Australia [Change Country]  |  Fluke [Change Company]
fluke
Home  |  Products  |  Power Quality Tools  |  High Precision Power Analyzers  |  
Contact usRefer this page

Fluke Norma High Precision Power Analyzers

 Fluke Norma 4000/5000


Reliable, highly accurate measurements for the test and development of power electronics

The compact Fluke Norma Series Power Analyzers provide the latest measurement technology to assist engineers with the development and testing of motors, inverters, lighting, power supplies, transformers and automotive components.

Based on a patented, high-bandwidth architecture, the instruments deliver high-precision measurements of single or three-phase current and voltage, harmonics analysis, Fast Fourier Transformation (FFT) analysis, as well as calculations of power and other derived values.

The Series consists of the Fluke Norma 4000 Three-Phase Power Analyzer and the Fluke Norma 5000 Six-Phase Power Analyzer. These rugged, high-precision analyzers provide unmatched price performance for easy and reliable use in the field, or as a bench unit in laboratories and on test benches.


Applications

  • Electric motors and inverter drive systems – Through detailed spectrum analysis and dynamic torque calculation capabilities, switching losses caused by the inverter are accurately measured, and a thorough evaluation is made of torque transients and harmonics at higher frequencies.
  • Inverter drive system – Simultaneous measurement of all electrical and mechanical power parameters in the same time window enables users to observe the influence one component has on another, or on the whole system.
  • Lighting systems – A wide bandwidth of up to 10 MHz and a high sampling rate up to 1 MHz provide detailed signal analysis at ballast outputs. A unique shunt technique enables power measurements at very high frequencies. Simultaneous measurement of input and output power provides instant calculation of ballast losses.
  • Transformers – Synchronous six-phase power measurements enable highly accurate efficiency and loss calculations of large power transformers even at very low power factors. Synchronous multiphase resistance measurements of transformer coils are also possible.
  • Automotive – Synchronous electrical input and mechanical output measurements provide complete data on the efficiency and losses of individual components as well as the whole drive system.
Fluke Norma 4000/5000 Fluke Norma 4000: Ideal for field testing, the Fluke Norma 4000 Three-Phase Power Analyzer offers easy and straight-forward operation with unmatched price performance. Features include: 1 to 3 power phases, 5.7” / 144 mm color display, harmonic analysis, scope mode, vector diagram display, recorder function, Fluke NormaView PC software and expandable 4 MB RAM data memory.

Fluke Norma 5000: Providing the highest bandwidth on the market, the Fluke Norma 5000 Six-Phase Power Analyzer is the ideal test and analysis tool for the development of frequency converters and lighting equipment. Features include: 3 to 6 power phases, optional internal printer, and all of the Fluke Norma 4000 features and functionality described above.

  • Compact design makes it easy to carry and saves working space.
  • Simple user interface ensures easy, intuitive operation.
  • A variety of standard configurations allows users to choose the exact functionality required for their unique application.
  • Simultaneous parallel acquisition of all phases allows accurate viewing of dynamic events on all phases at exactly the same point in time.
  • All inputs are galvanically isolated to avoid short circuits in all applications.
  • Voltage, current and power harmonics measured up to the 40th harmonic for complete analysis.
  • FFT analysis, vector diagram, and Digital Oscilloscope (DSO) mode included in the base unit for complete analysis capability.
  • User-selectable average time – from 15ms up to 3600s – for dynamic measurements.
  • 4 MB on-board memory (expandable to 128 MB) for storage of measured values.
  • Fast and easy connection to a PC – RS232 and USB included as standard; optional IEEE488, Ethernet, or USB2.0.
  • PI1 process interface to measure torque and speed with external sensors, plus four analog outputs for easy use on motor and drive applications.
  • 341kHz or 1 MHz sample rates for detailed signal analysis.
  • Bandwidth from dc to 3 MHz / 10 MHz for reliable measurement precision.
  • Fluke NormaView PC software for data download, analysis & report writing.

 

