Fluke 1750 Three-Phase Power Recorder

Contact Me
Request A Demo
Fluke 1750
Record three-phase power quality and monitor for power quality disturbances with the new Fluke 1750 Power Recorder and the Fluke Power Analyze software. These power meters automatically record every power quality parameter and event, on every cycle – all the time.

Applications
Long-term analysis: Uncover hard-to-find or intermittent issues; monitor critical equipment, capturing power quality events to correlate with equipment malfunction
Power quality surveys: Quantify power quality throughout a facility, documenting results with professional reports
Quality of service compliance: Validate incoming power quality at the service entrance
Equipment Installation/Commissioning: Benchmark: power system prior to install to insure quality of service

Fluke 1750
  • Power quality that meets the standard: All measurements comply with IEC61000-4-30 standards for correct evaluation of all measured values including voltage, current, power, harmonics, flicker etc.
  • Quick and reliable configuration: ARCHOS 43 Internet Tablet provides a window into what the instrument is recording, enabling quick and reliable configuration even in awkward test locations
  • Threshold-free set up: Apply thresholds after data is collected with Fluke Power Analyze Software – no need to worry about missed information due to incorrect setups
  • Captures everything: Cross-channel and current triggering capture every measurement, on every channel, every time
  • Intuitive PC software: Easily analyze data and generate reports with automated EN50160 reporting and compliance
  • Reporting has never been easier: Auto Report creates either standard reports or customized reports with the minimum effort or hassle. 
  • Plug and play: Set up in minutes with self-identifying current probes and single-lead voltage connections
  • No need to reconnect wires: Swap channels internally with the wireless PDA or PC when connections are not correct
  • Measure every parameter: Voltage and current on three phases, neutral, and ground
  • 5 MHz, 8000 Vpk waveform capture: Get a detailed picture of even the shortest events
  • Quickly retrieve data: With included SD memory card or via the 100BaseT high-speed Ethernet connection.  SD card includes automatic download to SD when no other connection is made to the instrument
Technical Specifications
Power quality measurement standards
Conformance  IEC 61999-1-4 Class 1, IEC 61000-4-30 Class A or B depending on measurement function, IEEE519, IEEE1159, IEEE1459 and EN50160
Clock/calendar  Leap years, 2 4-hour clock
Real-time clock accuracy  Not more than ± 1 s/day
Internal memory capacity for data  At least 2 GB
Maximum recording period  At least 31 days
Measurement time control  Automatic
Maximum number of events  Limited only by the size of the internal memory
Power requirements  100 to 2 40 V rms ± 10 %, 47-63 Hz, 40 W
Operating time during interruptions (internal UPS operation)  5 minutes per interruption, 60 minutes total operating time without recharging
Dimensions  215 mm x 310 mm x 35 mm (8.5 in x 12.2 in x 3.5 in)
Mass (weight)  6.3 kg (14 lb)
Input
Measurement types  One Phase Plus Neutral, One Phase IT No Neutral, One Phase Split Phase, Three Phase Wye, Three Phase Delta, Three Phase IT, Three Phase High Leg, Three Phase Open Leg, 2 Element Delta, 21/2 Element Wye
Input channels  Voltage: 4 channels, ac/dc
 Current: 5 channels
Voltage channels  Input resistance: 2 MΩ
 Input capacitance: < 2 0 pF
Current input characteristics  2 V rms = full scale, 1 MΩ Input Impedance for ferro CTs, low impedance for Flexi-CTs
Measuring method  Simultaneous digital sampling of voltage and current. Digital PLL synchronized sampling, internal frequency reference used during voltage drops.
Synchronization and sampling
PLL-synchronization source  The PLL synchronizes to the A-N voltage for wye power types, and to the A-B voltage for delta power types. All listed power types can be characterized as either wye or delta.
PLL lock range  42.5 to 69 Hz
Sampling frequency  Voltage and current: 2 56 samples/cycle Inter-harmonics per IEC 61000-4-7: 2 560 points/10 cycles (50 Hz), 3072 points/12 cycles (60 Hz) Transient Voltage: 5 MHz
A/D resolution  Voltage and current: 2 4 bits
 Transient voltage: 14 bits
Voltage and current measurements
Voltage measurement range  AC voltage: 1000 V rms ± 10 % over range
 DC voltage: ± 1000 V + 10 % over range
Voltage crest factor  3 or less
Current measurement range  Depends on current probe used
Current crest factor  4 or less
RMS voltage
Measurement type  True rms calculated continuously: every cycle, every 1/2 cycle, and every 10 or 12 cycles at 50 or 60 Hz respectively, as required by IEC 61000-4-30.
Measurement uncertainty  AC: ± 0.2 % reading ± 0.1 % full scale, above 50 V rms
 DC: ± 0.5 % reading ± 0.2 % full scale, above 50 V dc
RMS current
Measurement type  True rms calculated continuously: every cycle, every 1/2 cycle, and every 10 or 12 cycles at 50 or 60 Hz respectively, as required by standards
Transient voltage (impulse)
Measurement type  Waveshape sampling
Full scale  8000 V pk
Sample resolution  200 nS
Measurement uncertainty  ± 5 % reading ± 2 0 V (test parameters: 1000 V dc, 1000 V rms, 100 kHz)
Voltage swell (rms swell)
Measurement type  True rms (one cycle calculation by overlapping each half cycle - voltage between lines is measured for 3P3W lines and phase voltage is measured for 3P4W lines)
Displayed data  Amplitude and duration of swell
Measurement  Same as rms voltage
Voltage dip (rms sag)
Measurement type  True rms (one cycle calculation by overlapping each half cycle - voltage between lines is measured for 3P3W lines and phase voltage is measured for 3P4W lines)
Displayed data  Amplitude and duration of dip or interruption
Measurement  Same as rms voltage
Voltage dropout (interruption)
Measurement type  Same as voltage dip
LAN interface
Connector  RJ-45
Speed and type  10/100 Base-T, auto MDIX
Communications protocol  TCP/IP over Ethernet
Wireless controller interface
Connection  wireless (2.4 GHz radio)
Speed  up to 700 kbit/second
Communications protocol  Bluetooth SPP

