Get control of power problems
The Fluke 43 Power Quality Analyzer performs
the measurements you need to maintain power
systems, troubleshoot power problems and
diagnose equipment failures. All in a rugged
handheld package.
|
Fluke 43B Single Phase Power Quality Analyzer
5
5
1
1
Amazing Product and worth the money paid
Its robust features coupled with amazing accuracy makes it the best power quality analyzer available in the market
May 30, 2012
|
- NiMH Battery provides extended operating time of 6.5 hours
- Combines the most useful capabilities of a power quality analyzer, multimeter and scope
- Calculates 3-phase power on balanced loads, from a single-phase measurement
- Trends voltage, current, frequency, power harmonics and captures voltage sags, transients and inrush current
- Monitoring functions help track intermittent problems and power system performance
- Records two selectable parameters for up to 16 days
- 20 measurement memories to save/recall screens and data with cursor readings
- FlukeView® software can log harmonics and all other readings over time and provides a complete harmonics profile up to the 51st harmonic
- Measures resistance, diode voltage drop, continuity, and capacitance
- Users/applications manual and power quality video to help answer tough questions
- Complete package with voltage probes and 400 A current clamp, FlukeView Software and optically isolated interface cable
- 3 year warranty on the Fluke 43B, 1 year on accessories
|
Harmonics
- Voltage, current, and power harmonics
- Up to 51st harmonic
- Total harmonic distortion (THD)
- Phase angle of individual harmonics
|
Power
- Watts, power factor, displacement power factor (cos Θ), VA and VAR
- Voltage and current waveforms
|
Three phase
- On-screen graphics show you how to set up 3-phase power measurements
|
Sags and swells
- Measurements are always automatically recorded to instantly show changes over time
- Use cursors to read time and date of sags and swells
|
Transients
- Catch voltage transients and waveform distortion down to 40 nS
- Catch and save up to 40 transients
- Correlate the cause of transient with time and date stamps
|
Volts/Ampères/Hertz
- Voltage and current waveforms
- True RMS voltage and current
- Frequency
|
|
| Specifications |
| Input Characteristics |
| Input impedance
|
1 MΩ, 20 pF
|
| Voltage rating |
600V rms, CAT III |
| | V/A/Hz Display |
| True-rms voltage (ac + dc) |
|
| Ranges:
|
5.000 V, 50.00 V, 500.0 V, 1250 V*
|
| Accuracy: |
±(1% + 10 counts) |
|
|
| True-rms current (ac + dc) |
|
| Ranges:
|
50.00 A, 500.0 A, 5.000 kA, 50.00 kA, 1250 kA
|
| Accuracy: |
±(1% + 10 counts) |
|
|
| Frequency |
|
| Ranges:
|
10.0 to 15.0 kHz
|
| Accuracy: |
± ([% of reading] + [counts]): 0.5% + 2 |
|
|
| CF Crest factor |
|
| Ranges: |
1.0 - 10.0 |
| Accuracy: |
±(5% + 1 count) |
| | Power Display |
| Watts, VA, VAR
|
|
|
1-phase and 3-phase,3 conductor balanced loads |
| Ranges: |
250 W - 1.56 GW |
| Accuracy: |
±(4% + 4 counts) Fundamental Power
|
| Accuracy: |
± (2 % + 6 counts) Total Power |
|
|
| PF Power Factor
|
|
| Range: |
0 - 1.0 |
| Accuracy: |
±0.04 |
| DPF Displacement Power Factor, Cos .F |
|
| Range: |
0.25 - 0.9 |
| Accuracy: |
±0.04 |
| Range: |
0.90 - 1.0 |
| Accuracy: |
±0.03 |
|
|
| H2 Frequency Fundamental |
|
| Ranges: |
40.0 to 70.0 Hz |
| Accuracy: |
± ([% of reading] + [counts]): 0.5% + 2 |
| | Harmonics Display |
| Voltage, Current, Frequency |
|
| Ranges:
|
Fundamental to 51st harmonic
|
| Accuracy:
|
|
| Fundamental: |
VA ±(3% + 2 counts) W ±(5% + 2 counts) |
| 2 to 31st harmonic: |
