The most trusted tools in the world
Home  |  Products  |  Electrical Testers  |  Power Quality Tools  |  

Fluke VR1710 Single Phase Voltage Quality Recorder

 Fluke VR1710
The Fluke VR1710 Power Quality Recorder, is a single-phase, plug-in voltage quality recorder that offers an extremely easy-to-use solution for detecting and recording power quality problems, allowing for immediate action and less downtime. The VR1710 single phase recorder satisfies the needs of maintenance and facilities management personnel in industrial, utilities, and large service organizations where reliable power quality is essential to the operation of the business. Power quality parameters including RMS average, transients, flicker, and harmonics up to the 32nd are recorded using a user-selected average period from 1 seconds to 20 minutes.
  • Fast and easy recording of voltage trends, dropouts, and power quality – Easily pinpoint the root cause of single phase voltage problems
  • Extremely easy to use – Plug directly into the mains power socket and capture data
  • Continuous recording of all values with no gaps – Save testing time by getting the whole picture with one instrument that records both events and voltage
  • Clear graphical summary of data and quick overview of key power quality parameters – Take the guesswork out of diagnosing voltage quality problems
  • Min, Max, and Average RMS values (1/4 cycle) with time stamp – Quickly see what happened and when
  • Actual transient display (>100 μs) with time stamp – Identify power quality issues quickly with included graphical software
  • Flicker recording to EN 61000-4-15, individual harmonic and THD values with trends – Easily identify if the problem is power quality or equipment related
  • Statistical analysis of single phase voltage events - Reduces analysis time by tracking event quantities and magnitudes
  • Includes PowerLog software package for quick download, analysis, and automatic reporting – Save time by generating power quality reports automatically with pre-set templates
General specifications
Operating voltage
 70 V to 300 V
Min/Max/Avg RMS value
 Resolution 0.125 V
Number of events
 175,000
Dips/Interruptions
 Yes
Time resolution
 5 ms
Voltage resolution
 0.125 V
Over-voltages
 Yes
Frequency
 Yes
Harmonics measurement
 EN 61000-4-7 (up to 32nd)
Flicker measurement
 EN 61000-4-15
Number of recording channels
 1 Phase to Neutral
2 Phase/Neutral to Ground
Recording time
 1 day to 339 days depending on average time from 1 second to 20 minutes
Transients
 Yes
Frequency range
 50 Hz ± 1 Hz and 60 Hz ± 1 Hz
Safety category rating
 CAT II 300 V
Model NameDescriptionPrice List
Fluke VR1710 VOLTAGE QUALITY RECORDER

Fluke VR1710 includes:

  • Plug-in Fluke VR1710
  • USB cable
  • PowerLog software CD
  • Universal power cord adapters
On Request