Pinpoint power quality problems faster, safer and in greater detail
The Fluke 434 and 433 three-phase power quality analyzers help you locate, predict, prevent and troubleshoot problems in power distribution systems. These easy-to-use handheld tools have many innovative features to give you the details to pinpoint problems faster and safer.
|
- Complete three-phase troubleshooting tool: measures virtually every power system parameter : voltage, current, frequency, power, power consumption (energy), unbalance and flicker, harmonics and inter-harmonics. Captures events like dips and swells, transients, interruptions and rapid voltage changes.
- AutoTrend: no time wasted setting up additional trend graphs while every measurement is automatically recorded. Analyzes trends using cursors and zoom function, while recording continues in the background.
- System-Monitor: gives immediate insight into power system’s quality. Checks conformity to limits specified in EN50160 or to own custom limits.
- Four channels: simultaneously measures voltage and current on all three phases and neutral.
- Automatic transient display: captures up to 40 dips, swells, interruptions or transients automatically.
- Meets the stringent 600 V CAT IV, 1000 V CAT III safety standard required for measurements at the service entrance.
- Rugged, handheld instrument operates for more than 7 hours on included rechargeable NiMH battery pack. Menu-driven interface simplifies operation.
- Extensive data analysis possibilities. Cursors and zoom can be used ‘live’ while taking the measurements, or ‘offline’ on stored measurement data. The stored measurements can also be transferred to a PC with FlukeView software (included with Fluke 434).
- Complete package includes everything to get started: 4 current clamps, 5 voltages test leads and clips, line adapter/battery charger and hard case.
- Complies with IEC 61000-4-30 measurement standards.
|
AutoTrend - Quickly see the trend
AutoTrend automatically records all displayed parameters in the background
Toggle between data and trend view and use cursors and zoom to analyze measurements without interrupting the recording
Unique AutoTrend gives you fast insight into changes over time. Every displayed reading is automatically and continuously recorded without having to set up threshold levels or interval times, or having to manually start the process. You can quickly view trends in voltage, current, frequency, power, harmonics or flicker on all three phases plus neutral. And you can analyze the trends using the cursors and zoom function – even while background recording continues.
SystemMonitor - Check performance against EN50160 with ease
The System-Monitor overview screen gives instant insight into whether the voltage, harmonics, flicker, frequency and the number of dips and swells fall outside the set limits
With a single push of a button, the unique System-Monitor gives you an overview of power system performance, and checks the compliance of incoming power to EN50160 limits or to your own custom specifications. The overview is shown on a single screen, with color-coded bars clearly indicating which parameters fall outside the limits. A list of each event falling outside these limits is generated.
A detailed list is given of all events falling outside the set limits
Automatic transient display
Every time an event or distortion on the voltage waveform is detected, the instrument triggers and automatically stores voltage and current waveforms on all three phases and neutral. The instrument can also trigger when a certain current value level is exceeded. Up to 100 dips, swells, interruptions and transients can be captured in this way. You can see voltage transients as high as 6 kV and as fast as 5 microseconds.
Extensive data analysis possibilities
The Fluke 430 series provides three ways to analyze the measurements. Cursors and zoom can be used ‘live’ while taking the measurements, or ‘offline’ on stored measurement data. The stored measurements can also be transferred to a PC with FlukeView. This software’s "view” mode allows cursors and zoom to be used on stored measurements as if actually working with the instrument. To perform custom analysis and to create reports, measurement data can be exported to common spreadsheet programs. The instrument can store up 10 measurements, where each measurement can contain up to 32 parameters recorded for more than a year, and up to 50 screens
600 V CAT IV safety rating
Designed to help protect you and your equipment against electrical shock and fire, the Fluke 430 Series analyzers, accessories and charger are all certified to meet the stringent safety standards for use in 600 V CAT IV and 1000 V CAT III environments. They are the first tools of their kind to carry the CAT IV rating and can therefore be used at virtually all power connections and outlets in low-voltage power distribution systems
One tool to do the job
The full color display uses industry-standard color-coding (user selectable) to correlate measurements with actual wiring
Simple menu structure with logical function grouping gives fast access to key measurements
Scope view shows voltage and current waveforms for all three phases. You can toggle to a phasor diagram at any time
