Pinpoint power quality problems faster, safer and in greater detail
These three-phase power quality meters help you locate, predict, prevent and troubleshoot problems in power distribution systems. These easy-to-use power quality tools are a “must have for any person who maintains or troubleshoots three phase power. The new IEC Class A standards for flicker and power quality are built right in to take the guess work out of power monitoring.
Applications
- Frontline troubleshooting – quickly diagnose problems on-screen to get your operation back online
- Predictive maintenance – detect and prevent power quality issues before they cause downtime
- Quality of service compliance – validate incoming power quality at the service entrance
- Long-term analysis – uncover hard-to-find or intermittent issues
- Load studies – verify electrical system capacity before adding loads
- Energy assessments – quantify energy consumption before and after improvements to justify energy saving devices
|
|
|
- Complete three-phase troubleshooting tool: measures virtually every power system parameter: voltage, current, frequency, power, power consumption (energy), unbalance and flicker, harmonics and inter-harmonics. Captures events like dips and swells, transients, interruptions and rapid voltage changes.
- The Fluke 435 features 0.1 percent voltage accuracy making it fully compliant with the IEC 61000-4-30 Class A standard
- Logger function: record the detail you need. Detailed, user-configurable long-time recording gives you the MIN, MAX and AVG readings of up to 100 parameters on all 4 phases with selectable averaging time down to 0.5 seconds. Enough memory is available to record 400 parameters with 1 minute resolution for up to a month.
- Four channels: simultaneously measures voltage and current on all three phases and neutral.
- AutoScaling: easier trend analysis with automatic scaling of the vertical axis you
will always use the full display to view the waveforms.
- Automatic transient display: captures up to 40 dips, swells, interruptions or
transients automatically.
- Meets the stringent 600 V CAT IV, 1000 V CAT III safety standard required for
measurements at the service entrance.
- Rugged, handheld instrument operates for more than 7 hours on included
rechargeable NiMH battery pack. Menu-driven interface simplifies operation.
- Extensive data analysis possibilities. Cursors and zoom can be used ‘live’ while
taking the measurements, or ‘offline’ on stored measurement data. The stored
measurements can also be transferred to a PC with FlukeView software (included with Fluke 435 and 434).
- The Fluke 435 comes with Power log software to analyse recorded data and to
create reports.
- Complete package includes everything to get started: 4 current clamps, 4 flex
clamps with Fluke 435, 5 voltage test leads and clips, line adapter/battery
charger and hard case.
- Complies with IEC 61000-4-30 measurement standards
|
AutoTrend - Quickly see the trend
Unique AutoTrend gives you fast insight into changes over time. Every displayed reading is automatically and continuously recorded without having to set up threshold levels or interval times, or having to manually start the process. You can quickly view trends in voltage, current, frequency, power, harmonics or flicker on all three phases plus neutral. And you can analyze the trends using the cursors and zoom function – even while background recording continues.
AutoTrend automatically records all displayed parameters in the background.
SystemMonitor - Check performance against EN50160 with ease
With a single push of a button, the unique System-Monitor gives you an overview of power system performance, and checks the compliance of incoming power to EN50160 limits or to your own custom specifications. The overview is shown on a single screen, with color-coded bars clearly indicating
which parameters fall outside the limits.
The System-Monitor overview screen gives instant insight into whether the voltage, harmonics, flicker, frequency and the number of dips and swells fall outside the set limits. A detailed list is given of all events falling outside the set limits.
|
|
|
|
Logging function allows you to customize measurement selections and provides instantaneous analysis of user-selectable parameters.
|
Measure and record power (W), VA and VARs. The 434 adds the ability to record energy consumption.
