Key features

  • Safely test the PE conductor for possible presence of dangerous voltage against earth
  • Simulate various current capabilities of charging cables
  • Simulate vehicle charging states 
  • Simulate PE error (earth fault)
  • Includes Fluke 1664 FC to perform installation tests and Type 2 connector

Product overview: Fluke FEV300 EV Charging Station Test Adapter Kit: 1664 FC Installation Tester and Type 2 Connector

The FEV300 with 1664 FC Multifunction Installation Tester is a complete kit designed to test the function and safety of charging stations mode 3 for AC charging. This test adapter simulates the presence of an electrical vehicle, allowing you to conduct tests in combination with the Fluke 1664 FC installation tester to quickly and efficiently test to all local regulations without opening the charging station. Use the FEV300 to verify a charging station is working properly after install, during periodic maintenance or troubleshoot a charging station if it is not delivering the appropriate charge. With the adapter kit, charging stations can be tested in accordance with IEC/EN 61851-1 and IEC/HD 60364-7-722.

Run seven installation tests in one sequence

The FEV300 PE grounding protection pre-test verifies that there is no presence of dangerous voltage at the ground terminal. Connect the 1664 FC to the FEV300 to run seven installation tests automatically in one sequence through a single connection. The 1664 FC tests to all local regulations and allows you to share test results in real time over your smartphone via Fluke Connect Measurements.

Safety, simplicity and convenience

Perform a variety of tests including ground fault checks, insulation of wires, measuring voltage and duty cycle to see max current available for charging all in one adapter that safely integrates with the Fluke portfolio of test and measurement tools. There is no need to bring an electric vehicle onsite for charging station troubleshooting: the FEV300 adapter acts as an electric vehicle when connected to a charging station for easy performance and maintenance testing.

  • PE Pre-Test: Safely pre-test the PE conductor for possible presence of dangerous voltage against earth
  • Proximity Pilot (PP) state “Cable Simulation”: The PP State rotary switch enables the adapter to simulate various current capabilities of charging cables
  • Control Pilot (CP) state “Vehicle Simulation”: Use the CP State rotary switch selector to simulate various charging states
  • Simulation of CP error “E”: Simulate PE error (Earth fault)

Test EV charging station RCD type A-EV or RDC-DD DC protection devices

Perform tests with the 1664 FC on EV charging station DC protection devices using the RCD type B (smooth DC currents) VAR mode, which generates the test currents for RCD type A-EV or RDC-DD acc. to IEC 62955 (6/60/200 mA and ramp <2 to 6 mA ramp). This allows the quick an easy testing of additional 6 mA DC monitors on charging points.

Save time and enhance collaboration

Because the 1664 FC is Fluke Connect®-enabled, you can send test results to your smartphone, save them to the cloud, and share measurements in real time with team members through a ShareLive video call. It's the fastest way to let your team see what you see, and to help you get approvals without leaving the field. Fluke Cloud™ storage allows you to retrieve stored results whether you are in the office or in the field to make decisions in real time. You get world-class data protection and can import the data, manage files transferred from instruments, or manually enter data as needed into TruTest™ Software to process and generate certificates quickly and easily. Designed to eliminate the hassle associated with traditional electrical system data management and reporting, TruTest™ Software is an ideal solution for producing easy-to-understand reports for clients.

Compatible products:

What's in the box:

  • FEV300/BASIC Test Adapter
  • 1664 FC Installation Multifunction Tester
  • FEV300-CON-TY2 Type 2 Plug
  • Carrying case

Specifications: Fluke FEV300 EV Charging Station Test Adapter Kit: 1664 FC Installation Tester and Type 2 Connector

Specifications: Fluke FEV300 EV Charging Station Test Adapter Kit with 1664 FC Installation Tester and Type 2 Connector

General features
Input voltageUp to 250 V (single phase system) / up to 480 V (three phase system), 50/60 Hz, max 10 A
Internal power consumption3 W max.
FEV300-CON-TY2 PlugAC charging mode 3, suitable to IEC 62196-2 type 2 socket outlet or fixed cable with vehicle connector (type 2, 7P three-phase)
FEV300-CON-TY1 PlugAC charging mode 3, suitable to IEC 62196-2 type 1 or SAE J1772 with vehicle connector (type 1, 5P single-phase)
Dimensions (H × W × D)110  × 45  × 220 mm length without connection cable and test cable
Weight (including type 1 or type 2 connection cable)Approx. 1 kg
Safety standardsIEC/EN 61010-1, pollution degree 2
IEC/EN 61010-2-030, CAT II 300 V, protection class II
Ingress protectionIEC 60529: IP54 (housing)
IEC 60529: IP54 (sockets with protection caps in place, connectors in connected condition or with protection caps in place, otherwise IP20)
Operating temperature-20 °C to 40 °C
Storage temperature-20 °C to 50 °C
Operating humidity range10 % to 85 % relative humidity non-condensing
Storage relative humidity0 % to 85 % non-condensing
Operating altitude2000 m max.
Functions
PE Pre-TestVisible indication >50 V AC/DC between PE conductor and touch sensor
PP SimulationOpen, 13 A, 20 A, 32 A, 63 A
CP StatesState A, B, C, D
CP Error state “E”On/off (CP signal short-circuited to PE)
PE Error state "F" (Earth fault)On/off (interruption of PE conductor)
Outputs (for test purpose only)
Measuring terminals L1, L2, L3, N, PEMax. 250/480 V, max. 10 A
CP signal output terminalsApprox. +/-12 V
Caution: In case of wrong wiring or error of the charging station these terminals may be hazardous.
 
