i6000sFlex AC Current Probe

 i6000sFlex
The i6000sflex is an AC current probe utilising the Rogowski principle. It can be used to measure currents up to 6000A when used in conjunction with oscilloscopes, recorders or data loggers. The flexible and lightweight measuring head allows quick and easy installation in hard to reach areas.
Electrical Characteristics
Current Ranges
 60 A / 600 A / 6000 A ACRMS
Output Sensitivity (AC coupled)
 50 mV /5mV / 0.5mV per A
Load Impedance
 100 kOhm minimum
Accuracy (at +25°C)
 ±1% of range (45 – 65 Hz)
Linearity (10% to 100% of range)
 ±0.2% of reading
Noise
 8mV ACRMS (60 A)
 2 mV ACRMS (600/6000A)
Frequency Range
 10 Hz to 50 kHz (- 3 dB)
Phase Error
 < ±1º (45 – 65Hz),
 ±10º (at 20 kHz)
Position Sensitivity (with cable > 25mm from the coupling)
 ±2% of range
External field (with cable > 200mm from the head)
 ±1% of range
Power Supply
 2 x AA MN 1500 LR6 alkaline
 400 Hours, low battery indicator or dedicated ext power supply
Temperature Coefficient
 ±0.08% of reading per C
Working Voltage (see Safety Standards section)
 600 V ACRMS or DC

General Characteristics
Head Cable length…(double insulated)
 610mm (24”) I6000s Flex-24
915mm (36”) I6000s Flex-36
Head Cable Diameter
 14.3 mm
Head Bend Radius
 38.1 mm
Cable length (head to electronics)
 2 meters
Output Connection
 0.5 m cable terminated with
safety BNC connector
Supplied with 4mm safety plug
adaptor
Operating Temperature Range
 -20 to +90 °C (head)
-20 to +85 °C (electronics)
Storage Temperature Range
 -40 to +105 °C (head)
-20 to +85 °C (electronics)
Operating Humidity
 15% to 85% (non condensing)
Weight
 180 g (head), 190 g (electronics)

Safety Standards
BS EN 61010
 1: 2001
BS EN 61010
 2-032: 2002
BS EN 61010
 031: 2002
600VRMS, Category III, Pollution Degree 2
 
Note
 Use of the probe on uninsulated conductors is limited to 600 V ACRMS or DC and frequencies below 1 kHz.
EMC Standards
BS EN 61326:  1998 +A1, A2, & A3