VA ±(5% +3 counts) W ±(10% +10 counts) |
| 32 to 51st harmonic: |
VA ±(15% +5 counts) W ±(30% +5 counts) |
|
|
| Frequency Fundamental
|
|
| Ranges: |
40 Hz to 70 Hz |
| Accuracy: |
±0.25 Hz |
|
|
| Phase |
|
| Range:
|
V, A (between Fundamental & Harmonics)
|
| Accuracy:
|
±3º to ±15º
|
| Range: |
W (between Voltage Fundamental & Current Harmonics) |
| Accuracy: |
±5º to ±15º |
|
|
|
| K-factor (Current and Power)
|
|
| Range:
|
1.0 to 30.0
|
| Accuracy: |
±10% |
|
|
| THD Total Harmonic Distortion |
|
| Range: |
0.00 - 99.99 |
| Accuracy:
|
±(3% + 8 counts) |
| | Sags and Swells |
| Recording times:
|
4 min to 16 days (selectable)
|
| Vrms Actual, Vrms max, min(AC + DC)
|
|
| Ranges:
|
5.000V, 50.00V, 500.0V, 1250V*
|
| Accuracy: |
Readings ±(2% +10 counts); Cursor readings ± (2% + 12 counts) |
|
|
|
| Arms Actual, Arms max, min (AC + DC) |
|
| Ranges:
|
50.00A, 500.0A, 5.000 kA, 50.00 kA
|
| Accuracy:
|
±(2% +10 counts)
|
| | Transient Capture |
| Minimum pulse width:
|
40 ns
|
| Useful bandwidth input 1: |
DC to 1 MHz |
| Number of transients: |
40 |
| Voltage threshold settings:
|
20%, 50%, 100%, 200% above or below reference |
| Reference signal: |
After START, the Vrms and frequency of the signal are measured. From these data a pure sinewave is calculated as reference for threshold setting. |
| Vpeak min, Vpeak max at cursor: |
10 V, 25 V, 50 V, 125 V, 250 V, 500 V, 1250 V
Accuracy: ±5% of full scale |
| | R, C, Diode, Continuity |
| Resistance ranges:
|
500.0 Ω, 5.000 kΩ, 50.00 kΩ, 500.0 kΩ, 5.000 MΩ, 30.00 MΩ
|
| Resistance accuracy:
|
±(0.6% + 5 counts)
|
| Capacitance ranges: |
50.00 nF, 500.0 nF, 5.000 µF, 50.00 µF, 500.0 µF
|
| Capacitance accuracy:
|
±(2% + 10 counts) |
| Diode Ranges: |
0 to 3.000 V |
| Diode voltage:
|
|
| Accuracy: |
±(2% + 5 counts) |
| Continuity:
|
Beeper on at < 30 Ω ± 5 Ω
|
| Max current:
|
0.5 mA
|
| Temperature: |
°C or °F |
| | Inrush Current |
| Inrush times: |
1 s, 5 s, 10 s, 50 s, 100 s, 5 min |
| Current ranges:
|
1 A, 5 A, 10 A, 50 A, 100 A, 500 A, 1000 A |
| Cursor readings: |
A peak max at cursor 1 and cursor 2 |
| Accuracy: |
±5% of full scale
|
| Time between cursors: |
4 to 235 pixels (1 pixel = inrush time/250)
Accuracy: ±(0.2% + 2 pixels) |
| | Temperature (with accessory) |
| Range: |
-100 °C - 400 °C |
| Accuracy: |
±(0.5% + 5 counts) |
| | Scope Display |
| Measurements: |
dc, ac, ac+dc, peak, peak-peak, frequency, duty cycle, phase, pulse width, crest factor |
| Time ranges:
|
20 ns/div to 60 s/div
|
| Max sampling rate: |
25 MS/s
|
| Bandwidth
|
|
| Voltage channel [1]: |
20 MHz at inputs, 1 MHz with TL24 Leads
|
| Current channel [2]: |
DC to 15 kHz at inputs, 10 kHz with i400s Current Clamp
|
| Coupling:
|
AC, DC (10 Hz - 3 dB)
|
| Vertical sensitivity: |
5 mV/div to 500V/div |
| Vertical resolution:
|
8 bit (256 levels) |
| Record length:
|
512 samples per channel |
| Base ranges: |
60 S/div to 20 nS/div ± (0.4% + 1 pixel) |
| Timebase modes: |
Normal, roll, single |
| Pre-trigger:
|
Up to 10 divisions |
| Trigger Source: |
Input 1 or Input 2 or automatic selection |
| Trigger Mode: |
Automatic Connect-and-View™, Free Run, and Single Shot |
|
|
| Connect-and-View™: |
Advanced automatic triggering that recognizes signal patterns |
|
Automatically adjusts triggering, timebase and amplitude and displays stable pictures |
| | Memories |
|
20 (screens, settings, data) |
| | Recording |
| Recording times: |
4 min to 16 days (selectable) |
| Parameters: |
Choose one or two parameters from one of the groups below: |
|
Volts/Ampères/Hertz |
| Power: |
Watts, VA, VAR, PF, DPF, Frequency |