General Specifications
Number of Phases
Fluke Norma 4000:  1 to 3
Fluke Norma 5000:  3, 4 or 6
Weight
Fluke Norma 4000:  Approx. 5 kg (11 lb.)
Fluke Norma 5000:  Approx. 7 kg (15 lb.)
Size
Fluke Norma 4000:  150 mm x 237 mm x 315 mm
(5.9 in x 9.3 in x 12.4 in)
Fluke Norma 5000:  150 mm x 447 mm x 315 mm
(5.9 in x 17.6 in x 12.4 in)
On-board Printer
Fluke Norma 4000:  No
Fluke Norma 5000:  Yes (optional)
Display
 Color, 5.7“ / 144 mm - 320 x 240 pixel
 User-selectable background lighting and contrast.
Bandwidth
 dc to 3MHz or dc to 10MHz depending on input module
Basic Accuracy
 0.2%, 0.1% or 0.03% depending on input modules
Sampling Rate
 0.33 MHz or 1 MHz depending on input modules
Voltage Input Range
 0.3 V to 1000 V
Current Input Range (direct, not via shunt)
 0.03 mA to 20 A depending on input module
Memory for Configurations
 4 MB
Memory for Settings
 0.5 MB
Fast Fourier Transformation (FFT)
 To the 40th harmonic
RS232/USB Interface
 Standard
PI1 Process interface (8 analog/impulse inputs and 4 analog outputs)
 Optional
IEEE 488.2/GPIB interface (1 MBit/s Ethernet / 10 MBit/s or 100 MBit/s)
 Optional
Fluke NormaView PC software (for data download, analysis & report writing)
 Standard

 

Basic Functions
Fast Fourier Transformation (FFT)
 Calculation of harmonics with graphical representation. Up to 3 bar graphs are displayed at the same time.
 Measured values: U, I, P per phase
 Order: 1st to 40th harmonics, maximum half sample frequency
Digital Oscilloscope (DSO)
 Simultaneous display of up to 3 measured values on sample level. Quick view of curve form and distortion.
Integration function (energy)
 Simultaneous display of up to 6 configurable numeric values. Start/Stop conditions and positive negative direction available.
Vector Display
 Vector display of HO1 up to 6 signals. For easy testing of the right connection of the instrument and quick overview of the phase angle of each signal.
Recorder
 Display of average values over time for trend determination.
RAM data memory
 Storing of sample and average values; setting of start and stop conditions.
 From the RAM approximately 4 MB are available for the storage of measured values.
Configuration
 Set up the analyzer to measure and display data in the format required.

 

Ambient Conditions
Working Temperature Range
 5 °C to 35 °C (41 °F to 95 °F)
Storage Temperature Range
 -20 °C to 50 °C (-4 °F to 122 °F)
Housing Material
 Fluke Norma Power Analyzers are extremely compact and equipped with a solid metal case to meet stringent EMC requirements.
Climatic Class
 KYG DIN 40040, max. 85 % relative humidity, non-condensing.
Power supply
 85 V ac to 264 V ac, 50 Hz to 60 Hz, dc 100 to 260 V, ca. 40 VA European plug with switch. Binding post for current available on some models.
Measuring Inputs
 Safety sockets 4 mm, 2 for each input. External shunt connection over BNC socket.
Operation
 Membrane keyboard with cursor – function keys and direct functions.
Connections
 Rear panel of the 3-phase Analyzer

 

Measured Values
 
 Non-gapping calculation of averaged values for each phase. In three phase system additionally calculation of total power and averaging of V and I of the three phases. The fundamental H01 will be calculated in synchronous mode also for these values.
 Urms effective value, Urm rectified mean, Um mean value
 Up-, Up+, Upp peak values
 Ucf crest factor Ucf, Uff form factor
 Ufc fundamental content
 Uthd distortion factor DIN, IEC
 Irms effective value, Irm rectified mean, Im mean value
 Ip-, Ip+, Ipp peak values
 Icf crest factor Icf, Iff form factor
 Ifc fundamental content
 Ithd distortion factor DIN, IEC
 P active power [W]
 Q reactive power [Var]
 S apparent power [VA]
 ë, cos. phase angular
 Integral function for active power P, reactive power Q, apparent power S, voltage (Um) and current (Im),
 Number of digits 4 or 5 dependent on measured value.

 

Frequency and Synchronization
Range
 DC and 0.2 Hz to sample rate
Accuracy
 ±0.01 % of measured value (reading)
 
 Channels which can be selected: all U/I or external input.
 One of three low pass filter with different frequencies can be switched into the signal.
 The frequency is always visible on the top of the screen.
 The BNC synchronization socket on backside of the instrument can be used either as input or output.
 The input signals can be measured up to the sample rate of the power phase. The maximum level must not be higher then 50V.
 The output signal is a pulsed 5Volts TTL signal (frequency depends on the measured synch frequency).

 

Configuration Memory
 
 Up to 15 user configurations can be saved into a permanent memory and reloaded later on. Changes that were not saved are lost after switching off the instrument.

