Calculate energy loss in dollars

The Fluke 434 II Energy Analyzer is the ideal tool for energy logging. Utilizing the new Energy Loss Calculator function, the 434 II measures the fiscal cost of energy wasted due to poor power quality. This energy monetization capability allows you to identify the most energy-wasteful areas of your facility so you can determine potential energy saving solutions. Add basic power quality measurements to the package and you’re got yourself one powerful troubleshooting tool.

Applications
  • Energy monetization – calculate the fiscal cost of energy waste due to poor power quality
  • Energy assessment – quantify the before and after installation improvements in energy consumption to justify energy saving devices
  • Frontline troubleshooting – quickly diagnose problems on-screen to get your operation back online
  • Predictive maintenance – detect and prevent power quality issues before they cause downtime
  • Long-term analysis – uncover hard-to-find or intermittent issues
  • Load studies – verify electrical system capacity before adding loads

CSA cat3-1000/cat4-600 certified

The Fluke 434-II is designed for users who need to get to the solution of the power quality problem as quickly as possible so that they can minimize expensive downtime. The measurement process and display of data is optimized to get to the most important information as quickly as possible. Multiple parameters are measured simultaneously and displayed in formats that quickly describe overall power quality health while giving you the detailed information you need to make better maintenance decisions. Data can be quickly accessed as simple digital values, trend graphs that give you fast insight into changes over time, waveforms, phasor diagrams or analyzed and organized into tabular format such as the event data where the magnitude, duration and time stamping enable rapid correlation to the problems you are experiencing in your facility.
   
Energy loss Calculator — Calculate money lost to energy waste in terms of real dollars
It’s a simple fact, poor power quality can have a big impact on the bottom line. The Fluke 435-II enables you to identify issues and measure energy loss giving you specific insight into the amount of loss in dollars associated things like effective power and with poor power quality characteristics such as reactive power, unbalance, distortion, or neutral current. The 435-II even offers users the flexibility to input cable length and cable diameter so you can calculate loss due to conductor sizing (Or use AUTO mode if you don’t know your cable specification) and enter up to four unique time-dependent daily rates (kWh) for more accurate calculations. Armed with this critical data users can easily justify the investment necessary to take countermeasures.
 
Advanced Power Quality Health — At-a-glance power quality health data in real-time so you have the data you need, when you need it
The Fluke 430-II utilizes an integrated Power Quality Health summary that gives you an at-a-glance view of a complete range of power quality issues in real time. With a simple graphical presentation, complete with tolerance limits, you can quickly discover which power quality problems may be present on your electrical system. If you don’t know where to start or what problems might exist, the advanced Power Quality Health summary will simplify the task.
   
Power Inverter Efficiency
Power inverters take DC current and transform it into AC current, or vice versa. But, what percentage of that power going into the inverter comes out as usable current? Nothing is ever 100% efficient, and the efficiency will vary depending on how much power is being used at the time (with the efficiency generally being greater when more power is being used). Inverters can also lose performance over time and need to be checked. By comparing the input power with the output power you can determine the system efficiency. With the Power Inverter Efficiency feature you can discover just how good is your inverter at converting your DC power to AC (or vice versa).
 
AutoTrend — Quickly See the Trend
With a unique AutoTrend feature you can get fast insight into changes over time. Every displayed reading is automatically and continuously recorded without having to set up threshold levels or having to manually start the process So you can quickly view trends in voltage, current, frequency, power, harmonics or flicker on all three phases plus neutral.

