Every measurement, every event, on every cycle, all the time – without thresholds
From set-up to finished reports, the RPM Power Recorder is the complete solution to your portable power monitoring needs. The Power Recorder analyzer is all you need to monitor, study and document:
- Loading and load interaction
- Power consumption and demand
- Sags, swells or transient events
- Ground currents
- Phase relationships, including phase imbalance
- Frequency stability
- Harmonics and noise
|
The Power Recorder features:
- 4 voltage channels – three phases plus neutral-to-ground. Measures up to 600 Vrms, 1000 Vpeak.
- 5 current channels allow you to monitor neutral and ground current, in addition to phases
- Extruded metal enclosure, and designed to handle a life-time of use
- Ethernet interface makes downloads fast and easy
- Capture up to 6,000 simultaneous voltage events with simultaneous current in each monitoring session
- Multi-session option allows for 16 sessions, effectively multiplying event capture capability to 96,000 events
- 128 samples per cycle — on every cycle
- Supports single-phase, wye, delta, split phase, high-leg delta, open-leg delta, and other common power systems
- Power Consumption option adds Watts, VA, VAR, PF trends and measurements
- Harmonics option measures harmonics up to 63rd
- Optional 2 MS/s sampling system for capturing and viewing high-speed transients
- Nylon and hard-sided cases, mounting brackets, a wide variety of voltage and
current probes are available
|
Find out about Full Disclosure Technology for the Reliable Power Meters Power Recorder
|
| Measurement Features |
| All Power Recorders
|
| • |
Logging RMS voltage and RMS current on all channels |
| • |
Phasor diagrams |
| • |
Frequency trends |
| • |
Real-time oscilloscope display of voltage and current on all channels |
| | 1652 Power Consumption Option |
| • |
Watts and demand trends |
| • |
KWH, individual phases and total |
| • |
VA and VAR trends |
| • |
Power Factors trends, true and displacement |
| • |
Oscilloscope display of power meters for each phase |
| | 1653 Harmonics Option |
| • |
Voltage and current THD trends |
| • |
Voltage and current imbalance |
| • |
Harmonic spectrum, phase, magnitude to 63rd harmonic |
| • |
Tracking of individual harmonics |
| | 1651 Power Quality Option |
| • |
Voltage waveshape faults as short as 130 µs duration, 1000 V peak |
| • |
Voltage sags/swells |
| • |
Simulations current corresponding to correlated with voltage events |
| • |
Power tolerance curves |
| | 1658 High Speed Power Quality Option |
| • |
Voltage and current waveshape faults |
| • |
Voltage and current sags/swells |
| • |
Power tolerance curves |
| • |
Transients as short as 500 ns duration, 6400 V peak; with peak detect or detailed waveform graphs |
| | 1662 Multi-Session Option |
| • |
Allows a recorder to store up to 16 measurement sessions |
| • |
Each session can consist of up to 6000 events, increasing the event storage to 96,000 |
| | 1663 TCP/IP Option |
| • |
Enables Ethernet-equipped instruments to communicate via Internet |
|
Real-time waveform displays up to 9 channels
- Displays up to 9 channels (4 voltage, 5 current)
- Includes ground and neutral current
|
Real-time voltage and current meters
- Feature phasor diagrams to help with correct hookup
|
Trend Windows
- Give overview of power parameters - fast
- Measurements preocessed for every cycle
- Min, max and average values are plotted so you can see the worst-case
|
Real-time meter and vector diagram
- Available with 1652 option
- Displays Watts, VA, VAR, PF and dPF
|
Track demand using averaging intervals
- Available with 1652 option
- Demand tracking using averaging intervals from 5 minutes to 1 hour
|
Display harmonics up to the 63rd
- Available with 1653 option
- Display harmonics up to the 63rd as a spectrum table
|
Capture and view transients as short as 500 ns
- Available with 1658 option
|
|
|
| Technical Data: number of channels: 9 (4 voltage, 5 current) |
| Voltage (phases) |
| • |
Range: 100mV – 600 Vms |
| • |
Resolution: 14 bits, 90 millivolts |
| • |
Accuracy +/- (% of reading + floor): +/- (1.5% +0.5V) over entire range |
| | Voltage (neutral) |
