English

Product Selection Guide: IR windows

Use our product selection guide to find the IR window that fits your needs best.
RemoveRemove
F CV200 01A KO
Fluke 075 clkt 1b
Fluke CV200 ClirVu® 50 mm (2 in) Infrared WindowFluke 075 CLKT IR Window for Outdoor and Indoor Applications
Size50 mm (2 in)75 mm (3 in) 
Voltage rangeAnyAny 
NEMA environment typeType 4/12 (indoor/outdoor)Type 3/12 
AutoGround™   
ClirVu® Optic   
Operating temperature-40 °C to +232 °C (-40 °F to +450 °F) and +260 °C (+500 °F) intermittent-40 °C to +232 °C (-40 °F to +450 °F) 
Arc-tested (IEEE C27.20.7)67 kA for 30 cycles @ 60 Hz at KEMA60 kA for 30 cycles @ 60 Hz at KEMA 
UL 50/NEMA environmental ratingNEMA type 4/16NEMA type 3/12 
UL 1558  
CSA C22.2 No.   
CSA type ratingType 8Type 3/12 
IP ratingIP 67 at TUVIP 55 
Lloyd's RegisterUp to 11 kV marine switchgear, indoor or outdoor (offshore only)Up to 11 kV marine switchgear, indoor or outdoor (offshore only) 
Vibration ratingIEC60068-2-6 at TUVIEC60068-2-6 
Humidity rateIEC60068-2-3 at TUVIEC60068-2-3 
UL 50 V component recognition  
Actual mounting hole diameter required61.37 mm (2.416 in)69.9 mm (2.75 in) 
Greenlee punch kit - punch/die76BB = 441AV / 442AV04247/04246 
Door latchHand turnHand turn 
Install time9 minutes or less10 minutes 
Optic insert diameter50 mm (1.97 in)75 mm (3 in) 
WarrantyLifetime replacement against manufacturing defectsLifetime replacement against manufacturing defects