 

Interface
 
 RS232 interface for upload of firmware and data exchange with the PC. A printer can be connected over an external converter.
Options
 IEEE 488.2 / 1 MBit/s
 Ethernet / 10 MBit/s or 100 Mbit/s

 

Standards and Safety
Electrical Safety
 EN 61010-1 / 2nd Edition 1000 V CAT II (600V CAT III)
 Degree of pollution 2, safety Class I
 EN 61558 for transformer
 EN 61010-2-031/032 for accessories
Maximum inputs
 For voltage inputs Measurement range 1000 Veff, 2 kVpeak
 For current inputs Measurement range 10 Aeff, 20 Apeak
Test voltage
Net input  case (protective conductor): 1.5 KV AC
Net connection  Measurement input: 5.4 kV AC
Measurement inputs  Case: 3.3 kV AC
Measurement input  input: 5.4 kV
Electromagnetic susceptibility
Emission:  IEC 61326-1, EN 50081-1, EN 55011 Class B
Immunity:  IEC 61326-1 / Annex A (industrial sector), EN 50082-1

Power Phases

The Fluke Norma 4000 Power Analyzer can be equipped with up to three power phases and the Fluke Norma 5000 Power Analyzer can be equipped with up to six power phases. Users can select the power phase best suited for their application. Specifications vary depending on the model of the power phase.

Each modular plug-in power phase consists of a voltage and a current measurement channel. Each measuring channel is available for each basic unit, however only one kind of channel can be used per unit. Check standard configurations.

Power Phase Overview

 

Power Phase Channels
PP42
Accuracy:  0.2% (0.1% rd + 0.1 % rg)
Current range:  20 A
Sampling rate:  341 kHz
Bandwidth:  3 MHz
PP50
Accuracy:  0.1% (0.05% rd + 0.05 % rg)
Current range:  10 A
Sampling rate:  1 MHz
Bandwidth:  10 MHz
PP54
Accuracy:  0.1% (0.05% rd + 0.05 % rg)
Current range:  10 A
Sampling rate:  341 kHz
Bandwidth:  3 MHz
PP64
Accuracy:  0.03% (0.02% rg + 0.01% rg)
Current range:  10 A
Sampling rate:  341 kHz
Bandwidth:  3 MHz
Model NameDescription
Fluke Norma 4000 High Precision Power Analyzer

Includes:

  • Power supply cable
  • 5.7“ / 144 mm color display
  • RS232/USB interface for data download
  • Space for three power-phases and options
  • Fluke NormaView PC software
  • User’s manual
  • Test certificate
  • Calibration values
Fluke Norma 5000 High Precision Power Analyzer

Includes:

  • Power supply cable
  • 5.7“ / 144 mm color display
  • Internal printer
  • RS232/USB interface for data download
  • Space for six power-phases and options
  • Fluke NormaView PC software
  • User’s manual
  • Test certificate
  • Calibration values