|
Harmonics, THD, Volts (Fund. & Harmonic), Ampères (F&H) Watts(F&H) |
|
Frequency (H), %(H) of total, Phase(H), KF |
|
Temperature |
| Resistance: |
Resistance, Diode, Continuity, Capacitance |
| Scope: |
DC Voltage, DC Current, AC Voltage, AC Current, Frequency, |
|
Pulse Width + or -, Phase, Duty cycle + or -, Peak max, Peak min, Peak min-max, Crest Factor |
| | Note |
|
*Rated EN 61010-1 600 V CAT III CSA
|
|
| Environmental Specifications |
| Operating Temperature | |
| Safety Specifications |
| Electrical Safety |
|
EN 61010-1 CAT III, 600V. CSA listed |
|
| Mechanical & General Specifications |
| Size | | | Weight | | | Warranty | | | Battery Life |
|
Rechargeable NiMH pack (charger included), 6.5 hrs extended operating time (continuous) |
| | Shock & Vibration |
|
Mil 28800E, Type 3, Class III, Style B |
| | Case |
|
IP51 (dust, drip, waterproof) |
|
|
| Model Name | Description | Price List | Buy it | | Fluke 43B |
Fluke 43B includes:
- C120 Hard Case
- TP1 Flat-tipped Slim-Reach™ Test Probes
- TP4 4 mm Round Slim-Reach™ Test Probes
- i400s AC Current Clamp
- OC4USB Optically Isolated USB Interface Adapter
- BP120MH Rechargeable NiMH Battery Pack (installed)
- PM 8907 Line Voltage Adapter/Battery Charger
- SW43W FlukeView™ Power Quality Analyzer Software and Users Manual on CD-ROM
- Shielded Banana-to-BNC Adapter
- Users Manual / Application Guide
|
|  | |
| CarePlans | Buy it | | G3P-Group3 |
- GOLD CarePlan.
- Models covered: 43B/003, 123/003, 124/003, 125/003, and 1555.
- Extends warranty from three to five years and includes five annual NIST traceable calibrations with data.
| |  | | S3P-Group3 |
- SILVER CarePlan.
- Models covered: 43B/003, 123/003, 124/003, 125/003, and 1555.
- Extends warranty from three to five years.
|  |  |
| Clips | Buy it | | AC220 | AC220 SureGrip™ Alligator Clips |  |  | | AC285 | AC285 SureGrip™ Alligator Clips |  |  | | TLK225 | TLK-225 SureGrip™ Master Accessory Set |  |  |
| Test Probes | Buy it | | TP220 | TP220 SureGrip™ Industrial Test Probes |  |  | | TP74 | TP74 Lantern Tip Test Probes |  |  |
| Cables and Hardware | Buy it | | PAC91 | PAC 91 Printer Adapter Cable |  |  |
| Cases and Holsters | Buy it | | C125 | C125 Meter Case
|  | | | C43 | C43 Soft Carrying Case |  |  | | C550 | C550 Tool Bag |  |  |
| Current Clamps | Buy it | | 80i-110s | 80i-110s AC/DC Current Clamp |  |  | | i3000 Flex-4PK | Fluke i3000 Flex AC Current Clamp, 4 Pack |  |  | | i1000s | i1000s AC Current Probe |  |  | | i2000 flex | i2000 flex AC Current Clamp |  |  | | i200s | i200s AC Current Clamp |  |  | | i3000s | i3000s AC Current Clamp |  |  | | i3000s Flex-24 | i3000s Flex-24 AC Current Clamp, 610 mm (24 in.) |  |  | | i3000s Flex-36 | i3000s Flex-36 AC Current Clamp, 915 mm (36 in.) |  |  | | i400s | i400s AC Current Clamp |  |  | | i6000sFlex | i6000sFlex AC Current Probe | |  |
| Lights | Buy it | | L210 | L210 Probe Light Kit |  |  |
| Options | Buy it | | BB120 | BB120 Shielded Banana to Female BNC Adapter |  |  |
| Temperature | Buy it | | 80T-150UA | 80T-150UA Universal Temperature Probe |  |  | | 80TK | 80TK Thermocouple Module |  |  |
| Test Leads | Buy it | | TL220 | TL220 SureGrip™ Industrial Test Lead Set |  |  | | TL221 | TL221 SureGrip™ Test Lead Extension Set |  |  | | TL223 | TL223 SureGrip™ Electrical Test Lead Set |  |  | | TL224 | TL224 SureGrip™ Insulated Test Leads |  |  | | TL238 | TL238 SureGrip™ Test Lead Set for High Energy Environments |  |  | | TL27 | TL27 Heavy Duty Test Lead Set |  |  | | TL71 | TL71 Premium Test Lead Set |  |  |
|
|
|
|
|
|
|
|
|
|
|
|
| | |