Stromversorgungsanalysator Fluke 434 Serie II Basic

  • Fluke 434 Serie II Energianalysator | Fluke
  • Fluke 434 Serie II Energianalysator | Fluke
  • Fluke 434 Serie II Energianalysator | Fluke

Nøglefunktioner

The Fluke 434-II is designed for users who need to get to the solution of the power quality problem as quickly as possible so that they can minimize expensive downtime. The measurement process and display of data is optimized to get to the most important information as quickly as possible. Multiple parameters are measured simultaneously and displayed in formats that quickly describe overall power quality health while giving you the detailed information you need to make better maintenance decisions. Data can be quickly accessed as simple digital values, trend graphs that give you fast insight into changes over time, waveforms, phasor diagrams or analyzed and organized into tabular format such as the event data where the magnitude, duration and time stamping enable rapid correlation to the problems you are experiencing in your facility.

Energy loss Calculator—Calculate money lost to energy waste in terms of real dollars.
It’s a simple fact, poor power quality can have a big impact on the bottom line. The Fluke 435-II enables you to identify issues and measure energy loss giving you specific insight into the amount of loss in dollars associated things like effective power and with poor power quality characteristics such as reactive power, unbalance, distortion, or neutral current. The 435-II even offers users the flexibility to input cable length and cable diameter so you can calculate loss due to conductor sizing (Or use AUTO mode if you don’t know your cable specification) and enter up to four unique time-dependent daily rates (kWh) for more accurate calculations. Armed with this critical data users can easily justify the investment necessary to take countermeasures.

Advanced Power Quality Health— At-a-glance power quality health data in real-time so you have the data you need, when you need it
The Fluke 430-II utilizes an integrated Power Quality Health summary that gives you an at-a-glance view of a complete range of power quality issues in real time. With a simple graphical presentation, complete with tolerance limits, you can quickly discover which power quality problems may be present on your electrical system. If you don’t know where to start or what problems might exist, the advanced Power Quality Health summary will simplify the task.

 

Power Inverter Efficiency
Power inverters take DC current and transform it into AC current, or vice versa. But, what percentage of that power going into the inverter comes out as usable current? Nothing is ever 100% efficient, and the efficiency will vary depending on how much power is being used at the time (with the efficiency generally being greater when more power is being used). Inverters can also lose performance over time and need to be checked. By comparing the input power with the output power you can determine the system efficiency. With the Power Inverter Efficiency feature you can discover just how good is your inverter at converting your DC power to AC (or visa versa).

AutoTrend - Quickly See the Trend
With a unique AutoTrend feature you can get fast insight into changes over time. Every displayed reading is automatically and continuously recorded without having to set up threshold levels or having to manually start the process So you can quickly view trends in voltage, current, frequency, power, harmonics or flicker on all three phases plus neutral.

Få en gratis demoKøb nu

Produktoversigt: Stromversorgungsanalysator Fluke 434 Serie II Basic

Beregn energitab i local valuta

Fluke 434 II energianalysatoren er det ideelle værktøj til energi-logning. Med den nye funktion til energitabsberegning måler 434 II den økonomiske omkostning ved energi spildt på grund af dårlig effektkvalitet. Med denne energitabsberegner kan du identificere de områder af anlægget, hvor energispildet er størst, og dermed fastlægge eventuelle energibesparende løsninger. Føj de grundlæggende effektkvalitetsmålinger til pakken, og du har et kraftfuldt fejlfindingsværktøj.

Anvendelser

  • Opgørelse af energi i penge - beregn de økonomiske omkostninger ved energi spildt på grund af dårlig effektkvalitet
  • Energivurdering - kvantificer energiforbruget før og efter installationsforbedringer for at retfærdiggøre energibesparende enheder
  • Fejlfinding i frontlinien - diagnosticer øjeblikkeligt problemerne på skærmen, så du kan genoptage driften
  • Forebyggende vedligeholdelse - detekter og forebyg effektkvalitetsproblemer, inden de medfører nedetid
  • Langtidsanalyse - afslør skjulte eller periodiske problemer
  • Belastningsundersøgelser - kontroller elektriske systemers kapacitet, før der tilføjes belastninger