Power Measurements
Power, battery life
Measurement type  True rms calculated continuously: every cycle, and every 10 or 12 cycles at 50 or 60 Hz respectively, as required by standards
Frequency
Measurement range  42.5 to 69 Hz
Measurement source  Same as PLL synchronization source
Measurement accuracy  ± 10 mHz (10 to 110 % of range, with sine wave)
Power Factor
Measurement range  0.000 to 1.000
Measurement accuracy  ± 1 digit from the calculation of each measured value (±3 digits for total)
Displacement power factor
Measurement method  Calculated from the phase difference between voltage fundamental and current fundamental
Measurement range  - 1.000 (leading) to + 1.000 (lagging)
Measurement accuracy  ± 0.5 % reading ± 2 % full scale ± 1 digit
Voltage unbalance and phase sequence
Measurement method  Positive sequence voltage divided by negative sequence voltage, per IEC 61000-4-30
Harmonic voltage and current
Analysis window  rectangular
Analysis order  1st to 50th order
Measurement accuracy  Voltage / Current: 1st to 2 0th orders: ± 0.5 % reading ± 0.2 % full scale, 2 1st to 50th orders: ± 1 % reading ± 0.3 % full scale (current sensor accuracy must be included for current and power)
Measurement method  IEC 61000-4-7
Inter-harmonic voltage and current (intermediate harmonics)
Analysis window  rectangular
Analysis orders  1.5 to 49.5th order
Measurement method  IEC 61000-4-7
Flicker
Measurement method  IEC 61000-4-15
 Plt for 2 hours and PSt for 10 minutes
Measuring range:  0,1 to 5 (25) depending on voltage level, modulation and frequency

Environmental Specifications
Environmental
Operating environment  Indoors or in covered area outdoors, up to 2 000 m altitude
Storage temperature and humidity  -20 °C to 50 °C, 80 % RH max, non-condensing
Operating temperature and humidity  0 °C to 40 °C, 80 % RH max, non-condensing
Maximum rated working voltage
Voltage terminals  1100 V rms
Voltage durability  5550 V rms ac for 1 minute, between voltage input terminals, voltage input terminals and current probes, and voltage input terminals and case (50/60 Hz, 1 mA sense current)
Enclosure protection  IP30 (per EN 60529)
Standards:
EMC  EN 61326-1:1997+A1:1998 Class A
 EN 61000-3-2:1995+A1:1998+A2:1998
 EN 61000-3-3:1995
Safety  EN 61010-1 2 nd Edition; 2 000
 Voltage input unit: Contamination Level 2 , Overvoltage Category 1000 V CAT III, 600 V CAT IV (anticipated overvoltage: 8000 V)
Model NameDescriptionPrice List
Fluke 1750Three-Phase Power Recorder

Includes

  • 1750 acquisition unit
  • ARCHOS 43 Internet Tablet  
  • 4 - 400A current probes (3140)
  • 5 Test leads and clips
  • SD memory card
  • Fluke Power View and Fluke Power Analyze software
  • Power cord with international plug set
  • Ethernet cable
  • Color localization set
  • Printed Getting Started manual
  • Product CD with software and user manual PDF
  • CS 1750/1760 Rugged transit softcase
On Request
Fluke 1750/B Three-Phase Basic Power Recorder

Includes all the items above with the exception of 4 x 400 A current probes (3140R)

On Request

Current clampsPrice List
3210-PR-TF1000A Flex Thin Flex Current Probe (24 inch/60cm)On Request
i40s-PR Clamp-on Current Transformer40A Clamp-on Current TransformerOn Request
3310-PR-TF5000A Flex Thin Flex Current Probe (24 inch/60cm)On Request
3312-PR-TF5000A Flex Thin Flex Current Probe (48 inch/122cm)On Request
i5s-PR Clamp-on Current Transformer5A Clamp-on Current TransformerOn Request