Fluke 1664 FC Installation Multifunction Tester

Model#: FLK-1664FC
  • Fluke 1664 FC Multifunction Installation Tester
  • Fluke 1664 FC Multifunction Installation Tester
  • Fluke 1664 FC Multifunction Installation Tester
  • Fluke 1664 FC Multifunction Installation Tester

์ฃผ์š” ๊ธฐ๋Šฅ

Multifunction tester that tests to all local regulations

  • Includes "Insulation Pre-test" that detects when appliances are connected to the system and stops the test
  • Runs seven installation tests automatically in one sequence with a single connection through Auto Test
  • Allows you to share test results in real time over your smartphone via Fluke Connect Measurements
  • 6 mA RDC-DD testing for EV charging stations

์ œํ’ˆ ๊ฐœ์š”: Fluke 1664 FC Installation Multifunction Tester

The Fluke 1664 FCย Multifunction Installation Tester helps expedite installations

The 1664 FCย puts a lot of testing power in your hands to quickly and efficiently test to all local regulations, protect appliances, and share test results in real time over your smartphone.

Test EV charging station RCD type A-EV or RDC-DD DC protection devices

Perform tests on EV charging station DC protection devices using the RCD type B (smooth DC currents) VAR mode, which generates the test currents for RCD type A-EV or RDC-DD acc. to IEC 62955 (6/60/200 mA and ramp <2 to 6 mA ramp). This allows the quick an easy testing of additional 6 mA DC monitors on charging points and can be used in conjunction with the Fluke FEV100 or FEV300.

Protect appliances from accidental damage

The Fluke 1664 FC is the only tester with ""Insulation PreTest"" that stops the insulation test and provides a visual warning if it detects that an appliance is connected to the system under test. This helps you avoid potentially serious and costly mistakes that can cause damage to your customersโ€™ peripheral equipment.

Auto Test reduces test time

Auto Test performs up to seven installation tests in one sequence, ensuring compliance with local installation regulations. This reduces the number of manual connections, thus decreasing the possibility of errors and reducing test time.

Save time and enhance collaboration

Because the 1664 FCย is Fluke Connectยฎ-enabled, you can send test results to your smartphone, save them to the cloud, and share measurements in real time with team members through a ShareLive video call. It's the fastest way to let your team see what you see, and to help you get approvals without leaving the field. Fluke Cloudโ„ข storage allows you to retrieve stored results whether you are in the office or in the field to make decisions in real time. You get world-class data protection and can import the data, manage files transferred from instruments, or manually enter data as needed into TruTestโ„ข Software to process and generate certificates quickly and easily. Designed to eliminate the hassle associated with traditional electrical system data management and reporting, TruTestโ„ข Software is an ideal solution for producing easy-to-understand reports for clients.

Other helpful features:

  • Compact, lightweight (less than 1.3 kg) with padded neck-strap to free your hands
  • Rotary dial knob clearly indicates which function is selected, all in one spot with no complex multi-level menus.
  • Offers additional high current loop mode for faster measurements than loop tests with non-trip mode for RCDs
  • Includes Z-max memory for loop tests to support easy evaluation of the highest loop test value
  • Provides unique zero adapter for fast, reliable and accurate test lead and mains cord compensation
  • Performs fast voltage measurement between L-N, L-PE, and N-PE using the mains cord. No need to change measurement connections
  • Measures RCD trip current and trip time in parallel (RCD type AC and A)
  • Measures PEFC or PSC and loop impedance in parallel and displays them together on the dual display
  • Offers ring testing so you can select the required input sockets with soft keys and not have to exchange test leads
  • Uses continuity test currents to measure motor windings
  • Detects raised earth voltages > 50 V with Earth Volt Touchpad, indicating potential dangerous situations
  • Features large display with backlight, clear symbols, and exceptionally wide viewing angle for easy and safe readings
  • Offers extended three-layer memory