Specifikationer: Stromversorgungsanalysator Fluke 434 Serie II Basic

Produktspecifikationer

  Model Måleområde Opløsning Nøjagtighed
Volt
Vrms (AC+DC)434-II1 V til 1000 V fase til nul0,1 V± 0,5% af nominel spænding**** 
Vpk  1 Vpk til 1400 Vpk1 V5 % af nominel spænding
V topfaktor (CF)  1,0 > 2,80.01± 5 %
Vrms½434-II1 V til 1000 V fase til nul0,1 V± 1% af nominel spænding 
Vfund434-II1 V til 1000 V fase til nul0,1 V ± 0,5 % af nominel spænding
Ampere (nøjagtighed eksklusive nøjagtighed for tang)
Ampere (AC + DC)i430-Flex 1x 5 A til 6000 A1:00 AM± 0,5% ± 5 trin
i430-Flex 10x0,5 A til 600 A0,1 A± 0,5% ± 5 trin
1mV/A 1x5 A til 2000 A1A± 0,5% ± 5 trin
1mV/A 10x0,5 A til 200 A (kun AC)0,1 A± 0,5% ± 5 trin
Apki430-Flex 8400 Apk 1 Arms± 5 %
1mV/A5500 Apk1 Arms± 5 %
A topfaktor (CF)  1 til 100.01± 5 %
Ampere½i430-Flex 1x 5 A til 6000 A 1 A ± 1% ± 10 trin 
i430-Flex 10x0,5 A til 600 A0,1 A ± 1% ± 10 trin
1mV/A 1x  5 A til 2000 A 1A ± 1% ± 10 trin
1mV/A 10x0,5 A til 200 A (kun AC)0,1 A± 1% ± 10 trin
Afundi430-Flex 1x 5 A til 6000 A1:00 AM± 0,5% ± 5 trin 
i430-Flex 10x 0,5 A til 600 A0,1 A± 0,5% ± 5 trin
1mV/A 1x 5 A til 2000 A1A± 0,5% ± 5 trin
1mV/A 10x 0,5 A til 200 A (kun AC)0,1 A± 0,5% ± 5 trin
Hz
HzFluke 434 ved 50 Hz nominelt 

42,50 Hz til 57,50 Hz

0,01 Hz ± 0,01 Hz
Fluke 434 ved 60 Hz nominelt51,00 Hz til 69,00 Hz0,01 Hz± 0,01 Hz
Effekt
Watt (VA, var)i430-Flex maks. 6000 MW0,1 W til 1 MW± 1% ± 10 trin
1 mV/Amaks. 2000 MW0,1 W til 1 MW± 1% ± 10 trin
Effektfaktor (Cos j/DPF)  0 til 10.001± 0,1% ved nominel belastning
Energi
kWh (kVAh, kvarh)i430-Flex 10xAfhænger af skalering af tang og nominel spænding± 1% ± 10 trin
Energitabi430-Flex 10xAfhænger af skalering af tang og nominel spænding± 1 % ± 10 trin ekskl. nøjagtig ledningsmodstand
Harmoniske
Harmonisk rækkefølge (n)  DC, 1 til 50 gruppering: Harmoniske grupper i overensstemmelse med IEC 61000-4-7
Interharmonisk rækkefølge (n)  FRA , 1 til 50 gruppering: Harmoniske og interharmoniske undergrupper i overensstemmelse med IEC 61000-4-7
Volt%f0,0 % – 100 %0.10%± 0,1% ± n x 0,1 %
%r0,0 % – 100 %0.10%± 0,1% ± n x 0,4 %
Absolut0,0 til 1000 V0,1 V± 5 % *
THD0,0 % – 100 %0.10%± 2,5 %
Ampere%f0,0 % – 100 %0.10%± 0,1% ± n x 0,1%
%r0,0 % – 100 %0.10%± 0,1% ± n x 0,4 %
Absolut0,0 til 600 A0,1 A± 5 % ± 5 trin
THD0,0 % – 100 %0.10%± 2,5 %
Watt%f eller %r 0,0 % – 100 %0.10%± n x 2%
AbsolutAfhænger af skalering af tang og nominel spænding ± 5% ± n x 2 % ± 10 trin
THD0,0 % – 100 %  0.10%± 5 %
Fasevinkel-360° til +0°± n x 1°
Flicker
Plt, Pst, Pst (1 min.) Pinst  0,00 til 20,000.01± 5 %
Ubalance
Volt%0,0 % – 20,0 %0.10%± 0,1 %
Ampere%0,0 % – 20,0 %0.10%± 1 %
Netsignalering
Tærskelniveauer  Tærskel, grænseværdier og varighed af signalering kan programmeres for to signaleringsfrekvenser
Signaleringsfrekvens  60 Hz til 3000 Hz0,1 Hz 
Relativ V%  0 % – 100 %0.10%± 0,4 %
Absolut V3s (3 sekunders gennemsnit)  0,0 V til 1000 V0,1 V± 5 % af nominel spænding
 

