The most trusted tools in the world
Home  |  Products  |  Power Quality Tools  |  Logging Power Meters   |  

Fluke 1735 Three-Phase Power Logger

 

Contact Me
Request A Demo

 Fluke 1735

Power quality logging, electrical load studies and energy consumption testing.

The Fluke 1735 Power Logger is the ideal electrician or technician’s power meter for conducting energy studies and basic power quality logging. Set the Power Logger up in seconds with the included flexible current probes and color display. The power quality meter measures most electrical power parameters, harmonics, and captures voltage events.

Applications
  • Load studies - verify electrical system capacity before adding loads
  • Energy assessments - quantify energy consumption before and after improvements to justify energy saving devices
  • Harmonics measurements - uncover harmonic issues that can damage or disrupt critical equipment
  • Voltage event capture - monitor for dips and swells that cause spurious resets or nuisance circuit breaker tripping

Fluke 1735 Three-Phase Power Logger 4.8 5 4 4
Works great and has nice features. Used for logging power consuption on particular equipment and checking machine duty cycle. July 16, 2012
The features and ease of using the Pwoer Logger I am on assignment in the Republic of Georgia and ordered the Fluke 1735 power logger, when it arrived on site it was a happy day for me. So far it has been a good learning experience for me, since I was not exposed to the testing of power circuits with a power meter. Right away we begain using it to anylize a power problem with VFD`s tripping out on suspected dirty power. First testing the load side feeding the motor we had 92 events (dips) which led to the VFD tripping out. Then we attached to the supply side and the events went away except for start up and tripping off. Solution was to add capacitors on the load, coming from the VFD. This will not be the last time we use are power logger in fact I will now give a power point training on the power logger 1735 to our Georgian Staff Members. Over the years I have always relied on my Fluke meter, now power logger and hopefully the Thermal Imaging Ti125 that I will order for the site here in Georgia. June 8, 2012
Awesome full-featured logger! Using the Fluke 1735 logger is a real pleasure! The flexible current probes are a technological marvel! I've been able to loop multiple heavy-gauge panel feeders simultaneously even in the most crowded distribution and control panels! Another nice feature of the flexible probes is the ability to multi-loop for accuracy on small power feeds (divide results by number of turns of course)! The single point, quick disconnect multi-conductor plugs for current or for voltage are a snap to connect and cannot be crossed up. They make an end of numerous jacks and plugs getting mixed up. The Power Logger software is very user-friendly, making reports on data easy to extract and document. There are numerous reports available! See specifications! Very happy with the entire package!! June 7, 2012
best features I have two great equipment also 434 fluke is a great investment tool. June 7, 2012
1-4 of 4

Fluke 1735

  • Record power and associated parameters for up to 45 days
  • Monitor maximum power demand over user-defined averaging periods
  • Prove the benefit of efficiency improvements with energy consumption tests
  • Measure harmonic distortion caused by electronic loads
  • Improve reliability by capturing voltage dips and swells from load switching
  • Easily confirm instrument setup with color display of waveforms and trends
  • Measure all three phases and neutral with included 4 flexible current probes
  • View graphs and generate reports with included Power Log software
  • Compact, rugged design with IP65 case, 600 V CAT III and two-year warranty