AC voltage measurement
Range500 V
Resolution0.1 V
Accuracy 45 Hz – 66 Hz0.8% + 3
Input impedance360 kΩ
Overload protection660 V rms
Continuity testing (RLO)
Range (autoranging)20 Ω / 200 Ω / 2000 Ω
Resolution0.01 Ω / 0.1 Ω / 1 Ω
Open Circuit Voltage>4 V
Insulation resistance measurement (RISO)
Test voltages50-100-250-500-1000 V
Accuracy of test voltage (at rated test current)+10%, -0%
Test voltage50 V
100 V
250 V
500 V
1000 V
Insulation resistance range20 MΩ / 50 MΩ
20 MΩ / 100 MΩ
20 MΩ / 200 MΩ
20 MΩ / 200 MΩ / 500 MΩ
20 MΩ / 200 MΩ / 1000 MΩ
Resolution0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ / 1 MΩ
0.01 MΩ / 0.1 MΩ / 1 MΩ
Test current1 mA @ 50 kΩ
1 mA @ 100 kΩ
1 mA @ 250 kΩ
1 mA @ 500 kΩ
1 mA @ 1 MΩ
Loop and line impedance (ZI)
Range10 Ω (Hi current mΩ mode)/20 Ω/200 Ω/2000 Ω
Resolution0.001 Ω/ 0.01 Ω/ 0.1 Ω/1 Ω
Prospective earth fault current, PSC test 
Range1000 A / 10 kA (50 kA)
Resolution1 A / 0.1 kA
ComputationProspective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.
RCD testing, RCD types tested
RCD TypeAC¹
G²,S³
Model 1663A4, AC¹, G²,S³
Model 1664 FCA, AC, B5, S
Notes¹Responds to AC
²General, no delay
³Time delay
⁴Responds to pulsed signal
⁵Responds to smooth DC signal
Tripping speed test (ΔT)
Current settings¹10-30-100-300-500-1000 mA – VAR
10-30-100 mA
Multiplierx ½, x 1
x 5
VAR Mode Type B - 6, 60, 200 mA
Measurement rangeRCD Type G310 ms
50 ms
RCD Type S510 ms
160 ms
EV / RDC-DD6 mA - 10s
60 mA - 0.3s
200 mA - 0.1s
Notes¹1000 mA type AC only
700 mA maximum type A in VAR mode
The VAR Mode at RCD type B (smooth DC currents) generates the test currents acc. to IEC 62955 for RCD type A-EV or RDC-DD (6/60/200 mA and ramp <2 to 6 mA).
RCD/FI-Tripping Current Measurement/Ramp Test (IΔN)
Current range30% to 110% of RCD rated current¹
<2 mA to 6 mA smooth DC³
Step size10% of IΔN²
Linear rising within 30 s
Dwell timeRCD Type G300 ms/step
RCD Type S500 ms/step
Measurement accuracy±5%
Specified trip current ranges (EN 61008-1)50% to 100% for Type AC
35% to 140% for Type A (>10 mA)
35% to 200% for Type A (≤10 mA)
50% to 200% for Type B
Notes¹30% to 150% for Type A IΔN > 10 mA
30% to 210% for Type A IΔN = 10 mA
20% to 210% for Type B
²5% for Type B
³For RCD type A-EV/RDC-DD acc. to IEC 62955 
Earth Resistance Test (RE)
Range200 Ω / 2000 Ω
Resolution0.1 Ω / 1Ω
Frequency128 Hz
Output Voltage25 V
Phase Sequence Indication
Icon    icon phase sequence indicator   Phase Sequence indicator is active.
General Specifications
Size (L x W x H)10 x 25 x 12.5 cm
Weight (incl. batteries)1.3 Kg
Battery size, quantityType AA, 6 ea.
SealingIP-40
SafetyComplies with EN/IEC 61010-1 and EN/IEC 61010-2-034
OvervoltageCAT III / 500V; CAT IV 300V
PerformanceEN61557-1 to EN61557-7 and EN61557-10

Models: Fluke FEV300 EV Charging Station Test Adapter Kit: 1664 FC Installation Tester and Type 2 Connector

Fluke EV Charging Station Test Adapter Kit
Fluke FEV300 EV Charging Station Test Adapter Kit: 1664 FC Installation Tester and Type 2 Connector

Buy it

Includes:

  • FEV300/BASIC Test Adapter
  • 1664 FC Installation Multifunction Tester
  • FEV300-CON-TY2 Type 2 Plug
  • Carrying case
  • bvseo_sdk, p_sdk, 3.2.1
  • CLOUD, getContent, 23.56ms
  • QUESTIONS, PRODUCT
  • bvseo-msg: HTTP status code of 404 was returned;
  • bvseo_sdk, p_sdk, 3.2.1
  • CLOUD, getReviews, 21.94ms
  • REVIEWS, PRODUCT
  • bvseo-msg: HTTP status code of 404 was returned;
Please enable cookies to view product reviews.

Manuals + resources: Fluke FEV300 EV Charging Station Test Adapter Kit: 1664 FC Installation Tester and Type 2 Connector