์ œํ’ˆ ์‚ฌ์–‘: Fluke 1664 FC Installation Multifunction Tester

Specifications: Fluke 1663ย and 1664 FCย Installation Multifunction Testers

AC voltage measurement
Range500 V
Resolution0.1 V
Accuracy 45 Hz โ€“ 66 Hz0.8% + 3
Input impedance360 kฮฉ
Overload protection660 V rms
Continuity testing (RLO)
Range (autoranging)20 ฮฉ / 200 ฮฉ / 2000 ฮฉ
Resolution0.01 ฮฉ / 0.1 ฮฉ / 1 ฮฉ
Open Circuit Voltage>4 V
Insulation resistance measurement (RISO)
Test voltages50-100-250-500-1000 V
Accuracy of test voltage (at rated test current)+10%, -0%
Test voltage50 V
100 V
250 V
500 V
1000 V
Insulation resistance range20 Mฮฉ / 50 Mฮฉ
20 Mฮฉ / 100 Mฮฉ
20 Mฮฉ / 200 Mฮฉ
20 Mฮฉ / 200 Mฮฉ / 500 Mฮฉ
20 Mฮฉ / 200 Mฮฉ / 1000 Mฮฉ
Resolution0.01 Mฮฉ / 0.1 Mฮฉ
0.01 Mฮฉ / 0.1 Mฮฉ
0.01 Mฮฉ / 0.1 Mฮฉ
0.01 Mฮฉ / 0.1 Mฮฉ / 1 Mฮฉ
0.01 Mฮฉ / 0.1 Mฮฉ / 1 Mฮฉ
Test current1 mA @ 50 kฮฉ
1 mA @ 100 kฮฉ
1 mA @ 250 kฮฉ
1 mA @ 500 kฮฉ
1 mA @ 1 Mฮฉ
Loop and line impedance (ZI)
Range10 ฮฉ (Hi current mฮฉ mode)/20 ฮฉ/200 ฮฉ/2000 ฮฉ
Resolution0.001 ฮฉ/ 0.01 ฮฉ/ 0.1 ฮฉ/1 ฮฉ
Prospective earth fault current, PSC testย 
Range1000 A / 10 kA (50 kA)
Resolution1 A / 0.1 kA
ComputationProspective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.
RCD testing, RCD types tested
RCD TypeACยน
Gยฒ,Sยณ
Model 1663A4, ACยน, Gยฒ,Sยณ
Model 1664 FCA, AC, B5, S
NotesยนResponds to AC
ยฒGeneral, no delay
ยณTime delay
โดResponds to pulsed signal
โตResponds to smooth DC signal
Tripping speed test (ฮ”T)
Current settingsยน10-30-100-300-500-1000 mA โ€“ VAR
10-30-100 mA
Multiplierx ยฝ, x 1
x 5
VAR Mode Type B - 6, 60, 200 mA
Measurement rangeRCD Type G310 ms
50 ms
RCD Type S510 ms
160 ms
EV / RDC-DD6 mA - 10s
60 mA - 0.3s
200 mA - 0.1s
Notesยน1000 mA type AC only
700 mA maximum type A in VAR mode
The VAR Mode at RCD type B (smooth DC currents) generates the test currents acc. to IEC 62955 for RCD type A-EV or RDC-DD (6/60/200 mA and ramp <2 to 6 mA).
RCD/FI-Tripping Current Measurement/Ramp Test (Iฮ”N)
Current range30% to 110% of RCD rated currentยน
<2 mA to 6 mA smooth DCยณ
Step size10% of Iฮ”Nยฒ
Linear rising within 30 s
Dwell timeRCD Type G300 ms/step
RCD Type S500 ms/step
Measurement accuracyยฑ5%
Specified trip current ranges (EN 61008-1)50% to 100% for Type AC
35% to 140% for Type A (>10 mA)
35% to 200% for Type A (โ‰ค10 mA)
50% to 200% for Type B
Notesยน30% to 150% for Type A Iฮ”N > 10 mA
30% to 210% for Type A Iฮ”N = 10 mA
20% to 210% for Type B
ยฒ5% for Type B
ยณFor RCD type A-EV/RDC-DD acc. to IEC 62955ย 
Earth Resistance Test (RE)
Range200 ฮฉ / 2000 ฮฉ
Resolution0.1 ฮฉ / 1ฮฉ
Frequency128 Hz
Output Voltage25 V
Phase Sequence Indication
Iconicon phase sequence indicator

ย  ย Phase Sequence indicator is active.

General Specifications
Size (L x W x H)10 x 25 x 12.5 cm
Weight (incl. batteries)1.3 Kg
Battery size, quantityType AA, 6 ea.
SealingIP-40
SafetyComplies with EN/IEC 61010-1 and EN/IEC 61010-2-034
OvervoltageCAT III / 500V; CAT IV 300V
PerformanceEN61557-1 to EN61557-7 and EN61557-10

๋ชจ๋ธ: Fluke 1664 FC Installation Multifunction Tester

FLK-1664FC

Fluke 1664 FC ๋‹ค๊ธฐ๋Šฅ ์„ค์น˜ ํ…Œ์Šคํ„ฐ


๊ตฌ๋งคํ•˜๊ธฐ

ํฌํ•จ ์‚ฌํ•ญ:

  • 6x AA(IEC LR6) ์…€ ๋ฐฐํ„ฐ๋ฆฌ
  • C1600 ํœด๋Œ€์šฉ ํ•˜๋“œ ์ผ€์ด์Šค
  • ์ œ๋กœ ์–ด๋Œ‘ํ„ฐ
  • ๋‚ด๊ตฌ์„ฑ ๊ฐ•ํ•œ ์ „์› ์ฝ”๋“œ
  • STD ํ‘œ์ค€ ํ…Œ์ŠคํŠธ ๋ฆฌ๋“œ ์„ธํŠธ
  • C1600 ํœด๋Œ€์šฉ ํ•˜๋“œ ์ผ€์ด์Šค
  • ์•ˆ๊ฐ์„ ๋ง๋Œ„ ํœด๋Œ€ ๋ฐ ์›จ์ด์ŠคํŠธ ์ŠคํŠธ๋žฉ
  • ๋น ๋ฅธ ์ฐธ์กฐ ์•ˆ๋‚ด์„œ
  • TP165X ์›๊ฒฉ ์ œ์–ด ํ”„๋กœ๋ธŒ ๋ฐ ๋ฆฌ๋“œ
์ฑ„ํŒ…Fluke ๋„์šฐ๋ฏธ
์ฑ„ํŒ… ์ง€์šฐ๊ธฐ