Specifications
General
Display:  ¼ VGA Graphic Color transmissive displays 320 x 240 Pixel with additional background lighting and adjustable contrast, text and graphics in color
Quality:  Developed, designed and manufactured according to DIN ISO 9001
Memory:  4 MB Flash memory, 3.5 MB for measuring data
Interface:  RS-232 SUB-D socket; 115.2 k Baud, 8 data bits, no parity, 1 stop bit, firmware updates are possible with the RS- 232 interface (9-pole extension cable)
Sample rate:  10.24 kHz
Line frequency:  50 Hz or 60 Hz, user-selectable, with automatic synchronization
Power supply:  NiMH battery-pack, with ac adapter (15 V to 20 V/0.8 A)
Operation time with battery:  Typical > 12 hours without backlight and > 6 hours with backlight high
Dimensions:  240 mm x 180 mm x 110 mm
Weight:  1.7 kg, including battery
Ambient conditions
Working temperature range:  -10 °C to +50 °C
Storage temperature range:  -20 °C to +60 °C
Operating temperature range:  0 °C to +40 °C
Reference temperature range:  23 °C ± 2 °C
Note:  The above terms are defined in European Standards. To calculate the specification at any point in the working temperature range, use the temperature coefficient below.
Temperature coefficient:  ± 0.1 % of the measured value per °C from the reference
Intrinsic error:  Refers to reference temperature, maximum deviation is guaranteed for two years
Operating error:  Refers to operating temperature range, maximum deviation is guaranteed for two years
Climatic class:  C1 (IEC 654-1) -5 °C to +45 °C, 5% to 95% RH, no dew
Housing:  Cycoloy shock and scratch proof thermoplast V0-type (non-flammable) with rubber protection holster
EMC
Emission:  IEC/EN 61326-1:1997 class B
Immunity:  IEC/EN 61326-1:1997
Safety
Safety:  IEC 61010-1 600 V CAT III, double or reinforced insulation, pollution degree 2
Protection:  IP65; EN60529 (refers only to the main housing without the battery compartment)
 RMS values are measured with a 20 ms resolution.
V-rms wye measurement
Measuring range:  57 V/66 V/110 V/120 V/127 V/220 V/230 V/240 V/260 V/277 V/347 V/380 V/400 V/417 V/480 V ac
Intrinsic error:  ± (0.2% of measured value + 5 digits)
Operating error:  ± (0.5% of m. v. + 10 digit)
Resolution:  0.1 V
V-rms delta measurement
Measuring range:  100 V/115 V/190 V/208 V/220 V/380 V/400 V/415 V/450 V/480 V/600 V/660 V/690 V/720 V/830 V ac
Intrinsic error:  ± (0.2% of m. v. + 5 digit)
Operating error:  ± (0.5 % of m. v. + 10 digit)
Resolution:  0.1 V
A-rms measurement
Flexi set I ranges:  15 A/150 A/3000 A rms (at sine)
Current clamp ranges:  1 A/10 A
Resolution:  0.01 A
Ranges  150 A/3000 A and 1 A/10 A
Intrinsic error:  ± (0.5 % of m. v. + 10 digit)
Operating error:  ± (1 % of m. v. + 10 digit)
Ranges  15 A
Intrinsic error:  ± (0.5 % of m. v. + 20 digit)
Operating error:  ± (1 % of m. v. + 20 digit)
 The errors of the current probes are not considered.
By using Flexi-Set
Flexi Set measuring error:  ± (2% of m. v. + 10 digit)
Position influence:  ± (3 % of m. v. + 10 digit)
CF (typical):  2.83
Note:  When using Flexi Set please make sure to position the conductor opposite to the Flexi Set-lock
Power measurement (P - Active, S - Apparent, Q- reactive, D - Distorting
Measuring range:  see V rms and A rms measurement
 Power errors are calculated by adding the errors of voltage and current
 Additional error due to power factor PF
 Specified error x (1-[PF])
 Maximum range with voltage range 830 V delta-connection and 3000 A current range is 2.490 MW, higher displayed values possible when using PTs and CTs with ratio feature
Intrinsic error:  ± (0.7 % of m.v. +15 digit)
Resolution:  1 kW
Operating error:  ± (1.5 % of m.v. + 20 digit)
 Typical range with voltage range 230 V wye connection and 150 A current range is 34.50 KW.
Intrinsic error:  ± (0.7 % of m.v. +15 digit)
Resolution:  1 W to 10 W
Operating error:  ± (1.5 % of m.v. + 20 digit)
 The errors of the current sensors themselves have not been considered.
Energy measurement (kWh, KVAh, kVARh)
Intrinsic error:  ± (0.7 % of m.v.+ F variation error* + 15 digit)
Resolution:  1 W to 10 W
Operating error:  ± (1.5 % of m.v. + F variation error* + 20 digit)
 *Frequency variation error
PF (Power factor)
Range:  0.000 to 1.000
Resolution:  0.001
Accuracy:  ±1 % of full scale
Frequency measurement
Measuring range:  46 Hz to 54 Hz and 56 Hz to 64 Hz
Intrinsic error:  ± (0.2 % of m. v. + 5 digit)
Operating error:  ± (0.5 % of m. v.+ 10 digit)
Resolution:  0.01 Hz
Harmonics
Measuring range:  To 50th harmonic (< 50 % of nom)
Accuracy
Vm, Im, THDV, THDI:  IEC 61000-4-7:2002, Class II
Vm ≥ 3% Vn:  ± 5% Vm
Vm < 3 % Vnom:  ±0.15% Vnom
Im ≥ 10 % Inom:  ± 5% Im
Im < 10 % Inom:  ± 0 5% Inom
THDV:  for THD < 3% ± 0.15% at Vnom
for THD ≥ 3% ± 5% at Vnom
THDI:  for THD < 10% ± 0.5% at Inom
for THD ≥ 10% ± 5% at Inom
Vnom:  Normal voltage range
Inom:  Nominal current range
 Vm and Im are measured values of harmonic m
Events
 Detection of voltage dips, voltage swells and voltage interruptions with a 10 ms resolution and measuring error of the half period sine wave of rms.
Intrinsic error:  ± (1% of m.v. + 10 digit)
Operating error:  ± (2% of m.v. + 10 digit)
Resolution:  0.1 V
Model NameDescriptionBuy it
Fluke 1735 Power Logger
Includes:
  • Includes soft carrying case
  • 4 flexible current probes (15 A/150 A/3000 A)
  • Power Log software
  • Voltage leads and clips
  • Color localization set
  • PC interface cable
  • International ac adapter (115/230 V, 50/60 Hz)
  • Printed English manual
  • Multi-language manual CD
 

