Kit includes:
- Fluke 6500 Mainframe
- EXTL100 Extension lead test adaptor
- DMS 0702/PAT Appliance Tester Software
- Pass560R Appliance pass labels
|
|
| Test Specifications |
| |
|
The accuracy specification for the display range is defined as ± (%reading + digit counts) at 23 °C ± 5 °C, ≤ 75 % RH. Between 0 °C and 18 °C and between 28 °C and 40 °C, accuracy specifications may degrade by 0.1 x (accuracy specification) per °C. |
|
The measurement range meets the service operating errors specified in EN61557-1: 1997, EN61557-2: 1997 , EN61557-4: 1997. |
|
| Power-on Test |
|
The test indicates reversed L-N, missing PE, and measures the mains voltage and frequency. |
| Display range: |
90 V to 264 V |
| Accuracy at 50 Hz: |
± (2% + 3 counts) |
| Resolution: |
0.1 V (1 V - model 6200) |
| Input impedance |
> 1 MΩ // 2.2 nF |
| Maximum input mains voltage: |
300 V |
|
| Earth Bond Test (Rpe) |
| Display range: |
0 to 19.99 Ω |
| Accuracy (after Bond Test zeroing): |
± (2.5% + 4 counts) |
| Resolution: |
0.01 Ω |
| Test current: |
200 mA AC -0% +40% into 1.99 Ω |
|
25 A AC ± 20% into 25 mΩ at 230 V |
| Open circuit voltage: |
> 4 V AC, < 24 V AC |
| Bond test zeroing: |
can subtract up to 1.99 Ω |
|
| Insulation Test (Riso) |
| Display range: |
0 to 299 MΩ |
| Accuracy: |
± (5% + 2 counts) from 0.1 to 300 MΩ |
| Resolution: |
0.01 MΩ (0 to 19.99 MΩ) |
|
0.1 MΩ (20 to 199.9 MΩ) |
|
1 MΩ (200 to 299 MΩ) |
| Test voltage: |
500 V DC -0% + 10% at 500 kΩ load |
| Test current: |
> 1 mA at 500 kΩ load, < 15 mA at 0 Ω |
| Auto discharge time: |
< 0.5 s for 1 μF |
| Max. capacitive load: |
operational up to 1 μF |
|
| Touch Current Test |
| Display range: |
0 to 1.99 mA AC |
| Accuracy: |
± (4% + 2 counts) |
| Resolution: |
0.01 mA |
| Internal resistance (via probe): |
2 kΩ |
| Measuring method: |
probe |
|
The appliance under test is energized at mains potential. |
|
| Substitute Leakage Current Test |
| Display range: |
0 to 19.99 mA AC |
| Accuracy: |
± (2.5% + 3 counts) |
| Resolution: |
0.01 mA |
| Test voltage: |
35 V AC ± 20% |
|
| Load/Leakage Test: Load Current |
| Display range: |
0 to 13 A |
| Accuracy: |
± (4% + 2 counts) |
| Resolution: |
0.1 A |
|
The appliance under test is energized at mains potential. |
|
| Load/Leakage Test: Load Power |
| Display range: |
0 to 999 VA |
|
1.0 kVA to 3.2 kVA |
| Accuracy: |
± (5% + 3 counts) |
| Resolution: |
1 VA (0 to 999 VA) |
|
0.1 kVA (1.0 kVA to 3.2 kVA) |
|
The appliance under test is energized at mains potential. |
|
| Load/Leakage Test: Leakage Current |
| Display range: |
0 to 19.99 mA |
| Accuracy: |
± (4% + 4 counts) |
| Resolution: |
0.01 mA |
|
The appliance under test is energized at mains potential. |
|
| PELV Test |
| Accuracy at 50 Hz: |
± (2% + 3 counts) |
| Overload protection: |
300 Vrms |
| Warning threshold: |
25 Vrms |
|
| Environmental Specifications |
| Operating Temperature |
|
| Relative Humidity |
|
non condensing < 10 °C |
|
95% from 10 to 30 °C |
|
75% from 30 to 40 °C |
|
| Safety Specifications |
| Safety Rating |
|
| Mechanical & General Specifications |
| Size |
|
200 mm (L) x 275 mm (W) x 100 mm (H) |
|
| Weight |
|
| Power Supply |
|
V + 10 % - 15 %, 50 Hz ± 2 % |
|
| Power Consumption (Tester) |
|
13 W typical (idle) |
|
60 W max. during 25A Bond Test |
|
| Storage |
| Temperature: |
-10 to 60 °C |
| Corrosion: |
70 °C @ 95 % RH for 5 days max. |
|
| Operating Altitude |
|
| Sealing |
|
IP-40 (enclosure), IP-20 (connectors) |
|
| EMC |
|
complies with EN61326-1, criteria B |
|
| EMI Immunity |
|
|
| Model Name | Description | Price List | | Fluke 6500 Kit |
- Fluke 6500 Portable Appliance Tester
- EXTL100 Extension lead test adapter
- DMS 0702/PAT, APPLIANCE TESTER SOFTWARE
- Pass560R Appliance pass labels
| On Request |
| Kits Components | | Pass560R | Appliance pass labels
| On Request | | DMS 0702/PAT APPLIANCE TESTER SOFTWARE | Software for Appliance Tester Fluke 6500
Includes:
- RS232 interface adapter
- Printed short form manual
|
| On Request | | EXTL100 |
| On Request | | Fluke 6500 |
| On Request |
|
|
|
|