Fluke T6-1000 Electrical Tester and Proving Unit Kit, 1000 V AC
Model#: T6-1000/PRV240FS
Discontinued
Key features
- FieldSense technology for ac voltage, current and frequency measurement without making electrical contact to live voltage
- Prove the functionality of the tester
This product is discontinued or reclassified
Product overview: Fluke T6-1000 Electrical Tester and Proving Unit Kit, 1000 V AC
Ideal for commercial and light industrial electricians, this T6-1000 tester measures voltage up to 1000 V AC. Additionally, it comes equipped with a proving unit kit which is built to prove the functionality of the FieldSense and provides ac and dc voltages for other high impedance instruments.
Specifications: Fluke T6-1000 Electrical Tester and Proving Unit Kit, 1000 V AC
Fluke T6-1000 Electrical Tester
| Measurement Specifications | ||||
|---|---|---|---|---|
| Function | Requires test leads | Range | Resolution | Accuracy[1] |
| FieldSense ac voltage true-rms | No | 1000 V | 1 V | ± (3 % + 3 counts) 45 Hz - 66 Hz[2][3] |
| FieldSense ac current true-rms | No | 200.0 A | 0.1 A | ± (3% + 3 counts) 45 Hz - 66 Hz |
| FieldSense frequency (Hz) | No | 45 Hz – 66 Hz | 1 Hz | ± (1% + 2 counts)[3] |
| Volts ac true-rms | Yes | 1000 V | 1 V | ± (1.5% + 2 counts) 45 Hz - 66 Hz |
| Volts dc | Yes | 1000 V | 1 V | ± (1% + 2 counts) |
| Resistance | Yes | 2000 Ω | 1 Ω | ± (1% + 2 counts) |
| Yes | 20.00 kΩ | 0.01 kΩ | ||
| Yes | 100.0 kΩ | 0.1 kΩ | ||
| Safety | 1000 V CAT III 600 V CAT IV | |||
| Accuracy[1]: ± ( [ % of reading] + [number of least significant digits] ). Accuracy is specified for 1 year after calibration, at 18 °C to 28 °C (64 °F to 82 °F) with relative humidity to 90 %. AC measurements are ac-coupled, RMS responding. Accuracy[2]: Add 3 % without an external ground connection. External ground connection required for user wearing insulated gloves, standing on an insulated ladder, or otherwise insulated from earth ground. Accuracy[3]: FieldSense is specified from 16 V to 100 % of range. | ||||
| General Specifications | ||
|---|---|---|
| Calibration | 1-year calibration cycle | |
| Dimensions | 61.1 x 259.3 x 43.8 mm | |
| Jaw opening | 17.8 mm | |
| Weight | 0.35 kg (0.78 lb) | |
| Temperature | Operating | -10 °C to +50 °C (14 °F to 122 °F) |
| Storage | -30 °C to +60 °C (-22 °F to +140 °F) | |
| Altitude | Operating | 2,000 m (6,562 feet) |
| Storage | 10,000 m (32,808 feet) | |
| Relative Humidity | 0% to 90%, 5 °C to 30 °C (41 °F to 86 °F) | |
| 0% to 75%, 30°C to 40 °C (86 °F to 104 °F) | ||
| 0% to 45%, 40°C to 50 °C (104 °F to 122 °F) | ||
| Battery Type and Life | 2 x AA (IEC LR6); 360 hours continuous, typical; 200 hours using FieldSense | |
| Temperature coefficient | 0.1 x (specified accuracy) / °C for <18°C or >28 °C | |
| 0.1 x (specified accuracy) / °C for <18°C or >28 °C | ||
| Safety | IEC/EN 61010-1: Pollution Degree 2 | |
| Electromagnetic Environment | IEC/EN 61326-1: Portable | |
Models: Fluke T6-1000 Electrical Tester and Proving Unit Kit, 1000 V AC
T6-1000/PRV240FS
Fluke T6-1000 Electrical Tester and Proving Unit Kit, 1000 V AC
Includes:
- T6-1000/APAC
- PRV240FS