Product specifications

  Model Measurement range Resolution Accuracy
Volt
Vrms (ac+dc) 434-II 1 V to 1000 V phase to neutral
0.1 V ± 0.5% of nominal voltage**** 
Vpk   1 Vpk to 1400 Vpk 1 V 5% of nominal voltage
Voltage Crest Factor (CF)   1.0 > 2.8 0.01 ± 5 %
Vrms½ 434-II 1 V to 1000 V phase to neutral 0.1 V ± 1% of nominal voltage 
Vfund 434-II 1 V to 1000 V phase to neutral 0.1 V
± 0.5% of nominal voltage
Amps (accuracy excluding clamp accuracy)
Amps (ac +dc) i430-Flex 1x  5 A to 6000 A 1 A ± 0.5% ± 5 counts
i430-Flex 10x 0.5 A to 600 A 0.1 A ± 0.5% ± 5 counts
1mV/A 1x 5 A to 2000 A 1A ± 0.5% ± 5 counts
1mV/A 10x 0.5 A A to 200 A (ac only) 0.1 A ± 0.5% ± 5 counts
Apk i430-Flex  8400 Apk  1 Arms ± 5 %
1mV/A 5500 Apk 1 Arms ± 5 %
A Crest Factor (CF)   1 to 10 0.01 ± 5 %
Amps½ i430-Flex 1x  5 A to 6000 A  1 A  ± 1% ± 10 counts 
i430-Flex 10x 0.5 A to 600 A 0.1 A  ± 1% ± 10 counts
1mV/A 1x   5 A to 2000 A  1A  ± 1% ± 10 counts
1mV/A 10x 0.5 A A to 200 A (ac only) 0.1 A ± 1% ± 10 counts
Afund i430-Flex 1x  5 A to 6000 A 1 A ± 0.5% ± 5 counts 
i430-Flex 10x  0.5 A to 600 A 0.1 A ± 0.5% ± 5 counts
1mV/A 1x  5 A to 2000 A 1A ± 0.5% ± 5 counts
1mV/A 10x  0.5 A A to 200 A (ac only) 0.1 A ± 0.5% ± 5 counts
Hz
Hz Fluke 434 @ 50 Hz nominal 

42.50 Hz to 57.50 Hz

0.01 Hz
± 0.01 Hz
Fluke 434 @ 60 Hz nominal 51.00 Hz to 69.00 Hz 0.01 Hz ± 0.01 Hz
Power
Watts (VA, var) i430-Flex 
max 6000 MW 0.1 W to 1 MW ± 1% ± 10 counts
1 mV/A max 2000 MW 0.1 W to 1 MW ± 1% ± 10 counts
Power factor (Cos j/DPF)   0 to 1 0.001 ± 0.1% @ nominal load conditions
Energy
kWh (kVAh, kvarh) i430-Flex 10x Depends on clamp scaling and V nominal ± 1% ± 10 counts
Energy loss i430-Flex 10x Depends on clamp scaling and V nominal ± 1% ± 10 counts Excluding line resistance accuracy
Harmonics
Harmonic order (n)   DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7
Inter-harmonic order (n)   OFF, 1 to 50 Grouping: Harmonic and Interharmonic subgroups according to IEC 61000-4-7
Volts %f 0.0 % to 100 % 0.1 % ± 0.1% ± n x 0.1 %
%r 0.0 % to 100 % 0.1 % ± 0.1% ± n x 0.4 %
Absolute 0.0 to 1000 V 0.1 V ± 5% *
THD 0.0 % to 100 % 0.1 % ± 2.5 %
Amps %f 0.0 % to 100 % 0.1 % ± 0.1% ± n x 0.1%
%r 0.0 % to 100 % 0.1 % ± 0.1% ± n x 0.4 %
Absolute 0.0 to 600 A 0.1 A ± 5% ± 5 counts
THD 0.0 % to 100 % 0.1 % ± 2.5 %
Watts %f or %r  0.0 % to 100 % 0.1 % ± n x 2%
Absolute Depends on clamp scaling and V nominal  ± 5% ± n x 2 % ± 10 counts
THD 0.0 % to 100 %   0.1 % ± 5 %
Phase Angle -360° to +0° ± n x 1°
Flicker
Plt, Pst, Pst(1min) Pinst   0.00 to 20.00 0.01 ± 5 %
Unbalance
Volts % 0.0 % to 20.0 % 0.1 % ± 0.1 %
Amps % 0.0 % to 20.0 % 0.1% ± 1 %
Mains signaling
Threshold levels   Threshold, limits and signaling duration is programable for two signaling frequencies
Signaling frequency   60 Hz to 3000 Hz 0.1 Hz  
Relative V%   0 % to 100 % 0.10 % ± 0.4 %
Absolute V3s (3 second avg.)   0.0 V to 1000 V 0.1 V ± 5 % of nominal voltage

