English

Using Non-Contact Tools to Stay Out of Harm's Way

Safety

It's the foundation of any electrical safety program: limiting the exposure of workers to the electrical hazards of shock and arc flash. Using test leads and clamps to probe inside a live panel when troubleshooting and performing routine maintenance always exposes workers to danger. Electrical personal protective equipment (PPE) is a last line of defense and must never be relied upon as the primary method of protecting electricians and technicians. Safe work practices, including the use of non-contact test tools that do not require electrical workers to place themselves in harm's way, must first be considered when it comes to electrical safety.

Any time workers are exposed to electrical hazards they are required to establish boundaries and wear the appropriate arc-rated clothing and rubber insulating gloves. Safely reducing the amount of PPE worn, reducing the number of workers inside the boundary, and even completely moving the test technician or electrician outside of all boundaries and away from potential danger are the major safety advantages of non-contact measurements.

The simplest step

Obtain accurate temperature data
Using the IR thermometer allows technicians to stand at a safe distance from equipment and components to obtain accurate temperature data. Key to obtaining an accurate temperature is understanding that increasing the distance from the object measured decreases the accuracy of the reading as the thermometer takes an average of temperature of the area measured.

Among the simplest non-contact test tools to use are non-contact infrared (IR) thermometers. Using the tool's pistol grip to point a laser beam where the temperature is to be measured produces a temperature reading on the display. The laser beam is only for "aiming" the tool at the area to be measured. The temperature detected depends upon the tool's distance from the point of measurement. Care must be taken to achieve accurate results.

When it comes to safety, using an IR thermometer means no climbing on ladders to check ventilation exhaust temperatures, no reaching around hot temperature bands and barrels to troubleshoot process problems, no reaching around rotating shafts to check for motor hot spots, and no reaching inside of live panels to check temperatures of components.

Visual infrared thermometers

A more advanced, yet practical tool is the visual IR thermometer. In addition to the standard IR thermometer features, the visual thermometer provides a digital image creating an infrared heat map—somewhat like a thermal imager. The visual IR thermometer is more accurate than the standard IR thermometer as it does not average in surrounding areas. Instead, the heat map is blended with a standard digital image so problem areas can be readily identified. You can download digital images to computer for further analysis and report generation, allowing you to work at safe distances well beyond most shock and arc flash boundaries.

The Visual IR Thermometer blends the digital image of the object under measurement with the heat map indicating the now obvious to the unwary worker: This specific circuit breaker is overheating and poses a potential safety problem.

The heat map of the visual IR thermometer allows for quick identification of overheated conductors and terminations—potential fire hazards. Overheated contacts and electrical components could indicate pending equipment failures and possible arc flash issues. Identifying and reducing hazards is a goal of every safety program.

Using an infrared camera

Infrared cameras not only capture and measure the infrared (heat) energy emanating from a source, but produce a thermal image, as well. Colors on the screen indicate the degree of heat coming from various components. Viewing a thermal image, especially when the standard digital image of the source is fused with the thermal image, produces a user-friendly picture for identifying potential problems. The operator can readily distinguish the difference in temperatures across the source image and quickly determine if corrective action is needed, and even how soon.

For example, when performing a thermal scan of electrical equipment, the InterNational Electrical Testing Association (NETA) notes that if a temperature difference between similar components under similar loading is between 4 °C and 15 °C there is a problem with the higher temperature component and it should be repaired when possible. However, if that temperature difference between the similar components increases to greater than 15 °C, then immediate repairs should be completed.

Imagine one terminal on a three-phase breaker running significantly more than 15 °C hotter than the other two phases. Such an indication could mean a very high resistance at the terminal is producing dangerously high heat, insulation is beginning to soften and deform, and the breaker itself is near catastrophic failure. A non-contact measurement with a thermal imager identifies the potential failure in real time and, most importantly, keeps the technician at a much safer distance while diagnosing a potentially dangerous problem.

A person trained to use an infrared camera can function as part of a two-man team (the additional qualified person assists with setting up boundaries and opening enclosure doors) that can quickly move through a facility identifying overloaded circuits, faulty electrical and rotating mechanical equipment, and thermal process issues. Averting potential safety problems by correcting before failure is another component of a safe work environment.

