Safer than traditional solenoid testers and fully compliant with NFPA 70E*
The T+PRO and T+ Electrical Testers offer all the functionality that electricians look for in volt meters and voltage and continuity testers:
- Both have three ways to detect ac/dc voltage: light, sound, and vibration
- Both offer the added functionality of a GFCI trip and continuity beeper, plus the convenience of a built-in flashlight
- The T+PRO Electrical Tester comes with a rotary field indicator for troubleshooting three-phase systems, resistance measurement to 9.99 KOhms, as well as a backlit LCD display for easier viewing
|
Safer than traditional solenoid testers:
- Solid-state tester design
- CAT IV 600 V, CAT III 1000 V rated
- Complies with NFPA 70E*
|
The ruggedness and reliability that customers have come to expect from Fluke
* When used properly per Article 110.9 Use of Equipment (A) Test Instruments and Equipment.
|
Fluke T+PRO / T+ Electrical Testers
4.5
5
2
2
This is a good tester
I like the tester but I dropped it and now the screen is broke it still works I can read a little bit of the screen but with my job I need the hole screen I wish I could buy a screen for it
October 11, 2012
very good features easy to use
The T+Pro tester is well built/easy to use and very reliable I have owned and used for years
June 15, 2012
|
Added functionality available only on the T+PRO:
- Backlit LCD display for easier viewing
- Display resolution of 0.1 V, ideal for troubleshooting low-voltage lighting
- Resistance (Ohms) to 9.99 kOhms
- Rotary Field Indication
- Display Hold for easier viewing in hard-to-test areas
|
Features and benefits of the T+PRO and T+:
- 3 forms of ac/dc voltage indication: light, sound, and vibration for added user protection and convenience
- Detect live voltage even when the batteries are dead
- Extra heavy-duty, replaceable test leads for more flexibility and durability
- CAT IV 600 V, CAT III 1000 V rated for added user protection
- Continuity beeper
- Bright LED flashlight for work in poorly lit areas
- GFCI Trip
- On/Off switchable beeper, selectable according to your environment
- Compliant with latest NFPA 70E recommendations*
- Replaceable test probes for added flexibility and convenience
- Convenient probe storage on the back
- Probe holder for easier testing
- Hazardous voltage warning light for added user protection
- Test lead strap included for better test lead management
- AC/DC Voltage: 12 V – 600 V on LED bar, 10.2 V – 600 V on LCD (LCD on T+PRO only)
- Auto-off saves battery power
- 2-year warranty
|
* When used properly per Article 110.9 Use of Equipment (A) Test Instruments and Equipment
|
| Specifications |
| Temperature |
| Operating |
-10 °C to 55 °C (14 °F to 131 °F) |
| Storage |
-30 °C to 60 °C (-22 °F to 140 °F) |
| | Relative humidity |
|
0 °C to 30 °C (32 °F to 86 °F): 90 % |
|
30 °C to 40 °C (86 °F to 104 °F): 75 % |
|
40 °C to 50 °C (104 °F to 122 °F): 45 % |
| | Altitude |
| Operating |
2,000 m (approx. 6,561.6 ft) |
| Storage |
10,000 m (approx. 32,808.4 ft) |
| | Battery type/life | | | Shock, vibration |
|
Sinusoidal vibration per MIL-PRF-28800F for a Class 2 instrument |
| | Safety |
|
ISA-82.02.01 (IEC 61010-1 Mod) Second Edition, CAN/CSA-C22.2 No. 61010-1
Second Edition, IEC 61010 - 1 to 1000 V CAT III/600 V CAT IV |
|
Compliance to NFPA 70E* |
| | AC Bandwidth | | | Maximum working voltage | | | Maximum measurable voltage | | | Duty cycle |
|
Indefinitely for voltages up to 240 V |
|
For voltages between 240 V and 600 V the duty cycle is 30 s on / 300 s off |
|
For voltages above 240 V the tester must connect to a voltage source only for a
MAXIMUM of 30 s and then disconnect for a MINIMUM of 300 s |
| | Voltage hazard LED |
|
LEDs turn on at voltages > 30 V ac/dc ± 35 % |
| | LED voltage indication levels |
|
12 V, 24 V, 48 V, 120 V, 208 V, 240 V, 277 V, 480 V, 600 V |
| | LED voltage indication levels for
Canadian version |
|
12 V, 24 V, 48 V, 120 V, 208 V, 240 V, 347 V, 480 V, 600 V |
| | LEDs |
|
LEDs turn on between 90 % and 100 % of the indicated voltage on the LED, except
for the 12 V LED which turns on between 50 % and 100 % |
| | LCD Accuracy on T+PRO only |
| AC voltage |
± (3 % rdg + 2 digits) |
| DC voltage |
± (2 % rdg + 2 digits) |
| Resistance |
± (5 % rdg + 3 digits) |
| | LCD Resolution |
|
0.1 V for voltages < 50 V, 1 V for voltages ≥ 50 V |
|
0.01 kΩ for resistance measurement (For T+PRO Only) |
| | GFCI Test current |
|
100 V - 150 V @ 6 mA - 9 mA ac, 150 V - 240 V < 12 mA |
| | Standard input test current | | | Size (HxWxL) |
|
1.3 in x 2.15 in x 7.6 in (3.3 cm x 5.46 cm x 19.3 cm ) |
| | Weight | |
*When used properly per Article 110.9 Use of Equipment (A) Test Instruments and Equipment.
|
| Model Name | Description | Price List | Buy it | | T+ |
T+ ELECTRICAL TESTER Includes:
- User manual
- Test lead wrap
- TP2 test probes
|
|  | | | T+PRO |
T+ PRO ELECTRICAL TESTER Includes:
- User manual
- Test lead wrap
- TP2 test probes
|
|  | | | T+PRO-1AC KIT | T+PRO-1AC KIT, ELECTRICAL TESTER AND VOLTAGE DETECTOR KIT
|  | | | T+ CAN |
T+ CAN, ELECTRICAL TESTER*
*This model is only available in Canada
|  | | | T+PRO CAN |
T+ PRO CAN, ELECTRICAL TESTER*
*This model is only available in Canada
|  | | | T+PRO CAN-1AC KIT |
T+PRO CAN-1AC KIT, ELECTRICAL TESTER AND VOLTAGE DETECTOR KIT*
*This model is only available in Canada
|  | |
| Clips | Buy it | | AC220 | AC220 SureGrip™ Alligator Clips |  |  | | AC280 | AC280 SureGrip™ Hook Clips |  |  | | AC285 | AC285 SureGrip™ Alligator Clips |  |  |
| Test Probes | Buy it | | TP1 | TP1 Slim Reach Test Probes |  |  | | TP2 | TP2 Slim Reach Test Probes |  |  |
|
|
|
|
|
|
|
|
|