Resolution | Accuracy ±(% of Rdg+Counts) |
1000 nF | 1 nF | ±(1.2% + 2) |
10.00 μF | 0.01 μF | ±(1.2% + 2) |
100.0 μF | 0.1 μF | ±(1.2% ±90 counts) |
9999 μF | 1 μF | ±(1.2% ±90 counts) |
Temperature Measurement | ||
Range | Resolution | Accuracy ±(% of Rdg+Counts)¹ |
-40 ° C to 537 ° C | 0.1 °C | ±(1% + 10 counts) |
-40 ° F to 998 ° F | 0.1 °F | ±(1% + 18 counts) |
¹ Accuracies apply following 90 minutes settling time after a change in the ambient temperature of the instrument | ||
Insulation Specifications | ||
Measurement range | 0.01 MΩ to 2 GΩ | |
Test voltages | 50, 100, 250, 500, 1000 V | |
Test voltage accuracy | +20%, -0% | |
Short-circuit test current | 1 mA nominal | |
Auto discharge | Discharge time <0.5 second for C = 1 μF or less | |
Live circuit detection | Inhibit test if terminal voltage > 30 V prior to initialization of test | |
Maximum capacitive load | Operable with up to 1 μF load | |
Output Voltage | ||
50 V (0% to +20%) | Display range | 0.01 to 6.00 MΩ |
Resolution | 0.01 MΩ | |
Test current | 1 mA @ 50 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(3% + 5 counts) | |
Display range | 6.0 to 50.0 MΩ | |
Resolution | 0.1 MΩ | |
Test current | 1 mA @ 50 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(3% + 5 counts) | |
100 V (0% to +20%) | Display range | 0.01 to 6.00 MΩ |
Resolution | 0.01 MΩ | |
Test current | 1 mA @ 100 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(3% + 5 counts) | |
Display range | 6.0 to 60.0 MΩ | |
Resolution | 0.1 MΩ | |
Test current | 1 mA @ 100 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(3% + 5 counts) | |
Display range | 60 to 100 MΩ | |
Resolution | 1 MΩ | |
Test current | 1 mA @ 100 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(3% + 5 counts) | |
250 V (0% to +20%) | Display range | 0.1 to 60.0 MΩ |
Resolution | 0.1 MΩ | |
Test current | 1 mA @ 250 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(1.5% + 5 counts) | |
Display range | 60 to 250 MΩ | |
Resolution | 1 MΩ | |
Test current | 1 mA @ 250 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(1.5% + 5 counts) | |
500 V (0% to +20%) | Display range | 0.1 to 60.0 MΩ |
Resolution | 0.1 MΩ | |
Test current | 1 mA @ 500 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(1.5% + 5 counts) | |
Display range | 60 to 500 MΩ | |
Resolution | 1 MΩ | |
Test current | 1 mA @ 500 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(1.5% + 5 counts) | |
1000 V (0% to +20%) | Display range | 0.1 to 60.0 MΩ |
Resolution | 0.1 MΩ | |
Test current | 1 mA @ 1 MΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(1.5% + 5 counts) | |
Display range | 60 to 600 MΩ | |
Resolution | 1 MΩ | |
Test current | 1 mA @ 1 MΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(1.5% + 5 counts) | |
Display range | 0.6 to 2.0 GΩ | |
Resolution | 100 MΩ | |
Test current | 1 mA @ 1 MΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(10% + 3 counts) | |
General Specifications | ||
Maximum voltage applied to any terminal and common | 1000 V | |
Storage temperature | -40 °C to 60 °C (-40 °F to 140 °F) | |
Operating temperature | -20 °C to 55 °C (-4 °F to 131 °F) | |
Temperature coefficient | 0.05 x (specified accuracy) per °C for temperatures <18 °C or >28 °C (<64 °F or >82 °F) | |
Relative humidity | Noncondensing | |
0% to 95% @ 10 °C to 30 °C (50 °F to 86 °F) | ||
0% to 75% @ 30 °C to 40 °C (86 °F to 104 °F) | ||
0% to 40% @ 40 °C to 55 °C (104 °F to 131 °F) | ||
Vibration | Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument | |
Radio frequency communication | 2.4 GHz ISM Band | |
Radio frequency certification | FCC: T68-FBLE, IC: 6627A-FBLE | |
Electromagnetic Compatibility | ||
International | IEC 61326-1:Portable Electromagnetic Environment; IEC 61326-2-2 CISPR 11: Group 1, Class A | |
Group 1: Equipment has intentionally generated and/or uses conductively-coupled radio frequency energy that is necessary for the internal function of the equipment itself. | ||
Class A: Equipment is suitable for use in all establishments other than domestic and those directly connected to a low-voltage power supply network that supplies buildings used for domestic purposes. There may be potential difficulties in ensuring electromagnetic compatibility in other environments due to conducted and radiated disturbances. | ||
Emissions that exceed the levels required by CISPR 11 can occur when the equipment is connected to a test object. The equipment may not meet the immunity requirements of this standard when test leads and/or test probes are connected. | ||
