One Tool. Get More Done.
The Fluke 975 AirMeter test tool raises indoor air monitoring to the next level by combining five powerful tools in one, rugged and easy-to-use handheld device. Use the Fluke 975 to optimize HVAC ventilation settings for ASHRAE 62 recommendations, actively monitor conditions that promote a productive environment, and quickly and accurately address occupant comfort complaints the first time. The Fluke 975 measures:
- Temperature
- Velocity
- Humidity
- CO2
- CO
|
Use the Fluke 975 AirMeter test tool to:
- Respond to comfort-related calls from occupants.
- Verify the operation of building HVAC control systems.
- Determine whether adequate ventilation exists.
- Monitor air flow and velocity.
- Test for dangerous carbon monoxide leaks.
- Perform duct traversals.
- Optimize HVAC systems to manage energy costs
|
|
Fluke 975 AirMeter™
4
5
1
1
good product
the only hatch is, not compatible with os x. quick and detailed info
May 30, 2012
|
 |
The Fluke 975 offers an unparalleled featureset for HVAC and facilities technicians, helping them work more quickly and accurately, with the ease of use and durability customers expect from a Fluke meter.
|
- Simultaneously measures, logs, and displays temperature, humidity, CO2, and CO on a bright, backlit LCD display
- One-touch air flow and velocity with available probe*
- Wet bulb and dew point temperature
- % of outside air calculation
- CO2 and CO field calibration feature
- Self-test function at startup
- Auto-backlight
- Automatically compensates for barometric pressure changes
- Min/Max/Average on all measured and calculated readings
- Multi-language user interface
- Metric or standard units
- Audible and visual threshold alarms
- Extensive discrete or continuous data logging capacity, downloadable to PC via USB interface
- Keypad lock for security
- Included FlukeView Forms® software
|
*Included with Fluke 975V, optional with Fluke 975
|
| Measured specifications |
| Temperature |
| Range: |
-20 °C to 50 °C (-5 °F to 122 °F) |
| Display resolution: |
0.1 °C (0.1 °F) |
| Accuracy: |
± 0.9 °C/± 1.62°F from 40 °C to 60 °C
± 0.5 °C/± 1.00°F from 5 °C to 40 °C
± 1.1 °C/± 1.98 °F from -20 °C to 5 °C |
|
| Relative humidity |
| Range: |
10 % to 90 % RH, non-condensing |
| Display Resolution: |
1% |
| Accuracy: |
± 2 % RH (10 % RH to 90 % RH) |
|
| Air velocity |
| Range: |
50.0 fpm to 3000 fpm
0.25 m/sec to 15 m/sec |
| Display Resolution: |
1 fpm (0.005m/sec) |
| Accuracy: |
±4 % or 4 fpm*
±4 % or 0.02 m/sec* whichever is greater
*Accuracy specification only valid for velocity readings above 50 fpm. |
|
| C0 |
| Range: |
0 to 500 ppm |
| Display Resolution: |
1 ppm |
| Accuracy: |
± 5 % or ± 3 ppm, whichever is greater, @ 20 °C and
50 % RH |
|
| C02 |
| Range: |
0 to 5000 ppm |
| Display Resolution: |
1 ppm |
| Accuracy: |
Warm up time 1 min (5 minutes for full specification) 2.75% + 75 ppm |
|
| Calculated specifications |
| Dew point temperature |
| Range: |
-44 °C to 50 °C, (-47 °F to 122 °F) |
| Display Resolution: |
0.1 °C (0.1 °F) |
| Accuracy: |
± 1 °C when temp: -20 °C to 50 °C RH: 40 % to 90 %
± 2 °C when temp: -20 °C to 50 °C RH: 20 % to 40 %
± 4 °C when RH: 10 % to 20 % |
|
| Wet bulb temperature |
| Range: |
-16 °C to 50 °C, (3 °F to 122 °F) |
| Display Resolution: |
0.1 °C, (0.1 °F) |
| Accuracy: |
± 1.2 °C when RH: 20 % to 90 % temp: -20 °C to 60 °C
± 2.1 °C when RH: 10 % to 20 % |
|
| Volume flow rate (in a duct) |
| Range: |
0 to 3,965 M3/m, (0 to 140,000 cfm) |
| Display Resolution: |
0.001 M3/min, (1 cfm) |
| Accuracy: |
N/A: The volume flow calculation will be a simple average of the data points times the duct area |
|
| % outside air (based on temperature) |
| Range: |
0 to 100% |
| Display Resolution: |
0.1 |
|
| % outside air (based on CO2) |
| Range: |
0 to 100 % |
| Display Resolution: |
0.1 % N/A |
|
| General specifications |
| Operating and storage temperature: |
|
-20 °C to 50 °C (-4 °F to 122 °F) |
|
| Humidity |
|
10 % to 90 % (non-condensing) |
|
| Altitude |
|
| Shock and vibration |
|
| Multi-language interface |
|
English, French, Spanish, Portuguese and German |
|
| Battery |
|
Rechargeable Li-Ion (primary), three-AA (backup) |
|
| Data logging |
|
25,000 records (continuous), 99 records (discrete) |
|
| Warranty |
|
|
| Model Name | Description | Price List | Buy it | | Fluke 975V | AirMeter™ with Velocity |  | | | Fluke 975 | AirMeter™ |  | |
| CarePlans | Buy it | | G2P-Group4 |
- GOLD CarePlan.
- Models covered: 975, 1625, and 1735.
- Extends warranty from two to four years and includes four annual NIST traceable calibrations with data.
| |  | | S2P-Group4 |
- SILVER CarePlan.
- Models covered: 975, 1625, and 1735.
- Extends warranty from two to four years.
|  |  |
|
|
|
|