Calculate energy loss in dollars
The Fluke 434 II Energy Analyzer is the ideal tool for energy logging. Utilizing the new Energy Loss Calculator function, the 434 II measures the fiscal cost of energy wasted due to poor power quality. This energy monetization capability allows you to identify the most energy-wasteful areas of your facility so you can determine potential energy saving solutions. Add basic power quality measurements to the package and you’re got yourself one powerful troubleshooting tool.
Applications
- Energy monetization – calculate the fiscal cost of energy waste due to poor power quality
- Energy assessment – quantify the before and after installation improvements in energy consumption to justify energy saving devices
- Frontline troubleshooting – quickly diagnose problems on-screen to get your operation back online
- Predictive maintenance – detect and prevent power quality issues before they cause downtime
- Long-term analysis – uncover hard-to-find or intermittent issues
- Load studies – verify electrical system capacity before adding loads
|

|
- Energy loss calculator: Classic active and reactive power measurements, unbalance and harmonic power, are quantified to pinpoint the fiscal costs of energy losses.
- Troubleshoot real-time: Analyze the trends using the cursors and zoom tools.
- Highest safety rating in the industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance.
- Measure all three phases and neutral: With included four flexible current probes with enhanced thin flex design to fit into the tightest places.
- Automatic Trending: Every measurement is always automatically recorded, without any set-up.
- System-Monitor: Ten power quality parameters on one screen according to EN50160 power quality standard.
- Logger function: Configure for any test condition with memory for up to 600 parameters at user defined intervals.
- View graphs and generate reports: With included analysis software.
- Battery life: Seven hours operating time per charge on Li-ion battery pack.
 |
Unified Power Measurement
Fluke’s patented Unified Power Measurement system (UPM) provides the most comprehensive view of power available, measure:
- Parameters of Classical Power (Steinmetz 1897) and IEEE 1459-2000 Power
- Detailed Loss Analysis
- Unbalance Analysis
These UPM calculations are used to quantify the fiscal cost of energy loss caused by power quality issues. The calculations are computed, along with other facility-specific information, by an Energy Loss Calculator that ultimately determines how much money a facility loses due to wasted energy. |
| |
|
 |
AutoTrend - Quickly see the trend
Unique AutoTrend gives you fast insight into changes over time. Every displayed reading is automatically and continuously recorded without having to set up threshold levels or interval times, or having to manually start the process. You can quickly view trends in voltage, current, frequency, power, harmonics or flicker on all three phases plus neutral. And you can analyze the trends using the cursors and zoom function – even while background recording continues. |
SystemMonitor - Check performance against EN50160 with ease
With a single push of a button, the unique System-Monitor gives you an overview of power system performance, and checks the compliance of incoming power to EN50160 limits or to your own custom specifications. The overview is shown on a single screen, with color-coded bars clearly indicating which parameters fall outside the limits.

The System-Monitor overview screen gives instant insight into whether the voltage, harmonics, flicker, frequency and the number of dips and swells fall outside the set limits. A detailed list is given of all events falling outside the set limits.
