Fluke i2000 Flex AC Current Clamp

  • Fluke I2000 Flex AC Current Clamp | Fluke

Key features

  • Three ranges: 20A, 200 A & 2000 A, 100 mV/A, 10 mV/A & 1 mV/A output
  • Ideal for current measurement on thick and hard to reach conductors without breaking the circuit
  • Maximum conductor diameter 178 mm
  • CAT III 600 V safety rating
Buy now

Product overview

The i2000 is an AC current probe utilizing the Rogowski principle. It can be used to measure currents up to 2000 A when used in conjunction with multimeters, recorders or data loggers. The flexible and lightweight measuring head allows quick and easy installation in hard to reach areas.

Models

Fluke i2000 Flex
Buy it

Specifications

Electrical specifications
Current ranges 20 A
200 A
2000 A
AC rms
Output sensitivity (AC-coupled) 1 mV
10 mV
100 mV
1 mV per A
Load impedance 100 kΩ minimum
Accuracy at +25°C
±1% of range (45 Hz to 65 Hz)
Linearity 10% to 100% of range
±0.2% of reading
Noise 8 mV AC rms (30 A)
2 mV AC rms (300 A, 3000 A)
Frequency range 10 Hz to 20 kHz (-3 dB)
Phase error < ±1° (45 Hz to 65 Hz)
±10° (at 20 kHz)
Position sensitivity with cable > 25 mm from the coupling
±2% of range
External field with cable > 200 mm from the head
±1% of range
Power supply 2 x AA/MN 1500/LR6 Alkaline, 200 hours, low battery indicator
Temperature Coefficient ±0.08% of reading per °C
Working voltage see Safety standards section
600 V AC rms or DC
General Specifications
Head Circumference 610 mm (24 in)
Head cable diameter 14.3 mm (0.56 in)
Head bend radius 38.1 mm (1.5 in)
Cable length (head to electronics) 2 m (6.56 ft)
Output connection Molded 4 mm safety plugs (not integrated)
Operating temperature range 0°C to +70°C (32°F to 158°F) (head and electronics)
Storage temperature range -40°C to +105°C (-40°F to 221°F) (head)
-20°C to +85°C (-4°F to 185°F) (electronics)
Operating humidity 15% to 85% (non-condensing)
Weight 180 g (6.34 oz) (head)
190 g (6.70 oz) (electronics)
Safety standards EN 61010-031: 2002
EN 61010-2-032: 2002
EN 61010-1: 2001
600 Vrms, Category III, Pollution Degree 2
Use of the probe on uninsulated conductors is limited to 600 V ac rms or dc and frequencies below 1 kHz.
EMC standards EN 61326: 1998 +A1, A2, and A3
Dimensions (H x W x D) 116 x 68.5 x 30 mm (4.56 x 2.69 x 1.18 in)

Resources

Compatible products