High-Speed Capability for Permanent Installation
Designed for permanent installations, Multipoint performs just like the
portable Power Recorder simultaneously measuring all power quality
parameters, as well as power consumption and harmonics. The system consists
of a detachable acquisition unit and a base that manages connections to your
power system.
Full Disclosure Technology is included with Multipoint, making it a unique, professional tool that increases your ability to maintain and troubleshoot your plant’s power quality.
Read more about Full Disclosure technology in the Multipoint Power Recorder® datasheet.
|
|
Multipoint features:
- 2 MS/s sampling system for capturing and viewing high-speed events as fast as 500 ns
- 4 voltage channels – three phases plus neutral-to-ground. Measure up to 600 Vrms, 1000 Vpeak
- 5 current channels allow you to monitor neutral and ground current in addition to phases designed to connect to industry-standard 5-amp CT’s. Also available with connections for clamp-on CT’s
- Measurement system docks with a permanently-mounted base, allowing calibration or service without having to shut down power
- Capture up to 6,000 simultaneous voltage events with simultaneous current, in each monitoring session
- Multi-session option allows for 16 sessions, effectively multiplying event capture capability to 96,000 events
- 128 samples per cycle -- on every cycle at 50 or 60 Hz
|
| Measurement Features |
| Basic functions |
| • |
Logging RMS voltage and RMS current on all channels |
| • |
Phasor diagrams |
| • |
Frequency trends |
| • |
Real-time oscilloscope display of voltage and current on all channels |
| | 1652 Power consumption (included) |
| • |
Watts and demand trends |
| • |
KWH, individual phases and total |
| • |
VA and VAR trends |
| • |
Power Factors trends, true and displacement |
| • |
Oscilloscope display of power meters for each phase |
| | 1653 Harmonics (included) |
| • |
Voltage and current THD trends |
| • |
Voltage and current unbalance |
| • |
Harmonic spectrum, phase, magnitude to 63rd harmonic |
| • |
Tracking of individual harmonics |
| | 1651 Power Quality (included) |
| • |
Voltage waveshape faults as short as 130 µs duration, 1000 V peak |
| • |
Voltage sags/swells |
| • |
Simulations current corresponding to correlated with voltage events |
| • |
Power tolerance curves |
| | 1658 High Speed Power
Quality (included in 1948 and 1949) |
| • |
Voltage and current waveshape faults |
| • |
Voltage and current sags/swells |
| • |
Power tolerance curves |
| • |
Transients as short as 500 ns duration, 6400 V peak; with peak detect or detailed waveform graphs |
| | 1956 External CT (included in 1942 and 1949) |
| • |
Allows use of external RPM current transformers |
|
| Multipoint Options |
| 1662 Multi-session option |
| • |
Allows a recorder to store up to 16 measurement sessions |
| • |
Each session can consist of up to 6000 events, increasing the event storage to 96,000 |
| | 1663 TCP/IP option |
| • |
Enables Ethernet-equipped instruments to communicate via Internet |
|
Real time waveform
- Shows up to 9 channels (4 voltage, 5 current)
- Includes ground and neutral current
|
Trend Windows
- Provides an overview of power parameters-fast
- Measurements are processed for every cycle
- Min, max and average values are plotted so you can quickly see the worst case
|
Real-time meters and vector diagrams
- Display watts, VA, VAR, power factor and displacement power factor
|
Track demand using averaging intervals
- Use averaging intervals from 5 minutes to 1 hour
|
Display harmonics up to the 63rd
- Display harmonics up to the 63rd as a spectrum or a table
|
|
|
| Technical Data: number of channels: 9 (4 voltage, 5 current) |
| Voltage (phases) |
| • |
Range: 100mV – 600 Vms, 1000 V peak |
| • |
Resolution: 14 bits, 90 millivolts |
| • |
Accuracy +/- (% of reading + floor): +/- (1.5% +0.5V) |
| | Voltage (neutral) |
| • |
Range: 10 mV-70 Vms, 100 V peak |
| • |
Resolution: 14 bits, 90 millivolts |
| • |
Accuracy +/- (% of reading + floor): (1.5% +0.5V) |
| | External current (1942 & 1949) |
| • |