|
|
|
| Logging function allows you to customize measurement selections and provides instantaneous analysis of user-selectable parameters. |
Measure and record power (W), VA and VARs. The 434 adds the ability to record energy consumption. |
Track harmonics up to the 50th, and measure and record THD in accordance with IEC61000-4-7 requirements |
|
Product specifications
|
| |
Model |
Measurement range |
Resolution |
Accuracy |
| Volt |
| Vrms (ac+dc) |
434-II |
1 V to 1000 V phase to neutral
|
0.1 V |
± 0.5% of nominal voltage**** |
| Vpk |
|
1 Vpk to 1400 Vpk |
1 V |
5% of nominal voltage |
| Voltage Crest Factor (CF) |
|
1.0 > 2.8 |
0.01 |
± 5 % |
| Vrms½ |
434-II |
1 V to 1000 V phase to neutral |
0.1 V |
± 1% of nominal voltage |
| Vfund |
434-II |
1 V to 1000 V phase to neutral |
0.1 V
|
± 0.5% of nominal voltage |
| Amps (accuracy excluding clamp accuracy) |
| Amps (ac +dc) |
i430-Flex 1x |
5 A to 6000 A |
1 A |
± 0.5% ± 5 counts |
| i430-Flex 10x |
0.5 A to 600 A |
0.1 A |
± 0.5% ± 5 counts |
| 1mV/A 1x |
5 A to 2000 A |
1A |
± 0.5% ± 5 counts |
| 1mV/A 10x |
0.5 A A to 200 A (ac only) |
0.1 A |
± 0.5% ± 5 counts |
| Apk |
i430-Flex |
8400 Apk |
1 Arms |
± 5 % |
| 1mV/A |
5500 Apk |
1 Arms |
± 5 % |
| A Crest Factor (CF) |
|
1 to 10 |
0.01 |
± 5 % |
| Amps½ |
i430-Flex 1x |
5 A to 6000 A |
1 A |
± 1% ± 10 counts |
| i430-Flex 10x |
0.5 A to 600 A |
0.1 A |
± 1% ± 10 counts |
| 1mV/A 1x |
5 A to 2000 A |
1A |
± 1% ± 10 counts |
| 1mV/A 10x |
0.5 A A to 200 A (ac only) |
0.1 A |
± 1% ± 10 counts |
| Afund |
i430-Flex 1x |
5 A to 6000 A |
1 A |
± 0.5% ± 5 counts |
| i430-Flex 10x |
0.5 A to 600 A |
0.1 A |
± 0.5% ± 5 counts |
| 1mV/A 1x |
5 A to 2000 A |
1A |
± 0.5% ± 5 counts |
| 1mV/A 10x |
0.5 A A to 200 A (ac only) |
0.1 A |
± 0.5% ± 5 counts |
| Hz |
| Hz |
Fluke 434 @ 50 Hz nominal |
42.50 Hz to 57.50 Hz
|
0.01 Hz
|
± 0.01 Hz |
| Fluke 434 @ 60 Hz nominal |
51.00 Hz to 69.00 Hz |
0.01 Hz |
± 0.01 Hz |
| Power |
| Watts (VA, var) |
i430-Flex
|
max 6000 MW |
0.1 W to 1 MW |
± 1% ± 10 counts |
| 1 mV/A |
max 2000 MW |
0.1 W to 1 MW |
± 1% ± 10 counts |
| Power factor (Cos j/DPF) |
|
0 to 1 |
0.001 |
± 0.1% @ nominal load conditions |
| Energy |
| kWh (kVAh, kvarh) |
i430-Flex 10x |
Depends on clamp scaling and V nominal |
± 1% ± 10 counts |
| Energy loss |
i430-Flex 10x |
Depends on clamp scaling and V nominal |
± 1% ± 10 counts Excluding line resistance accuracy |
| Harmonics |
| Harmonic order (n) |
|
DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7 |
| Inter-harmonic order (n) |
|
OFF, 1 to 50 Grouping: Harmonic and Interharmonic subgroups according to IEC 61000-4-7 |
| Volts |
%f |
0.0 % to 100 % |
0.1 % |
± 0.1% ± n x 0.1 % |
| %r |
0.0 % to 100 % |
0.1 % |
± 0.1% ± n x 0.4 % |
| Absolute |
0.0 to 1000 V |
0.1 V |
± 5% * |
| THD |
0.0 % to 100 % |
0.1 % |
± 2.5 % |
| Amps |
%f |
0.0 % to 100 % |
0.1 % |
± 0.1% ± n x 0.1% |
| %r |
0.0 % to 100 % |
0.1 % |
± 0.1% ± n x 0.4 % |
| Absolute |
0.0 to 600 A |
0.1 A |
± 5% ± 5 counts |
| THD |
0.0 % to 100 % |
0.1 % |
± 2.5 % |
| Watts |
%f or %r |
0.0 % to 100 % |
0.1 % |
± n x 2% |
| Absolute |
Depends on clamp scaling and V nominal |
— |
± 5% ± n x 2 % ± 10 counts |
| THD |
0.0 % to 100 % |
0.1 % |
± 5 % |
| Phase Angle |
|
-360° to +0° |
1° |
± n x 1° |
| Flicker |
| Plt, Pst, Pst(1min) Pinst |
|
0.00 to 20.00 |
0.01 |
± 5 % |
| Unbalance |
| Volts |
% |
0.0 % to 20.0 % |
0.1 % |
± 0.1 % |
| Amps |
% |
0.0 % to 20.0 % |
0.1% |
± 1 % |
| Mains signaling |
| Threshold levels |
|
Threshold, limits and signaling duration is programable for two signaling frequencies |
— |
— |
| Signaling frequency |
|