Widening the safety window

IR window infrared camera thermal view
Using the IR Window to perform a thermal scan of equipment greatly increases safety for the thermal imaging technician. Shock and arc flash exposures are reduced to virtually zero.

Using an infrared (IR) window in conjunction with a thermal imager widens the safety envelope even further. Relatively small, circular IR windows can be permanently installed on enclosures that are part of the plant's thermal imaging program, or can be mounted on equipment enclosures that may produce a dangerous arc flash should an accident occur while the door is open. By scanning through an IR window that is rated to withstand an arc flash and blast, it is not even necessary to open an enclosure door to scan. As a result there is virtually no technician exposure to shock or arc flashes. It would be hard for routine maintenance and troubleshooting to get any safer!

Keeping your distance

One tool that is often overlooked when it comes to safety is the laser distance meter. Generally considered only a convenience item, this non-contact distance measurement tool also increases safety when doing such jobs as conducting an arc flash study. This engineering analysis requires measuring the lengths of conductor runs between equipment. Rather than using steel measuring tapes and stepladders with two people finding themselves in precarious positions near and over cable trays and switchgear, the laser distance meter allows many distance measurements to be taken safely from the floor by just one person. Press the Measure Button once and the laser is activated. Then, point the laser to where the distance is to be measured and press the Measure Button again to read an accurate distance of up to 200 feet (61 meters) or more on the display.

Don't make contact with an energized part

Non-contact voltage detectors allow voltages to be detected without having to make contact with an energized part. For quick power checks at a receptacle or troubleshooting a lighting circuit, using a voltage detector is safer than placing probes in a receptacle and much safer than opening boxes and lighting fixtures. Users must be aware that voltage detectors will only indicate power on the ungrounded side of the circuit; not on the grounded or neutral conductor side.

Remote display

Remote display multimeters allow readings to be taken up to thirty feet (9 meters) away from the equipment being monitored. The display unit is removed from the multimeter while the meter and probes (or clamp) remain at the point of measurement.

Safety applications include closing the door on an MCC cubicle or disconnecting and standing at a safe distance to measure motor inrush current. Standing directly in front of a motor starter when a large three-phase motor draws many times its normal running current at startup is no place to be, even if wearing the appropriate PPE. Once again, the use of non-contact tools greatly reduces the personnel risk.

Wireless tools

Wireless tools provide the most advanced technology for enhancing safety. For example, you set up three remote modules at the equipment to be monitored. The digital multimeter (DMM) itself, with its display, can be held and observed at a safe distance more than sixty feet (18 meters) away, where it receives the wireless signals. If desired, up to ten readings can be downloaded real time wirelessly directly from the modules to a laptop.

Wireless tools are increasingly utilizing the cloud, where data goes from the tools to an app, where data can be shared, stored, and viewed by your team from their laptop, tablet, or smart phone.

Wireless test tools allow multiple readings to be made at a safe distance from equipment rather than in front of open enclosures. Multiple readings mean less time inside a live panel.

Technicians can stay well outside any shock or arc flash boundaries as equipment is operated and various parameters are observed and recorded. Many troubleshooting motor controls tasks are classed as Hazard Risk Category 2 requiring the use of an arc rated face shield and balaclava. Once the modules are installed and the covers replaced, the hazard risk category can be dropped to zero with the need for cumbersome faceshields, uncomfortable balaclavas and bulky rubber insulating gloves all eliminated. Taking several readings simultaneously helps minimize the need for workers to re-enter the limited approach and arc flash boundaries.

Summary

The use of non-contact test tools greatly limits and oftentimes completely eliminates the need for workers to be exposed to the electrical hazards of shock, arc flash, and blast, but does not completely eliminate the need for PPE. Using non-contact tools may allow the user to reduce the hazard risk level associated with a measurement that will reduce the type and amount of PPE required. Probing inside a live panel with hands, test leads, and clamps while attempting to locate measuring points, and then placing and holding test leads while turning and leaning to read a meter display, carries hazards. Many times two workers are required to accomplish this task, with the additional worker thus being exposed to the hazards. Providing a practical safe working area free of electrical hazards is the stated purpose of electrical safety standards. The use of non-contact test tools can help achieve that goal and create an electrically safe and more efficient work environment for employees.

Other resources

Go to PDF version of this article