Phasor diagram shows voltage and current unbalance, and helps verify connections
Record dips and swells as short as one half-cycle with min/max/avg readings
Track harmonics up to the 50th, and measure and record THD in accordance with IEC61000-4-7 requirements
Measure and record power (W), VA, and VARs. The 434 adds the ability to record energy consumption
Inrush function captures starting current on motors and other devices to help determine trip levels
|
| Technical Data |
| Inputs |
| Number: |
4 voltage and current (3 phases + neutral) |
| Maximum voltage: |
1000 Vrms (6 kV peak) |
| Maximum sampling speed: |
200 kS/s on each channel simultaneously |
| | Volt/Amps/Hertz |
| Vrms (AC + DC) |
|
| Measurement range: |
1 ... 1000 V |
| Accuracy: |
0.5% of Vnom |
|
|
| Vpeak |
|
| Measurement range: |
1 ... 1400 V |
| Accuracy: |
5% of Vnom |
|
|
| Crest factor |
|
| Measurement range: |
1.0 ... > 2.8 |
| Accuracy: |
±5% |
|
|
| Arms (AC + DC) |
|
| Measurement range: |
0 ... 20 kA |
| Accuracy: |
±1% ± 5 counts |
|
|
| Apeak |
|
| Measurement range: |
0 ... 5.5 kA |
| Accuracy: |
5% |
|
|
| Crest factor |
|
| Measurement range: |
1 ... 10 |
| Accuracy: |
±5% |
|
|
| Hz (50 Hz nominal) |
|
| Measurement range: |
42.50 ... 57.50 Hz |
| Accuracy: |
±1% ± 5 counts |
| | Dips and swells |
| Vrms (AC+DC) ³ |
|
| Measurement range: |
0.0% … 100% of Vnom |
| Accuracy: |
±1% of Vnom |
|
|
| Arms (AC+DC) ³ |
|
| Measurement range: |
0 ... 20 kA |
| Accuracy: |
±1% ± 5 counts |
| | Harmonics |
| Harmonic (interharmonic) (n) |
|
| Measurement range: |
DC, 1..50; (Off, 1..49) measured relative to fundamental or to total rms |
|
|
| Vrms |
|
| Measurement range: |
0.0 … 1000 V |
| Accuracy: |
±5% ± 2 counts |
|
|
| Arms |
|
| Measurement range: |
0.0 … 4000 mV x clamp scaling |
| Accuracy: |
±5% ± 5 counts |
|
|
| Watts |
|
| Measurement range: |
Depends on clamp scaling |
| Accuracy: |
±5% ± n x 2% or reading, ± 10 counts |
|
|
| DC voltage |
|
| Measurement range: |
0.0 … 1000 V |
| Accuracy: |
±5% ± 10 counts |
|
|
| THD |
|
| Measurement range: |
0.0 … 100.0% |
| Accuracy: |
±2.5% |
|
|
| Hz |
|
| Measurement range: |
0 … 3500 Hz |
| Accuracy: |
± 1 Hz |
|
|
| Phase angle |
|
| Measurement range: |
-360º ... +360º |
| Accuracy: |
± n × 1.5º |
| | Power and energy |
| Watt, VA, VAR |
|
| Measurement range: |
1.0 … 20.00 MVA¹ |
| Accuracy: |
±1.5% ± 10 counts |
|
|
| kWh, kVAh, kVARh |
|
| Measurement range: |
00.00 …200.0 GVAh¹ |
| Accuracy: |
± 1.5% ± 10 counts |
|
|
| Power Factor/ Cos Ф / DPF |
|
| Measurement range: |
0…1 |
| Accuracy: |
± 0.03 |
| | Flicker |
| Pst (1 min), Pst, Plt, PF5 |
|
| Measurement range: |
0.00 … 20.00 |
| Accuracy: |
±5% |
| | Unbalance |
| Volts |
|
| Measurement range: |
0.0 … 5.0% |
| Accuracy: |
±0.5% |
|
|
| Current |
|
| Measurement range: |
0.0 … 20% |
| Accuracy: |
± 1% |
| | Transient Capture |
| Volts |
|
| Measurement range: |
±6000 V |
| Accuracy: |
±2.5% of Vrms |
| Minimum detect duration |
5 µs (200kS/s sampling) |
| | Inrush mode |
| Arms (AC+DC) |
|
| Measurement range: |
0.000 … 20.00 kA¹ |
| Accuracy: |
±1% of meas ± 5 counts |
| | Autotrend recording |
| Sampling: |
Up to 100 readings/s continuous sampling per channel |
| Memory: |
Up to 3600 min, max and avg points for each reading |
| Recording time: |
Up to 450 days |
| Zoom: |
Up to 12x horizontal zoom |
| | Memory |
| Screens: |
Fluke 434 - 50; Fluke 433 - 25 |
| Data sets including recordings: |
Fluke 434 - 10; Fluke 433 - 5 |
| | Notes |
| ¹ |
Depending on clamp scaling |
| ² |
50 Hz/60 Hz nominal frequency according to IEC 61000-4-30 |
| ³ |
Value is measured over 1 cycle, commencing at a fundamental zero crossing, and refreshed each half-cycle
|
|
| Environmental Specifications |
| Operating Temperature | | | Storage Temperature | | | Operating Altitude | |
| Safety Specifications |
| Compliance |
|
IEC/EN61010-1 (2nd edition) pollution degree 2; |
|
CAN/CSA C22.2 No 101.1 |
|
ANSI/ISA S82.01 |
|
| Mechanical & General Specifications |
| Size | | | Weight | | | Warranty | | | Battery Life |
| Rechargeable NiMH pack: |
>7 hours |
| Charging time: |
4 hours typical |
| | Shock & Vibration | | | Case |
|
IP51 (dust, drip, waterproof) |
|
|
| Model Name | Description | Price List | Buy it | | Fluke 433 |
Power Quality Analyzer
- C430 Hard carrying case with clamp holders
- i400s current clamps (4x)
- TLS430 Test leads and alligator clips (4 black, 1 green)
- BP190 NiMH Battery pack (installed)
- BC430 Battery charger/line voltage adapter
- WC100 Color localization set
- Getting Started (printed)
- User Manual (CD-ROM)
|
|  | |
| Batteries, Chargers and Adapters | Buy it | | BC430 | BC430 Line Voltage Adapter/Battery Charger |  |  |
| Cables and Hardware | Buy it | | OC4USB | OC4USB USB interface cable |  |  | | PAC91 | PAC 91 Printer Adapter Cable |  |  |
| Current Clamps | Buy it | | i1000s | i1000s AC Current Probe |  |  | | i2000 flex | i2000 flex AC Current Clamp |  |  | | i200s | i200s AC Current Clamp |  |  | | i3000s | i3000s AC Current Clamp |  |  | | i400s | i400s AC Current Clamp |  |  | | i5sPQ3 | i5sPQ3, 5 A ac Current Clamps, 3-pack |  |  |
| Test Leads | Buy it | | TLS430 | Fluke TLS430 – Test Leads and Alligator Clips (4 black, 1 green) |  |  | | WC100 | WC100 Color Localization Set |  |  |
|
|
|
|
|
|
|
|
|