| • |
Range: 10 mV-70 Vms |
| • |
Resolution: 100 V peak |
| • |
Accuracy +/- (% of reading + floor): 14 bits, 90 millivolts |
| | Current |
| • |
Range: Depends upon CT |
| • |
Resolution: 14 bits |
| • |
Accuracy +/- (% of reading + floor): +/- (0.5% + 0.1% of probe range + probe uncertainty) |
| | Nominal Fundamental Frequency |
| • |
Range: 50/60 Hz +/-0.1 Hz |
| | Voltage and current sampling |
| • |
128 samples per cycle on 50/60 Hz |
| | Voltage and current sampling rate |
| • |
6.4 / 7.7 kS/s depending upon line frequency |
| | Voltage and current rms measurements |
| • |
Processed for every full cycle |
| | Waveform fault measurements (1941 & 1942)
Sampling rate |
| • |
Range: 6.4 / 7.7 kS/s depending upon line frequency |
| | Impulse Measurements (standard speed unit with option 1651):
Sampling Rate
Impulse Voltage
|
| • |
Range: 6.4 / 7.7 kS/s depending upon line frequency |
| • |
Range: 200 – 1000 V peak |
| • |
Resolution: 10 bits, 12 volts |
| • |
Accuracy +/- (% of reading + floor): +/- (5% + 36 V) over entire range |
| | Impulse Measurements (high-speed unit):
Sampling Rate
Impulse Voltage
|
| • |
Range: 2 MHz |
| • |
Range: 100 – 6400 V peak |
| • |
Resolution: 10 bits, 12 volts |
| • |
Accuracy +/- (% of reading + floor): +/- (5% + 36V) over entire range |
|
| General Specifications |
| Event memory |
| • |
6,000 simultaneous voltage and current events (96,000 with option 166Z) |
| | Communication |
| • |
10-base T Ethernet, RJ 45 Connector, optional TC/PIP stack enables communication via Internet |
| | Electrical |
| • |
Safety: 600 V CAT III |
| • |
Operating Voltages: 85 - 264 V AC, 47 – 440 Hz |
| • |
Power consumption: 40 watts |
| • |
Batteries: NiCd battery recharges automatically while line power is applied. Power the instrument for 5 minutes after power is removed and allows controlled shutdown of monitor. Monitoring resumes after power is restored. |
| | Mechanical |
| • |
Available Enclosures: Standard enclosure, hostile environment enclosure |
| • |
Size: 21.25 cm x 30 cm x 7.5 cm (8.5” x 12” x 3”) |
| • |
Weight: 6 Kg (13 lbs.) |
| • |
Operating Temperature: 0° – 50° C (32° - 122° F), 90% RH non-condensing |
| | Standards | | | Warranty | |
|
|
| Available Models |
| 1650 – 56 |
| • |
Standard enclosure |
| • |
Ethernet computer interface |
| • |
High-speed sampling system |
| • |
PQ measurements included |
| • |
Harmonics option |
| • |
Power consumption option |
| • |
Impulse waveform option |
| • |
Multi-session software option |
| • |
TCP/IP Stack option |
| | 1650 – 50 |
| • |
Standard enclosure |
| • |
Ethernet computer interface |
| • |
Standard sampling system |
| • |
PQ measurement option |
| • |
Harmonics option |
| • |
Power consumption option |
| • |
Multi-session software option
|
| • |
TCP/IP Stack option |
| | 1650 – 15 |
| • |
Hostile enclosure |
| • |
Ethernet computer interface |
| • |
High-speed sampling system |
| • |
PQ measurements included |
| • |
Harmonics option |
| • |
Power consumption option |
| • |
Impulse waveform option |
| • |
Multi-session software option
|
| • |
TCP/IP Stack option |
| | 1650 – 51 |
| • |
Hostile enclosure |
| • |
Ethernet computer interface |
| • |
Standard sampling system |
| • |
PQ measurement option |
| • |
Harmonics option |
| • |
Power consumption option |
| • |
Multi-session software option |
| • |
TCP/IP Stack option |
| | 1650 – 10 |
| • |
Hostile enclosure |
| • |
Parallel computer interface |
| • |
High speed sampling system |
| • |
PQ measurement option |
| • |
Harmonics option |
| • |
Power consumption option |
| • |
Impulse waveform |
| • |
Multi-session software option |
| | 1650 – 11 |
| • |
Hostile enclosure |
| • |
Parallel computer interface |
| • |
High speed sampling system |
| • |
PQ measurement option |
| • |
Harmonics option |
| • |
Power consumption option |
| • |
Multi-session software option |
|
| Included Accessories |
| All Units Include |
| • |
User manual |
| • |
Line cord |
| • |
5 voltage leads |
| • |
5 alligator clips |
| | Units with Ethernet Interface Include |
| • |
10 ft. Ethernet cable |
| • |
Socket-socket adapter |
| • |
2 ft. cross-over cable |
| | Units with Parallel Interface Include | |
|
|
|
|
|
|
|
|
|