CarePlansBuy it
G2P-Group4
  • GOLD CarePlan.
  • Models covered: 975, 1625, and 1735.
  • Extends warranty from two to four years and includes four annual NIST traceable calibrations with data.
 
S2P-Group4
  • SILVER CarePlan.
  • Models covered: 975, 1625, and 1735.
  • Extends warranty from two to four years.

Cases and HolstersBuy it
C435C435 Hard Rolling Case 

Current ClampsBuy it
3000/6000A Flex 43000A/6000A 36-INCH FLEXI PROBE 4 PHASE  
I1A/10A Clamp PQ1I1A/10A Clamp PQ1, 1-PHASE 1A/10A MINI CURRENT CLAMP SET for PQ 
I1A/10A Clamp PQ3I1A/10A Clamp PQ3 3-Phase 1A/10A 
I1A/10A Clamp PQ4I1A/10A Clamp PQ4 
I20A/200A Clamp PQ3I20A/200A Clamp PQ3  
I20A/200A Clamp PQ4I20A/200A Clamp PQ4  
I5A/50A Clamp PQ1I5A/50A Clamp PQ1, 1-PHASE 5A/50A MINI CURRENT CLAMP SET FOR PQ 
I5A/50A Clamp PQ3I5A/50A Clamp PQ3 
I5A/50A Clamp PQ4I5A/50A Clamp PQ4 

Test LeadsBuy it
VL1735/45VL1735/45 

Power Meter | Power Monitoring | Digital Power Meter | Power Quality Analyzer
Voltage Recorder | Power Quality Analysis | Disturbance Analyzer

        
Related Products

 Write the first review
 
 3000A/6000A 36-INCH FLEXI PROBE 4 PHASE »

 Write the first review
 
 C435 Hard Rolling Case »

 Write the first review
 
 I1A/10A Clamp PQ4 »
You need Flash player 8+ and JavaScript enabled to view this video.
Learn More »
Home   |   Site Map   |   Fluke Corporation   |   Safety Notices  |   Terms and Conditions   |   Privacy Statement   |   Disclaimer © 1995 - 2013 Fluke Corporation