The Fluke 41B Harmonics Analyzer combines the ease of use of a digital multimeter, the visual feedback of an oscilloscope and the power of a harmonics analyzer in a single instrument. If you're testing power on three-phase systems or trouble-shooting harmonics on non-linear loads, no test tool makes it easier.

The Model 41B is ideal for further analyzing data and optimizing system performance. Use the Fluke 41B's FlukeView® software (included) to download acquired data to a printer or an MS-DOS® or Windows® compatible computer for analysis and presentation.

Features at a Glance

Three Views of each reading

  • Waveform
  • Bargraph showing harmonic levels
  • Numeric values

Real-time Display Updates

Display updates three times a second for a dynamic view of actual circuit conditions.

Comprehensive Measurements

Measure rms, peak and total harmonic distortion (THD) for complex voltages and currents - with no manual calculations required.

Three-Phase readings

From a simple single-phase measurement, automatically calculates three-phase power for 3-wire balanced loads (typically 5% or less imbalance). To make the single-phase measurement, simply connect the meter as shown and select the 3º, 3C watts display.

System Critical Data

Immediate readings of Power Factors, KVAR, Crest Factor, K-Factor.

Display Harmonics individually to the 31st

Min/Max and Average Recording

Data Storage

Up to eight complete measurement sets.

Isolated Serial Interface

Communications with a serial printer or DOS® or Windows®-compatible computer.

Safety Designed

To meet the latest standards: IEC 1010-1, pollution degree 2, Installation Category III, material group II, 600 V. Double insulated protection as described in IEC 1010-1, Annex H.

Volts

Display

One cycle of the fundamental waveform and its frequency. Instantaneous voltage at cursor position.

figure 2

Application

Identifying sources of harmonic currents. Obtaining data for designing, specifying or sizing transformers, filters, etc.

Amperes

Display

%-fundamental or %-rms, rms value, frequency, and phase angle of fundamental or harmonic currents (up to 31st), as selected by cursor from bar graph.

Application

Identifying sources of harmonic currents. Obtaining data for designing, specifying or sizing transformers, filters, etc.

Watts

Display

Watts, volt-amps, power factor (total) and displacement power factor of fundamental of single-phase or three-phase power.

Application

Identifying displacement versus total power-factor. Determining proper power-factor correction methods.

Measurement Accuracy
Voltage
Range and Resolution:  5.0 V to 600 V rms (AC+DC); ±5.0 V to ±933 V peak
Accuracy:  rms: ±(0.5 % + 2 digits); Peak or DC: ±(2 % + 3 digits) (Add 2 digits if < 15 V rms)
Current (1mV/A) Isolated input
Range and Resolution:  1.00 A to 1000 A rms (AC+DC); ±1.0 A to ±2000 A peak
Accuracy:  rms: ±(0.5% + 3 digits)+probe specs; Peak or DC: ±(2 % + 4 digits) + probe specs
Watts/Volt-Amps (1mV/A) isolated input
Range and Resolution:  0.0W(VA) to 600 kW(kVA) average;
 0.0W(VA) to ±2000 kW(kVA) peak
Accuracy:  AC+DC: ±(1 % + 4 digits) + probe specs
Harmonics (harmonic level >5% using Smooth 20)
Volts:  : Fundamental to 13th ±(2 %+2 digits);
 At 31st ±(8 %+2 digits);
Amperes or Watts:  Fundamental to 13th ±(3 % + 3 digits) + probe specs;
 At 31st ±(8 % + 3 digits) + probe specs
Frequency
Range and Resolution:  6.0 Hz to 99.9 Hz
Accuracy:  ±0.3 Hz
Input Bandwidth
 DC, 6 Hz to 2.1 kHz
Crest Factor (CF)
Range and Resolution:  6.0 Hz to 99.9 Hz
Accuracy :  ±0.3 Hz
Power Factor (PF)
Range and Resolution:  0.00 to 1.00
Accuracy:  ±0.02
Displacement Power Factor (DPF)
Range and Resolution:  0.00 to 1.00
Accuracy:  ±0.04 to ±0.03 (0.30 to 0.89) ±0.02 (0.90 to 1.00)
Phase
Range and Resolution:  -179 º to 180 º
Accuracy (Fundamental):  ±2 º + probe specs
K-Factor (KF)
Range and Resolution  1.0 to 30.00
Accuracy  ± 10%
% THD-F
Range and Resolution:  0.00 % to 799.9 %
Accuracy:  ±(0.03 Reading + 2.0 %)
% THD-R
Range and Resolution:  0.0 % to 99.9 %
Accuracy:  ±(0.03 Reading + 2.0 %)

General Specifications
Minimum Input Levels
 5 V rms or 1 A rms
Battery Life
 4 alkaline "C" cells ANSI/NEDA-14A, IEC-LR14 (supplied) 48 hours typical (continuous)
Shock & Vibration
 Per MIL-T-28800, Class 3
Case
 Drip-Proof and Dust-Proof per IEC, IP 52
Size
 234 mm L x 100 mm W x 64 mm D (9.2" L x 3.9" W x 2.5" D)
Weight
 0.9 kg (2.0 lb.)
Warranty
 One Year Warranty
Model NameDescription
Fluke 41B Power Harmonics Analyzer including:
  • Isolated RS-232 Cable
  • FlukeView® Software
  • Software Manual
  • 80i-500s AC Current Probe
  • TL24 Test Leads
  • AC20 Test Clips
  • TP20 Test Probes
  • Operator's manual

Clips
AC285AC285 SureGrip™ Alligator Clip Set

Test Probes
TP1TP1 Slim Reach Test Probe (flat blade)
TP2TP2 Slim Reach Test Probe (2 mm)
TP4TP4 Slim Reach Test Probe (4 mm)

Cables & Hardware
PAC91PAC91 Printer Adapter Cable

Cases and Holsters
C100C100 Hard Meter and Accessory Case
C125C125 Soft Meter Case
C43C43 Soft Carrying Case
C550C550 Tool Bag
C800C800 Hard Meter and Accessory Case

Current clamps
80i-110s80i-110s AC/DC Current Probe (100 A)
i1000si1000s AC Current Clamp (1000 A)
i2000 flexi2000 flex AC Current Clamp
i200si200s AC Current Clamp
i3000si3000s AC Current Clamp

High Voltage Probes
80k-1580K-15 High Voltage Probe
80K-4080K-40 High Voltage Probe
80K-680K-6 High Voltage Probe

Temperature
80T-150UA80T-150U Universal Temperature Probe (for DMMs)
80TK80TK Thermocouple Module (Type K)

Test Leads
TL220TL220 SureGrip™ Industrial Test Lead Kit
TL221TL221 SureGrip™ Extension Lead Set
TL223TL223 SureGrip™ Electrical Test Lead Kit
TL224TL224 SureGrip™ Silicone Test Lead Set
TL238TL238 SureGrip™ Test Lead Set for High Energy Environments
TL71TL71 Test Lead Set
TLK220TLK-220 EUR SureGrip Industrial Test Lead Kit
Home   |   Site Map   |   Fluke Corporation   |   Safety Notices  |   Terms and Conditions   |   Privacy Statement   |   Disclaimer© 1995 - 2013 Fluke Corporation