Generelle specifikationer

TaskeRobust og stødsikkert design med indbygget beskyttelseshylster. Dryp- og støvtæt (IP51) i henhold til IEC60529 ved anvendelse i tilt-stativet. Stød og vibration: stød 30 g, vibration: 3 g sinus, tilfældig 0,03 g2/Hz i overensstemmelse med MIL-PRF-28800F Class 2
DisplayLysstyrke: 200 cd/m2 typisk ved brug af netadapter, 90 cd/m2 typisk ved batteridrift. Mål: 127 mm x 88 mm (153 mm/6.0 in diagonal) LCD-opløsning: 320 x 240 pixel. Kontrast og lysstyrke: brugerjusterbar, temperaturkompenseret
Hukommelse8 GB SD-kort (SDHC-kompatibelt, FAT32-formatteret) som standard, fås med op til 32 GB. Skærmlagring og flere hukommelser til lagring af data, herunder registreringer (afhængigt af størrelsen af hukommelsen)
SandtidsurTids- og datostempel for Trend funktion, transientvisning, systemovervågning og hændelsesregistrering
 

Miljø

Driftstemperatur0 °C ~ +40 °C; +40 °C ~ +50 °C ekskl. batteri
Opbevaringstemperatur -20 °C ~ +60 °C
Fugtighed+10 °C ~ +30 °C: 95 % relativ luftfugtighed, ikke-kondenserende
+30 °C ~ +40 °C: 75% relativ luftfugtighed, ikke-kondenserende
+40 °C ~ +50 °C: 45% relativ luftfugtighed, ikke-kondenserende
Maks. driftshøjdeOp til 2.000 m (6666 fod) for KAT IV 600 V, CAT III 1000 V
Op til 3.000 m (10,000 fod) for KAT III 600 V, KAT II 1000 V
Maksimal opbevaringshøjde: 12 km (40.000 fod)
Elektromagnetisk kompatibilitet (EMC)EN 61326 (2005-12) for emission og immunitet
Interfacesmini-USB-B, isoleret USB-port til pc-tilslutning. Indgang til SD-kort bag instrumentets batteri
GarantiTre år (materialer og udførelse) på måleinstrumentet, et år på tilbehør
 

View full family specifications

    * ± 5 % hvis ≥ 1 % af nominel spænding ± 0.05 % af nominel spænding, hvis < 1% af nominel spænding
   ** 50 Hz/60 Hz nominel frekvens i overensstemmelse med IEC 61000-4-30
 *** 400 Hz-målinger understøttes ikke i flicker-, netsignalerings- og overvågningstilstand.
****for nominel spænding 50 V til 500 V

Modeller: Stromversorgungsanalysator Fluke 434 Serie II Basic

Fluke 434 II Basic
Fluke 434 Series II Basic Energy Analyzer
Køb

Includes:

  • BC430 Power Adapter
  • International Plug Adapter Set
  • BP290 (Single Capacity Li-ion Battery) 28 Wh (8 hours or more)
  • TLS430 Test Lead and Alligator Clip Set
  • WC100 Color Coding Clips and Regional Decals
  • 8 GB SD Card
  • PowerLog on CD (includes operator manuals in PDF format)
  • USB Cable A - Mini B
  • C1740 Soft Case
Fluke-438-II/MA

430-II motoranalysator opgraderingssæt

Køb

inkluderer:

  • Firmwareopgraderingspakke til at tilføje motoranalysefunktioner til eksisterende Fluke 434, 435 og 437 serie II effektkvalitetsanalysatorer