Korea (KCC) | Class A Equipment (Industrial Broadcasting & Communication Equipment) | |
Class A: Equipment meets requirements for industrial electromagnetic wave equipment and the seller or user should take notice of it. This equipment is intended for use in business environments and not to be used in homes. | ||
USA (FCC) | 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103. | |
Enclosure protection | IEC 60529: IP40 (non-operating) | |
Safety | ||
IEC 61010-1 | Pollution Degree 2 | |
IEC 61010-2-033 | CAT IV 600 V / CAT III 1000 V | |
Batteries | Four AA batteries (IEC LR6) | |
Battery life | Meter use 1000 hours; Insulation test use: Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off. | |
Size (H x W x L) | 5.0 x 10.0 x 20.3 cm (1.97 x 3.94 x 8.00 in) | |
Weight | 550 g (1.2 lb) | |
Altitude | Operating | 2000 m |
Storage | 12,000 m | |
Over-range capability | 110% of range except for capacitance which is 100% | |
Frequency overload protection | <107 V Hz | |
Fuse protection for mA input | 0.44A, 1000 V, IR 10 kA |
Models: Fluke 1587 FC Insulation Multimeter
FLK-1587-FC
Fluke 1587 FC Insulation Multimeter
Includes:
- Remote probe
- Test leads
- Alligator clips
- K-type thermocouple
- Soft case
- User documentation
what is the recommended time interval to recalibrate the Fluke 1587 FC?
Fluke recommends yearly calibration for those customers that are subject to audits. The certificate is dated for a one year expiration. Otherwise, an every other year cycle is recommended.
Date published: 2024-03-28
What are the recommended batteries to use
is there a separate part number for the 1587-FC with calibration certificates?
Rated 5 out of 5 by EGOLF from Fluke quality product like youd expect. Great product, works like it should, quality you would expect
Date published: 2023-05-31
Rated 5 out of 5 by ACH1 from Thank you Fluke Description was correct with included accessories!
Date published: 2022-10-24
Rated 5 out of 5 by PowerGenerationTech from Just what the mechanic ordered! Works great. Very pleased with the product. Received quickly. Just what the mechanic ordered!
Date published: 2021-08-31
Rated 5 out of 5 by Cebrown630 from Great meter Great meter...does all I need and more. The only option it doesn't have that i wish it did is temperature.
Date published: 2021-06-02
Rated 5 out of 5 by Austin from Fluke Connect made a great instrument better. I just recently upgraded to this new 1587FC, but the 1587 has always been my go to favorite insulation tester. The fluke connect feature, while not something I use extremely regularly, does work amazingly when you need it. It is very convenient to be able to see your meter readings from your phone even if you're not close to the meter itaelf.
Date published: 2020-05-30
Rated 5 out of 5 by Korey from Best Multi-Meter/Megger Combo I have been an electrician for over four years since I left high school in 2012. I have used many instruments in the past four years as a marine electrician. This is probably one of the best all-around instruments for Megging and checking continuity that I can think of. It also has so many other features such as checking temperature diodes current and voltage.
Date published: 2016-12-17
Rated 5 out of 5 by Derk from AWESOME COMPACT METER WITH BIG CAPABILITIES! Saw a coworker breakout his 1587 Fluke to do what i have only seen done in motor shops... I was sold. I looked and found the Fluke 1587FC for a great price. Have used this on my own now several times in place of guessing with my other more basic fluke meter, Takes the guesswork out of trouble shooting and adding a great deal of customer confidence! This meter has been a huge time saver making a better bottom line. no longer performing further repairs on motors only to find deeper problems! (Quicker repairs) I would definitely purchase this meter again! Highly recommended. Derk G. Utah
Date published: 2016-12-17
Rated 5 out of 5 by GTB02 from Two meters in one As a defense contractor working on Navy ships I use the 1587 FC Insulation Multimeter daily. We are required to perform insulation resistance checks using 500 volts as well as continuity checks. This meter can accomplish both. No need to carry two meters around. The remote probe and ability to record data on my phone is a real time saver and ensures accuracy. The display has large digits that are easy to read in dark locations. The meter can be used with the FLUKE SV225 Stray Voltage Eliminator to prevent false reading from ghost voltage. Very versatile meter.
Date published: 2016-12-12