General specifications

Case Design Rugged, shock proof with integrated protective holster Drip and dust proof IP51 according to IEC60529 when used in tilt stand position Shock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g 2 /Hz according to MIL-PRF-28800F Class 2
Display Brightness: 200 cd/m 2 typ. using power adapter, 90 cd/m 2 typical using battery power Size: 127 mm x 88 mm (153 mm/6.0 in diagonal) LCD Resolution: 320 x 240 pixels Contrast and brightness: user-adjustable, temperature compensated
Memory 8GB SD card (SDHC compliant, FAT32 formatted) standard, upto 32GB optionally Screen save and multiple data memories for storing data including recordings (dependent on memory size)
Real-time clock Time and date stamp for Trend mode, Transient display, System Monitor and event capture

Environmental

Operating temperature 0 °C ~ +40 °C; +40 °C ~ +50 °C excl. battery
Storage temperature -20 °C ~ +60 °C
Humidity +10 °C ~ +30 °C: 95% RH non-condensing
+30 °C ~ +40 °C: 75% RH non-condensing
+40 °C ~ +50 °C: 45% RH non-condensing
Maximum operating altitude Up to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V
Up to 3,000 m (10,000 ft) for CAT III 600 V, CAT II 1000 V
Maximum storage altitude 12 km (40,000 ft)
Electro-Magnetic-Compatibility (EMC) EN 61326 (2005-12) for emission and immunity
Interfaces mini-USB-B, Isolated USB port for PC connectivity SD card slot accessible behind instrument battery
Warranty Three years (parts and labor) on main instrument, one year on accessories

View full family specifications »

    * ± 5 % if ≥ 1 % of nominal voltage ± 0.05 % of nominal voltage if < 1% of nominal voltage
   ** 50Hz/60Hz nominal frequency according to IEC 61000-4-30
 *** 400Hz measurements are not supported for Flicker, Mains Signaling and Monitor Mode.
****for nominal voltage 50 V to 500 V

Model NameDescription
Fluke 434 II

Three-Phase Energy Analyzer

Included accessories

  • BC430 Power Adapter
  • International plug adapter set
  • BP290 (Single capacity Li-ion battery) 28 Wh (8 hours or more)
  • TLS430 Test lead and Alligator clip set
  • WC100 color coding clips and regional decals
  • i430flex-TF, 24 inch (61 cm) length, 4 flexible current probes
  • 8 GB SD card
  • PowerLog on CD (includes operator manuals in PDF format)
  • USB cable A - Mini B
  • C1740 Soft Case

Cables and Hardware
GPS430GPS430 Time Synchronization Module

Clips
AC285AC285 SureGripTM Alligator Clips

Batteries, Chargers and Adapters
BP2902400 mAh Li-ion battery for Fluke 190 Series II
BP2914800 mAh High capacity Li-ion battery ) for Fluke 190-seriesII
BC430BC430 Line Voltage Adapter/Battery Charger
EBC290External Battery Charger for charging BP290 or BP291 outside the instrument

Cases and Holsters
C435C435 Hard Rolling Case

Current Clamps
i30sFluke i30s AC/DC Current Clamp
i400si400s AC Current Clamp
i5sPQ3i5sPQ3, 5 A ac Current Clamps, 3-pack
i1000si1000s AC Current Probe
i3000si3000s AC Current Clamp

Options
HH290Hanging Hook for ScopeMeter 190-Series II

PC Adapter and Software
FLK-FC-SD CARDFluke Connect Wireless SD Card

Test Leads
TLS430Fluke TLS430 – Test Leads and Alligator Clips (4 black, 1 green)