Range: Depends upon CT |
| • |
Resolution: 14 bits |
| • |
Accuracy +/- (% of reading + floor): +/- (0.5% + 0.1% of probe range + probe accuracy) |
| | Internal current (1941 & 1948) |
| • |
Range: 20 A maximum |
| • |
Resolution: 14 bits |
| • |
Accuracy +/- (% of reading + floor): +/-(1% + 0.04 A) |
| | Nominal fundamental frequency |
| • |
Range: 50/60 Hz +/- 0.1 Hz |
| | Voltage and current sampling |
| • |
128 samples per cycle on 50/60 Hz |
| | Voltage and current sampling rate |
| • |
6.4 / 7.7 kS/s depending upon line frequency |
| | Voltage and current rms measurements |
| • |
Processed for every full cycle |
| | Power measurements |
| • |
W, VA, VAR, PF, dPF, THD, harmonics processed for every full cycle |
| | Waveform fault measurements (1941 & 1942)
Sampling rate
Impulse voltage |
| • |
Range: 6.4 / 7.7 kS/s depending upon line frequency |
| • |
Range: 100 – 1000 V peak |
| • |
Resolution: 10 bits, 12 volts |
| • |
Accuracy +/- (% of reading + floor): +/- (5% + 36 V) over entire range |
| | Impulse measurements (1948 & 1949)
Sampling rate
Impulse voltage |
| • |
Range: 2 MHz |
| • |
Range: 100 – 6400 V peak |
| • |
Resolution: 10 bits, 12 volts |
| • |
Accuracy +/- (% of reading + floor): +/- (5% +36V) over entire range |
|
| General Specifications |
| Event memory |
| • |
6,000 simultaneous voltage and current events (96,000 with option 166Z)
Multi-session increases storage to 96,000
|
| | Communication |
| • |
10-base T Ethernet, RJ 45 Connector, Optional TC/PIP Stack enables communication via Internet |
| | Electrical |
| • |
Operating Voltages: 85 - 264 V AC, 47 – 440 Hz |
| • |
Power Consumption: 40 Watts |
| • |
Batteries: Rechargeable NiCd battery maintains operation after power loss for 5 minutes, allowing the monitor to record outage, reclosure attempts, and to resume monitoring upon restoration of power. Real time clock is backed up using a lithium battery with 10-year life |
| | Mechanical |
| • |
Size: 31.47 cm x 29.36 cm x 15.24 (cm12.39” x 11.56” x 6”) |
| • |
Weight: 6 Kg (9 lbs.) |
| • |
Operating Temperature: 0° – 50° C (32° - 122° F), 90% RH non-condensing |
| | Standards | | | Warranty | |
|
|
| Available Models |
| 1941 |
| • |
Standard sampling system |
| • |
5-A fixed current transformer type |
| • |
PQ Measurements included |
| • |
Power Consumption included |
| • |
Harmonics included |
| • |
Multi-Session Software option |
| • |
TCP/IP Stack option |
| | 1942 |
| • |
High-speed sampling system |
| • |
External clamp-on current transformer type |
| • |
PQ Measurements included |
| • |
Power Consumption included |
| • |
Harmonics included |
| • |
Multi-Session Software option |
| • |
TCP/IP stack option |
| | 1948 |
| • |
Standard sampling system |
| • |
External clamp-on transformer type |
| • |
PQ Measurements included |
| • |
Power Consumption included |
| • |
Harmonics included |
| • |
Impulse Waveform option |
| • |
Multi-Session Software option |
| • |
TCP/IP Stack option |
| | 1949 |
| • |
High-speed sampling system |
| • |
External clamp-on current transformer type |
| • |
PQ Measurements included |
| • |
Power Consumption included |
| • |
Harmonics included |
| • |
Impulse Waveform included |
| • |
Multi-Session Software option |
| • |
TCP/IP Stack option |
|
| Included Accessories |
| All units include | |
| Accessories |
| 1230 | | | 5000/RPM |
| • |
Power Analysis Software with User Manual |
| | 5100/RPM |
| • |
Professional Report Writer Software (requires 5000/RPM) |
| | 5400/RPM |
| • |
Scenario Analysis Software |
| | 5500/RPM |
| • |
Master Polling and Annunciation Software (requires 5000/RPM) |
| | 5502/RPM |
| • |
Sub-polling and Annunciation Software (requires 5000/RPM and 5500/RPM) |
|
| Accessories for Multipoint models with external CT Option |
| 3014R | | | 3100R | | | 3110/RPM |
| • |
24-inch 100 amp Flexi-Ct (tm) |
| | 3112/RPM |
| • |
48-inch 100 amp Flexi-Ct |
| | 3120R | | | 3210/RPM |
| • |
24-inch 1000 amp Flexi-Ct |
| | 3212/RPM |
| • |
48-inch 1000 amp Flexi-Ct |
| | 3300R | | | 3310/RPM |
| • |
24-inch 5000 amp Flexi-Ct |
| | 3312/RPM |
| • |
48-inch 5000 amp Flexi-Ct |
|
|
|
|
|
|
|
|
|
|