Middle East [Change]  |  Fluke [Change Company]
fluke
Home  |  Products  |  Power Quality Tools  |  Logging Power Meters   |  
Contact usRefer this page
This product is discontinued or reclassified

Fixed-installation multipoint power recorders (RPM)

 Multipoint Power Recorders
Simply disclose everything, every event, every parameter, on every cycle, all the time – within seconds

No longer will your power distribution system hold any secrets. The power recorder series is a unique range of instruments that increase your ability to maintain and troubleshoot your plant’s power quality. They monitor every aspect of power without blind spots or gaps, on all conductors in your 3-phase distribution system. 9 channels allow you to exactly monitor what’s happening on the neutral and ground conductors as well. Unlike other power monitors, every parameter on every conductor is measured all the time.

  • 4 voltage channels to measure the three phases plus neutral-to-ground voltage.
  • Unique 5 current channels allow you to monitor neutral and ground current in addition to the individual phases.
  • The power recorder looks at every cycle for power quality events such as sags, swells, interruptions and transients on all channels simultaneously. You will see everything from sub-cycle transients to harmonics
  • Don’t know what to look for? Don’t worry, you don’t need to set trigger thresholds. Adaptive thresholds optimize event capture. You won’t be disappointed about missed events or a memory full of noise
  • Records true RMS voltage, true RMS current, frequency, harmonics, power consumption parameters (W, kWh, VA, VAR, PF), imbalance and flicker.
  • Analyzes voltage characteristics according to the EN50160 standard.
  • Transient capture down to 500 ns duration and 6400 Vpk.
  • High-speed waveform capture allows you to display transients as fast as 500 ns.
  • Stores up to 96,000 events.
  • Real-time oscilloscope shows all 9 channels simultaneously.
  • Ethernet interface makes downloads fast and easy and TCP/IP enables communication via Internet.
Software completes the system

Capture thousands of events without setting any threshold using the unique Full Disclosure technology.

There are two software packages available for the Power Recorder:

  • The Power Analysis System software and
  • The Scenario software.
  • Both packages handle seamless communication with the Power Recorder, graphical display of power-system parameters, and data-management tools.


Power Analysis System software

Plot events on any power tolerance curve. You can create your own or use CBEMA, ITIC and ANSI curves

For the Power Analysis System software there are two optional packages available:

  • Report writer software. This software analyzes all the data collected. It sorts events and summary data and merges graphs with Microsoft Word for easy documentation and report creation.
  • Polling and alarm software. This automates collection of data from multiple monitors to: alert key personnel to serious events by executing alarm procedures. easily centralize data collection via


The Scenario software

Real-time waveform display shows up to 9 channels (4 voltage, 5 current) including ground and neutral current.

This powerful software package performs predictive analysis, manages data and gives advanced warning to avoid shutdowns.

  • Allows plotting of multiple-measurement sessions on one timescale
  • Includes facilities for comparing trends from multiple databases
  • Calculates a Power Quality Index - a single figure of merit that characterizes the overall performance of a power system. The Power Quality Index allows you to determine system-performance trends over
Specifications
Number of channels
Voltage channels:  4
Current channels:  5
Voltage (phase)
Range:  100 mV - 600 VRMS, 1000 V peak
Sampling rate:  6.4 kS/s¹ or 2 MS/s²
Resolution:  14 bits, 90 mV
Accuracy:  ±(1.5% of reading + 0.5 V)
Voltage (neutral)
Range:  10 mV - 70 VRMS, 1000 V peak
Sampling rate:  6.4 kS/s¹ or 2 MS/s²
Resolution:  14 bits, 90 mV
Accuracy:  ±(1.5% of reading + 0.5 V)
Current
Range:  Depends upon CT
Sampling rate:  6.4 kS/s¹
Resolution:  14 bits
Accuracy:  ±(0% of reading + 0.1% of probe range + probe uncertainty)
Transient Capture
Range:  200 - 1000 V peak
Sampling rate:  6.4 kS/s¹
Resolution:  10 bits, 12 V
Accuracy:  ±(5% of reading + 36 V)
High speed transient capture
Range:  200 - 6400 V peak
Sampling rate:  6.4 kS/s¹
Resolution:  10 bits, 12 V
Accuracy:  ±(5% of reading + 36 V)
Notes:
¹)  50 Hz line frequency
²)  For high speed models
Nominal fundamental frequency:  50/60 Hz ± 0.1 Hz
Voltage and current sampling:  128 samples per cycle

Environmental Specifications
Operating Temperature
 0 - 50 °C
Humidity (Without Condensation)
 90%

Safety Specifications
Standards:
Measurements:  IEC 61000-4-30 Class B using cycle based techniques
Power Quality:  EN 50160
Flicker:  EN 60868

Mechanical & General Specifications
Size
 31.25 x 29.4 x 15.2 cm
Weight
 4 kg
Warranty
 1 year
Power, battery life
Mains:  85 - 264 VAC, 47 - 440 Hz
DC:  10 - 15 V with 4255 Cable
Backup:  NiCd, recharges automatically while power is applied
 Powers the instrument for 5 minutes then controlled shutdown. Monitoring resumes after power is restored.
Power Consumption:  40 W
Communication
 10Base-T Ethernet, RJ45 connector or via Internet

Current clampsPrice List
Model 3100R Current TransformerModel 3100R Clamp-on Current TransformerOn Request
Model 3112/RPM CTModel 3112/RPM Flexi-CT™ Flexible Current TransformerOn Request
Model 3120R Current TransformerModel 3120R Clamp-on Current TransformerOn Request
Model 3212/RPM CTModel 3212/RPM Flexi-CT™ Flexible Current TransformerOn Request

OptionsPrice List
1658/OPKAdds 2 MS/s waveform display to /B, /F and /H versionsOn Request
1653/OPKAdds harmonics spectrum, THD, imbalance and flicker to /B versionsOn Request
1652/OPKAdds Watts, kWh, VA, VAR and Cos Φ to /B, /F and /L versionsOn Request
1662/OPKIncrease event capture to 96000 events for /B versionsOn Request
1651/OPKPower quality measurement option (standard in /B,/F,/H,/L,and /M versions)On Request
1663/OPKTCP/IP stack (standard in /B,/F,/H,/L,and /M versions)On Request

SoftwarePrice List
5000/RPM5000/RPM Power analysis softwareOn Request
5000S/RPM5000S/RPM Power analysis softwareOn Request
5400/RPM5400/RPM Scenario analysis softwareOn Request
5600/RPM5600/RPM Power analysis software with Report Writer and Master PollingOn Request
5600S/RPM5600S/RPM Power analysis software with Report Writer, Master PollingOn Request
5903/RPMAdds Master Polling to power analysis softwareOn Request
5905/RPMAdds Report Writer and Master Polling to power analysis softwareOn Request
5904/RPMAdds Sub-Polling to power analysis softwareOn Request
Search Fluke