60 Hz to 3000 Hz |
0.1 Hz |
|
| Relative V% |
|
0 % to 100 % |
0.10 % |
± 0.4 % |
| Absolute V3s (3 second avg.) |
|
0.0 V to 1000 V |
0.1 V |
± 5 % of nominal voltage |
General specifications
|
| Case |
Design Rugged, shock proof with integrated protective holster Drip and dust proof IP51 according to IEC60529 when used in tilt stand position Shock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g 2 /Hz according to MIL-PRF-28800F Class 2 |
| Display |
Brightness: 200 cd/m 2 typ. using power adapter, 90 cd/m 2 typical using battery power Size: 127 mm x 88 mm (153 mm/6.0 in diagonal) LCD Resolution: 320 x 240 pixels Contrast and brightness: user-adjustable, temperature compensated |
| Memory |
8GB SD card (SDHC compliant, FAT32 formatted) standard, upto 32GB optionally Screen save and multiple data memories for storing data including recordings (dependent on memory size) |
| Real-time clock |
Time and date stamp for Trend mode, Transient display, System Monitor and event capture |
Environmental
|
| Operating temperature |
0 °C ~ +40 °C; +40 °C ~ +50 °C excl. battery |
| Storage temperature |
-20 °C ~ +60 °C |
| Humidity |
+10 °C ~ +30 °C: 95% RH non-condensing
+30 °C ~ +40 °C: 75% RH non-condensing
+40 °C ~ +50 °C: 45% RH non-condensing |
| Maximum operating altitude |
Up to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V
Up to 3,000 m (10,000 ft) for CAT III 600 V, CAT II 1000 V
Maximum storage altitude 12 km (40,000 ft) |
| Electro-Magnetic-Compatibility (EMC) |
EN 61326 (2005-12) for emission and immunity |
| Interfaces |
mini-USB-B, Isolated USB port for PC connectivity SD card slot accessible behind instrument battery |
| Warranty |
Three years (parts and labor) on main instrument, one year on accessories |
View full family specifications »
* ± 5 % if ≥ 1 % of nominal voltage ± 0.05 % of nominal voltage if < 1% of nominal voltage
** 50Hz/60Hz nominal frequency according to IEC 61000-4-30
*** 400Hz measurements are not supported for Flicker, Mains Signaling and Monitor Mode.
****for nominal voltage 50 V to 500 V
|
| Model Name | Description | Price List | | Fluke 434 II |
Three-Phase Energy Analyzer
Included accessories
- BC430 Power Adapter
- International plug adapter set
- BP290 (Single capacity Li-ion battery) 28 Wh (8 hours or more)
- TLS430 Test lead and Alligator clip set
- WC100 color coding clips and regional decals
- i430flex-TF, 24 inch (61 cm) length, 4 flexible current probes
- 8 GB SD card
- PowerLog on CD (includes operator manuals in PDF format)
- USB cable A - Mini B
- C1740 Soft Case
|
| Cables and Hardware | | GPS430 | GPS430 Time Synchronization Module |
| Clips | | AC285 | AC285 SureGripTM Alligator Clips |
| Batteries, Chargers and Adapters | | BP290 | 2400 mAh Li-ion battery for Fluke 190-series II | | BP291 | 4800 mAh High capacity Li-ion battery ) for Fluke 190-seriesII | | BC430 | BC430 Line Voltage Adapter/Battery Charger | | EBC290 | External Battery Charger for charging BP290 or BC291 outside the instrument |
| Cases and Holsters | | C435 | C435 Hard Rolling Case |
| Current Clamps | | 90i-610s | 90i-610s 1A to 600A AC/DC Current Probe | | i30s | Fluke i30s AC/DC Current Clamp | | i1000s | i1000s AC Current Probe | | i200s | i200s AC Current Clamp | | i3000s | i3000s AC Current Clamp | | i400s | i400s AC Current Clamp | | i5sPQ3 | i5sPQ3, 5 A ac Current Clamps, 3-pack |
| Options | | HH290 | Hanging Hook for ScopeMeter 190-Series II |
| Test Leads | | TLS430 | Fluke TLS430 – Test Leads and Alligator Clips (4 black, 1 green) | | WC100 | WC100 Color Localization Set |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|