Standard Configurations

Short Description | Description
Fluke-N4K 1PP42
 Fluke-Norma 4000, single phase with PP42 power phase input module
Fluke-N4K 3PP42
 Fluke-Norma 4000, three phase with 3xPP42 power phase input modules
Fluke-N4K 3PP42I
 Fluke-Norma 4000, three phase with 3xPP42 power phase input modules with IEEE488 / Ethernet interface
Fluke-N4K 3PP42IP
 Fluke-Norma 4000, three phase with 3xPP42 power phase input modules with IEEE488 / Ethernet interface and analog / digital output channels
Fluke-N4K 3PP42B
 Fluke-Norma 4000, three phase with 3xPP42 power phase input modules with current binding post
Fluke-N4K 3PP42IB
 Fluke-Norma 4000, three phase with 3xPP42 power phase input modules with current binding post with IEEE488 / Ethernet interface
Fluke-N4K 3PP42IPB
 Fluke-Norma 4000, three phase with 3xPP42 power phase input modules with current binding post with IEEE488 / Ethernet interface and analog / digital output channels
Fluke-N4K 3PP50
 Fluke-Norma 4000, three phase with 3xPP50 power phase input modules
Fluke-N4K 3PP50I
 Fluke-Norma 4000, three phase with 3xPP50 power phase input modules with IEEE488 / Ethernet interface
Fluke-N4K 3PP50IP
 Fluke-Norma 4000, three phase with 3xPP50 power phase input modules with IEEE488 / Ethernet interface and analog / digital output channels
Fluke-N4K 3PP52IB
 Fluke-Norma 4000, three phase with 3xPP52 power phase input modules with current binding post with IEEE488 / Ethernet interface
Fluke-N4K 3PP54I
 Fluke-Norma 4000, three phase with 3xPP54 power phase input modules with IEEE488 / Ethernet interface
Fluke-N4K 3PP54IP
 Fluke-Norma 4000, three phase with 3xPP54 power phase input modules with IEEE488 / Ethernet interface and analog / digital output channels
Fluke-N5K 3PP50
 Fluke-Norma 5000, three phase with 3xPP50 power phase input modules
Fluke-N5K 3PP50I
 Fluke-Norma 5000, three phase with 3xPP50 power phase input modules with IEEE488 / Ethernet interface
Fluke-N5K 3PP50IP
 Fluke-Norma 5000, three phase with 3xPP50 power phase input modules with IEEE488 / Ethernet interface and analog / digital output channels
Fluke-N5K 3PP54
 Fluke-Norma 5000, three phase with 3xPP54 power phase input modules
Fluke-N5K 3PP54I
 Fluke-Norma 5000, three phase with 3xPP54 power phase input modules with IEEE488 / Ethernet interface
Fluke-N5K 3PP54R
 Fluke-Norma 5000, three phase with 3xPP54 power phase input modules and printer
Fluke-N5K 3PP54IP
 Fluke-Norma 5000, three phase with 3xPP54 power phase input modules with IEEE488 / Ethernet interface and analog / digital output channels
Fluke-N5K 3PP54IR
 Fluke-Norma 5000, three phase with 3xPP54 power phase input modules with IEEE488 / Ethernet interface and printer
Fluke-N5K 3PP64
 Fluke-Norma 5000, three phase with 3xPP64 power phase input modules
Fluke-N5K 3PP64I
 Fluke-Norma 5000, three phase with 3xPP64 power phase input modules with IEEE488 / Ethernet interface
Fluke-N5K 3PP64IP
 Fluke-Norma 5000, three phase with 3xPP64 power phase input modules with IEEE488 / Ethernet interface and analog / digital output channels
Fluke-N5K 3PP64R
 Fluke-Norma 5000, three phase with 3xPP64 power phase input modules and printer
Fluke-N5K 3PP64IR
 Fluke-Norma 5000, three phase with 3xPP64 power phase input modules with IEEE488 / Ethernet interface and printer
Fluke-N5K 3PP64IPR
 Fluke-Norma 5000, three phase with 3xPP64 power phase input modules with IEEE488 / Ethernet interface and analog / digital output channels and printer
Fluke-N5K 4PP54
 Fluke-Norma 5000, three phase with 4xPP54 power phase input modules
Fluke-N5K 4PP54IP
 Fluke-Norma 5000, three phase with 4xPP54 power phase input modules with IEEE488 / Ethernet interface and analog / digital output channels
Fluke-N5K 6PP42IB
 Fluke-Norma 5000, three phase with 6xPP42 power phase input modules with current binding post with IEEE488 / Ethernet interface
Fluke-N5K 6PP42IBR
 Fluke-Norma 5000, three phase with 6xPP42 power phase input modules with current binding post with IEEE488 / Ethernet interface and printer
Fluke-N5K 6PP50IP
 Fluke-Norma 5000, three phase with 6xPP50 power phase input modules with IEEE488 / Ethernet interface and analog / digital output channels
Fluke-N5K 6PP50IR
 Fluke-Norma 5000, three phase with 6xPP50 power phase input modules with IEEE488 / Ethernet interface and printer
Fluke-N5K 6PP50IPR
 Fluke-Norma 5000, three phase with 6xPP50 power phase input modules with IEEE488 / Ethernet interface and analog / digital output channels and printer
Fluke-N5K 6PP50I
 Fluke-Norma 5000, three phase with 6xPP50 power phase input modules with IEEE488 / Ethernet interface
Fluke-N5K 6PP54I
 Fluke-Norma 5000, three phase with 6xPP54 power phase input modules with IEEE488 / Ethernet interface
Fluke-N5K 6PP54IP
 Fluke-Norma 5000, three phase with 6xPP54 power phase input modules with IEEE488 / Ethernet interface and analog / digital output channels
Fluke-N5K 6PP54IR
 Fluke-Norma 5000, three phase with 6xPP54 power phase input modules with IEEE488 / Ethernet interface and printer
Fluke-N5K 6PP54IPR
 Fluke-Norma 5000, three phase with 6xPP54 power phase input modules with IEEE488 / Ethernet interface and analog / digital output channels and printer
Fluke-N5K 6PP64I
 Fluke-Norma 5000, three phase with 6xPP64 power phase input modules with IEEE488 / Ethernet interface
Fluke-N5K 6PP64IP
 Fluke-Norma 5000, three phase with 6xPP64 power phase input modules with IEEE488 / Ethernet interface and analog / digital output channels
Fluke-N5K 6PP64IR
 Fluke-Norma 5000, three phase with 6xPP64 power phase input modules with IEEE488 / Ethernet interface and printer
Fluke-N5K 6PP64IPR
 Fluke-Norma 5000, three phase with 6xPP64 power phase input modules with IEEE488 / Ethernet interface and analog / digital output channels and printer

Search Fluke
ResourcesProducts
Find Resources

Follow us        Home   |   Site Map   |   Fluke Corporation   |   Privacy Statement   |   Terms of Use   |   Terms and Conditions of Sale © 1995 - 2014 Fluke Corporation