|
Track harmonics up to the 50th, and measure and record THD in accordance with IEC61000-4-7 requirements
|
|
|
| Technical Data |
| Inputs |
| Number: |
4 voltage and current (3 phases + neutral) |
| Maximum voltage: |
1000 Vrms (6 kV peak) |
| Maximum sampling speed: |
200 kS/s on each channel simultaneously |
| | Volt/Amps/Hertz |
| Vrms (AC + DC) |
|
| Measurement range: |
1 ... 1000 V |
| Accuracy: |
0.1% of Vnom |
|
|
| Vpeak |
|
| Measurement range: |
1 ... 1400 V |
| Accuracy: |
5% of Vnom |
|
|
| Crest factor, voltage |
|
| Measurement range: |
1.0 ... > 2.8 |
| Accuracy: |
±5% |
|
|
| Arms (AC + DC) |
|
| Measurement range: |
0 ... 20 kA |
| Accuracy: |
±0.5% ± 5 counts |
|
|
| Apeak |
|
| Measurement range: |
0 ... 5.5 kA |
| Accuracy: |
5% |
|
|
| Crest factor, A |
|
| Measurement range: |
1 ... 10 |
| Accuracy: |
±5% |
|
|
| Hz 50 Hz nominal |
|
| Measurement range: |
40 ... 70 Hz |
| Accuracy: |
±0.01 Hz |
| | Dips and swells |
| Vrms (AC+DC) ² |
|
| Measurement range: |
0.0% … 100% of Vnom |
| Accuracy: |
±0.2% of nominal voltage |
|
|
| Arms (AC+DC) ² |
|
| Measurement range: |
0 ... 20 kA |
| Accuracy: |
±1% ± 5 counts |
| | Harmonics |
| Harmonic (interharmonic) (n) |
|
| Measurement range: |
DC, 1..50; (Off, 1..49) measured according to IEC 61000-4-7 |
|
|
| Vrms |
|
| Measurement range: |
0.0 … 1000 V |
| Accuracy: |
±0.05% of nominal voltage |
|
|
| Arms |
|
| Measurement range: |
0.0 … 4000 mV x clamp scaling |
| Accuracy: |
±5% ± 5 counts |
|
|
| Watts |
|
| Measurement range: |
Depends on clamp scaling and voltage |
| Accuracy: |
±5% ± n x 2% or reading, ± 10 counts |
|
|
| DC voltage |
|
| Measurement range: |
0.0 … 1000 V |
| Accuracy: |
±0.2% of nominal voltage |
|
|
| THD |
|
| Measurement range: |
0.0 … 100.0% |
| Accuracy: |
±2.5% V and A (± 5% Watt) |
|
|
| Hz |
|
| Measurement range: |
0 … 3500 Hz |
| Accuracy: |
± 1 Hz |
|
|
| Phase angle |
|
| Measurement range: |
-360º ... +360º |
| Accuracy: |
± n × 1.5º |
| | Power and energy |
| Watt, VA, VAR |
|
| Measurement range: |
1.0 … 20.00 MVA¹ |
| Accuracy: |
±1% ± counts |
|
|
| kWh, kVAh, kVARh |
|
| Measurement range: |
00.00 …200.0 GVAh¹ |
| Accuracy: |
± 1.5% ± 10 counts |
|
|
| Power Factor/ Cos Ф / DPF |
|
| Measurement range: |
0…1 |
| Accuracy: |
± 0.03 |
| | Flicker |
| Pst (1 min), Pst, Plt, PF5 |
|
| Measurement range: |
0.00 … 20.00 |
| Accuracy: |
±5% |
| | Unbalance |
| Volts |
|
| Measurement range: |
0.0 … 5.0% |
| Accuracy: |
±0.5% |
|
|
| Current |
|
| Measurement range: |
0.0 … 20% |
| Accuracy: |
± 1% |
| | Transient Capture |
| Volts |
|
| Measurement range: |
±6000 V |
| Accuracy: |
±2.5% of Vrms |
| Minimum detect duration |
5 µs (200kS/s sampling) |
| | Inrush mode |
| Arms (AC+DC) |
|
| Measurement range: |
0.000 … 20.00 kA¹ |
| Accuracy: |
±1% of meas ± 5 counts |
|
|
| Inrush duration (selectable) |
|
| Measurement range: |
7.5 s ... 30 min |
| Accuracy: |
±20 ms (Fnom = 50 Hz) |
| | Autotrend recording |
| Sampling: |
5 readings/sec continuous sampling per channel |
| Memory: |
1800 min, max and avg points for each reading |
| Recording time: |
Up to 450 days |
| Zoom: |
Up to 12x horizontal zoom |
| | Memory |
| Screens & data: |
50, shared memory divided between logging, screens and data sets |
| | Notes |
| ¹ |
Depending on clamp scaling |
| ² |
Value is measured over 1 cycle, commencing at a fundamental zero crossing, and refreshed each half-cycle
|
|
| Environmental Specifications |
| Operating Temperature | |
| Safety Specifications |
| Safety |
|
EN61010-1 (2nd edition) pollution degree 2; 1000 V CAT III / 600 V CAT IV
ANSI/ISA S82.01
|
|
| Mechanical & General Specifications |
| Size | | | Weight | | | Battery Life |
| Rechargeable NiMH pack (installed): |
>7 hours |
| Battery charging time: |
4 hours typical |
| | Shock & Vibration |
| Shock: |
30 g |
| Vibration: |
3 g according to MIL-PRF-28800F Class 2 |
| | Case |
|
Rugged, shock proof with integrated protective holster, IP51 (drip and dust proof) |
| | Warranty | |
|
| Clips | | AC285 | AC285 SureGrip™ Alligator Clip Set |
| Batteries, Chargers & Adapters | | BP190 | BP190 Rechargeable NiMH Battery Pack |
| Cables & Hardware | | OC4USB | OC4USB USB interface cable | | PAC91 | PAC91 Printer Adapter Cable |
| Current clamps | | i1000s | i1000s AC Current Clamp (1000 A) | | i2000 flex | i2000 flex AC Current Clamp | | i200s | i200s AC Current Clamp | | i3000s | i3000s AC Current Clamp | | i400s | i400s AC Current Clamp | | i430-flex-4pk | i430 Flex 4 Pack | | i430-flex | i430 Flex Current Clamp | | i5sPQ3 | i5sPQ3 AC Current Clamp, 3-pack |
| Lights | | L206 | L206 Deluxe LED Hat Light |